• CHAPTER 5 [RE]
    EXISTING BUILDINGS

    SECTIONR501
    GENERAL

    R501.1Scope.

    The provisions of this chapter shall control the alteration, repair, addition and change of occupancy of existing buildings and structures.

    R501.1.1Additions, alterations, or repairs: General.

    Additions, alterations, or repairs to an existing building, building system or portion thereof shall comply with Section R502, R503 or R504. Unaltered portions of the existing building or building supply system shall not be required to comply with this code.

    R501.2Existing buildings.

    Except as specified in this chapter, this code shall not be used to require the removal, alteration or abandonment of, nor prevent the continued use and maintenance of, an existing building or building system lawfully in existence at the time of adoption of this code.

    R501.3Maintenance.

    Buildings and structures, and parts thereof, shall be maintained in a safe and sanitary condition. Devices and systems that are required by this code shall be maintained in conformance to the code edition under which installed. The owner or the owner’s authorized agent shall be responsible for the maintenance of buildings and structures. The requirements of this chapter shall not provide the basis for removal or abrogation of energy conservation, fire protection and safety systems and devices in existing structures.

    R501.4Compliance.

    Alterations, repairs, additions and changes of occupancy to, or relocation of, existing buildings and structures shall comply with the provisions for alterations, repairs, additions and changes of occupancy or relocation, respectively, in the Florida Building Code, Residential; Florida Building Code, Building; Florida Fire Prevention Code; Florida Building Code, Fuel Gas; Florida Building Code, Mechanical; Florida Building Code, Plumbing, and NFPA 70.

    R501.5New and replacement materials.

    Except as otherwise required or permitted by this code, materials permitted by the applicable code for new construction shall be used. Like materials shall be permitted for repairs, provided hazards to life, health or property are not created. Hazardous materials shall not be used where the code for new construction would not permit their use in buildings of similar occupancy, purpose and location.

    R501.6Historic buildings.

    No provision of this code relating to the construction, repair, alteration, restoration and movement of structures, and change of occupancy shall be mandatory for historic buildings provided a report has been submitted to the code official and signed by the owner, a registered design professional, or a representative of the State Historic Preservation Office or the historic preservation authority having jurisdiction, demonstrating that compliance with that provision would threaten, degrade or destroy the historic form, fabric or function of the building.

    R501.7Building systems and components.

    Thermal efficiency standards are set for the following building systems and components where new products are installed or replaced in existing buildings, and for which a permit must be obtained. New products shall meet the minimum efficiencies allowed by this code for the following systems and components:

    • Heating, ventilating or air-conditioning systems;

    • Service water or pool heating systems;

    • Lighting systems; and

    • Replacement fenestration.

    Exceptions:

    1. 1.Where part of a functional unit is repaired or replaced. For example, replacement of an entire HVAC system is not required because a new compressor or other part does not meet code when installed with an older system.

    2. 2.If the unit being replaced is itself a functional unit, such as a condenser, it does not constitute a repair. Outdoor and indoor units that are not designed to be operated together must meet the U.S. Department of Energy certification requirements contained in Section R303.1.2. Matched systems are required; this match may be verified by any one of the following means:

      1. a.AHRI data

      2. b.Accredited laboratory

      3. c.Manufacturer’s letter

      4. d.Letter from registered P.E. State of Florida

    3. 3.Where existing components are utilized with a replacement system, such as air distribution system ducts or electrical wiring for lights, such components or controls need not meet code if meeting code would require that component’s replacement.

    4. 4.Replacement equipment that would require extensive revisions to other systems, equipment or elements of a building where such replacement is a like-for-like replacement, such as through-the-wall condensing units and PTACs, chillers and cooling towers in confined spaces.

    R501.7.1Existing equipment efficiencies.

    Existing cooling and heating equipment in residential applications need not meet the minimum equipment efficiencies, including system sizing and duct sealing.

    SECTIONR502
    ADDITIONS

    R502.1General.

    Additions to an existing building, building system or portion thereof shall conform to the provisions of this code as those provisions relate to new construction without requiring the unaltered portion of the existing building or building system to comply with this code. Additions shall not create an unsafe or hazardous condition or overload existing building systems. An addition shall be deemed to comply with this code where the addition alone complies, where the existing building and addition comply with this code as a single building, or where the building with the addition uses no more energy than the existing building. Additions shall be in accordance with Section R502.1.1, R502.1.2 or R502.1.3.

    R502.1.1Prescriptive compliance.

    Additions shall comply with Sections R502.1.1.1 through R502.1.1.4.

    R502.1.1.1Building envelope.

    New building envelope assemblies that are part of the addition shall comply with Sections R402.1, R402.2, R402.3.1 through R402.3.5, and R402.4.

    Exception: Where nonconditioned space is changed to conditioned space, the building envelope of the addition shall comply where the UA, as determined in Section 402.1.5, of the existing building and the addition, and any alterations that are part of the project, is less than or equal to UA generated for the existing building.

    R502.1.1.2Heating and cooling systems.

    New heating, cooling and duct systems that are part of the addition shall comply with Sections R403.1, R403.2, R403.3, R403.5 and R403.6.

    Exception: Where ducts from an existing heating and cooling system are extended to an addition, duct systems with less than 40 linear feet (12.19 m) in unconditioned spaces shall not be required to be tested in accordance with Section R403.3.3.

    R502.1.1.3Service hot water systems.

    New service hot water systems that are part of the addition shall comply with Section R403.4.

    R502.1.1.4Lighting.

    New lighting systems that are part of the addition shall comply with Section R404.1.

    R502.1.2 Simulated performance alternative.

    The addition or existing building and addition together shall comply with Section R405 in its entirety.

    R502.1.3 Energy Rating Index compliance alternative.

    The addition or existing building and addition together shall comply with Section R406 in its entirety.

    SECTIONR503
    ALTERATIONS

    R503.1General.

    Alterations to any building or structure shall comply with the requirements of the code for new construction. Alterations shall be such that the existing building or structure is no less conforming to the provisions of this code than the existing building or structure was prior to the alteration.

    Alterations to an existing building, building system or portion thereof shall conform to the provisions of this code as they relate to new construction without requiring the unaltered portions of the existing building or building system to comply with this code. Alterations shall not create an unsafe or hazardous condition or overload existing building systems. Alterations shall be such that the existing building or structure uses no more energy than the existing building or structure prior to the alteration. Alterations to existing buildings shall comply with Sections R503.1.1 through R503.2.

    R503.1.1Building envelope.

    Building envelope assemblies that are part of the alteration shall comply with Section R402.1.2 or R402.1.4, Sections R402.2.1 through R402.2.13, R402.3.1, R402.3.2, R402.4.3 and R402.4.5.

    Exception: The following alterations need not comply with the requirements for new construction provided the energy use of the building is not increased:

    1. 1.Storm windows installed over existing fenestration.

    2. 2.Existing ceiling, wall or floor cavities exposed during construction provided that these cavities are filled with insulation.

    3. 3.Construction where the existing roof, wall or floor cavity is not exposed.

    4. 4.Roof recover.

    5. 5.Roofs without insulation in the cavity and where the sheathing or insulation is exposed during reroofing shall be insulated either above or below the sheathing.

    6. 6.Surface-applied window film installed on existing single pane fenestration assemblies to reduce solar heat gain provided the code does not require the glazing or fenestration assembly to be replaced.

    7. 7.Swimming pool filtration pumps and motors.

    R503.1.1.1 Replacement fenestration.

    Where some or all of an existing fenestration unit is replaced with a new fenestration product, including sash and glazing, the replacement fenestration unit shall meet the applicable requirements for U-factor and SHGC as provided in Table R402.1.2.

    R503.1.2Heating and cooling systems.

    New heating, cooling and duct systems that are part of the alteration shall comply with Sections R403.1, R403.2, R403.3 and R403.6.

    Exception: Where ducts from an existing heating and cooling system are extended, duct systems with less than 40 linear feet (12.19 m) in unconditioned spaces shall not be required to be tested in accordance with Section R403.3.3.

    R503.1.3Service hot water systems.

    New service hot water systems that are part of the alteration shall comply with Section R403.4.

    R503.1.4 Lighting.

    New lighting systems that are part of the alteration shall comply with Section 404.1.

    Exception: Alterations that replace less than 50 percent of the luminaires in a space, provided that such alterations do not increase the installed interior lighting power.

    R503.2Change in space conditioning.

    Any nonconditioned or low-energy space that is altered to become conditioned space shall be required to be brought into full compliance with this code.

    Exception: Where the simulated performance option in Section R405 is used to comply with this section, the annual energy cost of the proposed design is permitted to be 110 percent of the annual energy cost otherwise allowed by Section R405.3.

    SECTIONR504
    REPAIRS

    R504.1General.

    Buildings, structures and parts thereof shall be repaired in compliance with Section R501.3 and this section. Work on nondamaged components necessary for the required repair of damaged components shall be considered part of the repair and shall not be subject to the requirements for alterations in this chapter. Routine maintenance required by Section R501.3, ordinary repairs exempt from permit, and abatement of wear due to normal service conditions shall not be subject to the requirements for repairs in this section.

    R504.2Application.

    For the purposes of this code, the following shall be considered repairs:

    1. 1.Glass-only replacements in an existing sash and frame.

    2. 2.Roof repairs.

    3. 3.Repairs where only the bulb and/or ballast within the existing luminaires in a space are replaced provided that the replacement does not increase the installed interior lighting power.

    SECTIONR505
    CHANGE OF OCCUPANCY OR USE

    R505.1General.

    Spaces undergoing a change in occupancy that would result in an increase in demand for either fossil fuel or electrical energy shall comply with this code.

    R505.2General.

    Any space that is converted to a dwelling unit or portion thereof from another use or occupancy shall comply with this code.

    Exception: Where the simulated performance option in Section R405 is used to comply with this section, the annual energy cost of the proposed design is permitted to be 110 percent of the annual energy cost otherwise allowed by Section R405.3.