CHAPTER 6
TYPES OF CONSTRUCTION

SECTION 601
GENERAL

601.1 Scope.

The provisions of this chapter shall control the classification of buildings as to type of construction.

TABLE 601

FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (hours)

BUILDING ELEMENT TYPE I TYPE II TYPE III TYPE IV TYPE V
A B Ad B Ad B HT Ad B
Structural framea                  
   Including columns, girders, trusses 3b 2b 1 0 1 0 HT 1 0
Bearing walls                  
   Exterior 3 2 1 0 2 2 2 1 0
   Interior 3b 2b 1 0 1 0 1/HT 1 0
Nonbearing walls and partitions  
   Exterior See Table 602
   Interiore See Section 602
Floor construction 2 2 1 0 1 0 HT 1 0
   Including supporting beams and joists
Roof construction 11/2c 1c 1c 0 1c 0 HT 1c 0
   Including supporting beams and joists

For SI: 1 foot = 304.8 mm.

  1. a. The structural frame shall be considered to be the columns and the girders, beams, trusses and spandrels having direct connections to the columns and bracing members designed to carry gravity loads. The members of floor or roof panels which have no connection to the columns shall be considered secondary members and not a part of the structural frame.

  2. b. Roof supports: Fire-resistance ratings of structural frame and bearing walls are permitted to be reduced by 1 hour where supporting a roof only.

  3. c.

    1. 1. Except in Factory-Industrial (F-I), Hazardous (H), Mercantile (M) and Moderate-Hazard Storage (S-1) occupancies, fire protection of structural members shall not be required, including protection of roof framing and decking where every part of the roof construction is 20 feet or more above any floor immediately below. Fire-retardant-treated wood members shall be allowed to be used for such unprotected members.

    2. 2. In all occupancies, heavy timber shall be allowed where a 1-hour or less fire-resistance rating is required.

    3. 3. In Type I and Type II construction, fire-retardant-treated wood shall be allowed in buildings not over two stories including girders and trusses as part of the roof construction.

  4. d. An approved automatic sprinkler system in accordance with Section 903.3.1.1 shall be allowed to be substituted for 1-hour fire-resistance-rated construction, provided such system is not otherwise required by other provisions of the code or used for an allowable area increase in accordance with Section 506.3 or an allowable height increase in accordance with Section 504.2. The 1-hour substitution for the fire resistance of exterior walls shall not be permitted.

  5. e. For interior nonbearing partitions in Type IV construction, also see Section 602.4.6.

  6. f. Not less than the fire-resistance rating based on fire separation distance (see Table 602).

SECTION 602
CONSTRUCTION CLASSIFICATION

602.1 General.

Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. The building elements shall have a fire resistance rating not less than that specified in Table 601 and exterior walls shall have a fire-resistance rating not less than that specified in Table 602.

TABLE 602

FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCEa

FIRE SEPARATION DISTANCE (feet) TYPE OF CONSTRUCTION GROUP H GROUP F-1, M, S-1 GROUP A, B, E, F-2, I, Rb, S-2, U
< 5c All 3 2 1
≥ 5 IA 3 2 1
< 10 Others 2 1 1
≥ 10 IA, IB 2 1 1
< 30 IIB, VB 1 0 0
  Others 1 1 1
≥ 30 All 0 0 0

For SI: 1 foot = 304.8 mm.

  1. a. Load-bearing exterior walls shall also comply with the fire-resistance rating requirements of Table 601.

  2. b. Group R-3 and Group U when used as accessory to Group R-3, as applicable in Section 101.2 shall not be required to have a fire-resistance rating where fire separation distance is 3 feet or more.

  3. c. See Section 503.2 for party walls.

602.1.1 Minimum requirements.

A building or portion thereof shall not be required to conform to the details of a type of construction higher than that type, which meets the minimum requirements based on occupancy even though certain features of such a building actually conform to a higher type of construction.

602.2 Types I and II.

Types I and II construction are those types of construction in which the building elements listed in Table 601 are of noncombustible materials.

602.3 Type III.

Type III construction is that type of construction in which the exterior walls are of noncombustible materials and the interior building elements are of any material permitted by this code. Fire-retardant-treated wood framing complying with Section 2303.2 shall be permitted within exterior wall assemblies of a 2-hour rating or less.

602.4 Type IV.

Type IV construction (Heavy Timber, HT) is that type of construction in which the exterior walls are of noncombustible materials and the interior building elements are of solid or laminated wood without concealed spaces. The details of Type IV construction shall comply with the provisions of this section. Fire-retardant-treated wood framing complying with Section 2303.2 shall be permitted within exterior wall assemblies with a 2-hour rating or less.

602.4.1 Columns.

Wood columns shall be sawn or glued laminated and shall not be less than 8 inches (203 mm), nominal, in any dimension where supporting floor loads and not less than 6 inches (152 mm) nominal in width and not less than 8 inches (203 mm) nominal in depth where supporting roof and ceiling loads only. Columns shall be continuous or superimposed and connected in an approved manner.

602.4.2 Floor framing.

Wood beams and girders shall be of sawn or glued laminated timber and shall be not less than 6 inches (152 mm) nominal in width and not less than 10 inches (254 mm) nominal in depth. Framed sawn or glued laminated timber arches, which spring from the floor line and support floor loads, shall be not less than 8 inches (203 mm) nominal in any dimension. Framed timber trusses supporting floor loads shall have members of not less than 8 inches (203 mm) nominal in any dimension.

602.4.3 Roof framing.

Wood-framed or glued laminated-arches for roof construction, which spring from the floor line or from grade and do not support floor loads shall have members not less than 6 inches (152 mm) nominal in width and have less than 8 inches (203 mm) nominal in depth for the lower half of the height and not less than 6 inches (152 mm) nominal in depth for the upper half. Framed or glued laminated arches for roof construction that spring from the top of walls or wall abutments, framed timber trusses and other roof framing, which do not support floor loads, shall have members not less than 4 inches (102 mm) nominal in width and not less than 6 inches (152 mm) nominal in depth. Spaced members may be composed of two or more pieces not less than 3 inches (76 mm) nominal in thickness where blocked solidly throughout their intervening spaces or where spaces are tightly closed by a continuous wood cover plate of not less than 2 inches (51 mm) nominal in thickness secured to the underside of the members. Splice plates shall be not less than 3 inches (76 mm) nominal in thickness. Where protected by approved automatic sprinklers under the roof deck, framing members shall be not less than 3 inches (76 mm) nominal in width.

602.4.4 Floors.

Floors shall be without concealed spaces. Wood floors shall be of sawn or glued laminated planks, splined, or tongue-and-groove, of not less than 3 inches (76 mm) nominal in thickness covered with 1-inch (25 mm) nominal dimension tongue-and-groove flooring, laid crosswise or diagonally, or 0.5-inch (12.7 mm) particle board or planks not less than 4 inches (102 mm) nominal in width set on edge close together and well spiked and covered with 1-inch (25 mm) nominal dimension flooring or 1/2-inch (12.7 mm) wood structural panel or 0.5-inch (12.7 mm) particle board. The lumber shall be laid so that no continuous line of joints will occur except at points of support. Floors shall not extend closer than 0.5 inch (12.7 mm) to walls. Such 0.5-inch (12.7 mm) space shall be covered by a molding fastened to the wall and so arranged that it will not obstruct the swelling or shrinkage movements of the floor. Corbeling of masonry walls under the floor may be used in place of molding.

602.4.5 Roofs.

Roofs shall be without concealed spaces and wood roof decks shall be sawn or glued laminated, splined or tongue-and-groove plank, not less than 2 inches (51 mm) thick, 11/8 (32 mm)-inch-thick wood structural panel (exterior glue), or of planks not less than 3 inches (76 mm) nominal wide, set on edge close together and laid as required for floors. Other types of decking may be used if providing equivalent fire resistance and structural properties.

602.4.6 Partitions.

Partitions shall be of solid wood construction formed by not less than two layers of 1-inch (25 mm) matched boards or laminated construction 4 inches (102 mm) thick, or of 1-hour fire-resistance-rated construction.

602.4.7 Exterior structural members.

Where a horizontal separation of 20 feet (6096 mm) or more is provided, wood columns and arches conforming to heavy timber sizes may be used externally.

602.5 Type V.

Type V construction is that type of construction in which the structural elements, exterior walls and interior walls are of any materials permitted by this code.

SECTION 603
COMBUSTIBLE MATERIAL IN TYPES I AND II CONSTRUCTION

603.1 Allowable uses.

Combustible materials are permitted in buildings of Type I and Type II construction in the following applications:

  1. 1. Fire-retardant-treated wood shall be permitted in:

    1. 1.1. Nonbearing partitions where the required fire-resistance rating is 2 hours or less.

    2. 1.2. Nonbearing exterior walls where no fire rating is required.

    3. 1.3. Roof construction as permitted in Table 601, Note c, Item 3.

  2. 2. Thermal and acoustical insulation, other than foam plastics, having a flame spread index of not more than 25.

    Exceptions:

    1. 1. Insulation placed between two layers of noncombustible materials without an intervening airspace shall be allowed to have a flame spread index of not more than 100.

    2. 2. Insulation installed between a finished floor and solid decking without intervening airspace shall be allowed to have a flame spread index of not more than 200.

  3. 3. Foam plastics in accordance with Chapter 26.

  4. 4. Roof coverings that have an A, B or C classification.

  5. 5. Interior floor finish and interior finish, trim and mill-work such as doors, door frames, window sashes and frames.

  6. 6. Where not installed over 15 feet (4572 mm) above grade, show windows, nailing or furring strips, wooden bulkheads below show windows, their frames, aprons and show cases.

  7. 7. Finish flooring applied directly to the floor slab or to wood sleepers that are firestopped in accordance with Section 716.2.7.

  8. 8. Partitions dividing portions of stores, offices or similar places occupied by one tenant only and which do not establish a corridor serving an occupant load of 30 or more may be constructed of fire-retardant-treated wood, 1-hour fire-resistance-rated construction or of wood panels or similar light construction up to 6 feet (1829 mm) in height.

  9. 9. Platforms as permitted in Section 410.

  10. 10. Materials complying with Section 602 of the International Mechanical Code.

  11. 11. Combustible exterior wall coverings, balconies, bay or oriel windows, or similar appendages in accordance with Chapter 14.

  12. 12. Blocking such as for handrails, millwork, cabinets, and window and door frames.

  13. 13. Light-transmitting plastics as permitted by Chapter 26.

  14. 14. Mastics and caulking materials applied to provide flexible seals between components of exterior wall construction.

  15. 15. Exterior plastic veneer installed in accordance with Section 2605.2.

  16. 16. Nailing or furring strips as permitted by Section 803.3.

  17. 17. Heavy timber as permitted by Note c, Item 2, to Table 601 and Sections 602.4.7 and 1406.3.

  18. 18. Aggregates, component materials and admixtures as permitted by Section 703.2.2.

  19. 19. Sprayed cementitious and mineral fiber fire-resistance-rated materials installed to comply with Section 1704.11.

  20. 20. Materials used to protect penetrations in fire-resistance-rated assemblies in accordance with Section 711.

  21. 21. Materials used to protect joints in fire-resistance-rated assemblies in accordance with Section 712.

  22. 22. Materials allowed in the concealed spaces of buildings of Types I and II construction in accordance with Section 716.5.