CHAPTER 22
STEEL


  • SECTION 2201
    GENERAL

    2201.1 Scope.
    The provisions of this chapter govern the quality, design, fabrication and erection of steel used structurally in buildings or structures.

    SECTION 2202
    DEFINITIONS

    2202.1 Definitions.
    The following terms are defined in Chapter 2:

    STEEL CONSTRUCTION, COLD-FORMED.

    STEEL JOIST.

    STEEL MEMBER, STRUCTURAL.

    SECTION 2203
    IDENTIFICATION AND PROTECTION OF STEEL FOR STRUCTURAL PURPOSES

    2203.1 Identification.
    Identification of structural steel members shall comply with the requirements contained in AISC 360. Identification of cold-formed steel members shall comply with the requirements contained in AISI S100. Identification of cold-formed steel light-frame construction shall also comply with the requirements contained in AISI S200. Other steel furnished for structural load-carrying purposes shall be properly identified for conformity to the ordered grade in accordance with the specified ASTM standard or other specification and the provisions of this chapter. Steel that is not readily identifiable as to grade from marking and test records shall be tested to determine conformity to such standards.

    2203.2 Protection.
    Painting of structural steel members shall comply with the requirements contained in AISC 360. Painting of open-web steel joists and joist girders shall comply with the requirements of SJI CJ-1.0, SJI JG-1.1, SJI K-1.1 and SJI LH/DLH-1.1. Individual structural members and assembled panels of cold-formed steel construction shall be protected against corrosion in accordance with the requirements contained in AISI S100. Protection of cold-formed steel light-frame construction shall also comply with the requirements contained in AISI S200.

    SECTION 2204
    CONNECTIONS

    2204.1 Welding.
    The details of design, workmanship and technique for welding, inspection of welding and qualification of welding operators shall conform to the requirements of the specifications listed in Sections 2205, 2206, 2207, 2208, 2210 and 2211. Special inspection of welding shall be provided where required by Section 1705.

    2204.2 Bolting.
    The design, installation and inspection of bolts shall be in accordance with the requirements of the specifications listed in Sections 2205, 2206, 2207, 2210 and 2211. Special inspection of the installation of high-strength bolts shall be provided where required by Section 1705.

    2204.2.1 Anchor rods.
    Anchor rods shall be set in accordance with the construction documents. The protrusion of the threaded ends through the connected material shall fully engage the threads of the nuts, but shall not be greater than the length of the threads on the bolts.

    SECTION 2205
    STRUCTURAL STEEL

    2205.1 General.
    The design, fabrication and erection of structural steel for buildings and structures shall be in accordance with AISC 360. Where required, the seismic design of structural steel structures shall be in accordance with the additional provisions of Section 2205.2.

    2205.2 Seismic requirements for structural steel structures.
    The design of structural steel structures to resist seismic forces shall be in accordance with the provisions of Section 2205.2.1 or 2205.2.2, as applicable.

    2205.2.1 Seismic Design Category B or C.
    Structural steel structures assigned to Seismic Design Category B or C shall be of any construction permitted in Section 2205. Where a response modification coefficient, R, in accordance with ASCE 7, Table 12.2-1 is used for the design of structural steel structures assigned to Seismic Design Category B or C, the structures shall be designed and detailed in accordance with the requirements of AISC 341.

    Exception: The response modification coefficient, R, designated for “Steel systems not specifically detailed for seismic resistance, excluding cantilever column systems” in ASCE 7, Table 12.2-1 shall be permitted for systems designed and detailed in accordance with AISC 360, and need not be designed and detailed in accordance with AISC 341.

    2205.2.2 Seismic Design Category D, E or F.
    Structural steel structures assigned to Seismic Design Category D, E or F shall be designed and detailed in accordance with AISC 341, except as permitted in ASCE 7, Table 15.4-1.

    SECTION 2206
    COMPOSITE STRUCTURAL STEEL AND
    CONCRETE STRUCTURES

    2206.1 General.
    Systems of structural steel acting compositely with reinforced concrete shall be designed in accordance with AISC 360 and ACI 318, excluding ACI 318 Chapter 22. Where required, the seismic design of composite steel and concrete systems shall be in accordance with the additional provisions of Section 2206.2.

    2206.2 Seismic requirements for composite structural steel and concrete construction.
    Where a response modification coefficient, R, in accordance with ASCE 7, Table 12.2-1 is used for the design of systems of structural steel acting compositely with reinforced concrete, the structures shall be designed and detailed in accordance with the requirements of AISC 341.

    Deleted

    SECTION 2207
    STEEL JOISTS

    2207.1 General.
    The design, manufacture and use of open web steel joists and joist girders shall be in accordance with one of the following Steel Joist Institute (SJI) specifications:

    1. SJI CJ-1.0

    2. SJI K-1.1

    3. SJI LH/DLH-1.1

    4. SJI JG-1.1

    Where required, the seismic design of buildings shall be in accordance with the additional provisions of Section 2205.2 or 2211.6.

    2207.2 Design.
    The registered design professional shall indicate on the construction documents the steel joist and/or steel joist girder designations from the specifications listed in Section 2207.1 and shall indicate the requirements for joist and joist girder design, layout, end supports, anchorage, non-SJI standard bridging, bridging termination connections and bearing connection design to resist uplift and lateral loads. These documents shall indicate special requirements as follows:

    1. Special loads including:

    1.1. Concentrated loads;

    1.2. Nonuniform loads;

    1.3. Net uplift loads;

    1.4. Axial loads;

    1.5. End moments; and

    1.6. Connection forces.

    2. Special considerations including:

    2.1. Profiles for nonstandard joist and joist girder configurations (standard joist and joist girder configurations are as indicated in the SJI catalog);

    2.2. Oversized or other nonstandard web openings; and

    2.3. Extended ends.

    3. Deflection criteria for live and total loads for non-SJI standard joists.

    2207.3 Calculations.
    The steel joist and joist girder manufacturer shall design the steel joists and/or steel joist girders in accordance with the current SJI specifications and load tables to support the load requirements of Section 2207.2. The registered design professional may require submission of the steel joist and joist girder calculations as prepared by a registered design professional responsible for the product design. If requested by the registered design professional, the steel joist manufacturer shall submit design calculations with a cover letter bearing the seal and signature of the joist manufacturer's registered design professional. In addition to standard calculations under this seal and signature, submittal of the following shall be included:

    1. Non-SJI standard bridging details (e.g.for cantilevered conditions, net uplift, etc.).

    2. Connection details for:

    2.1. Non-SJI standard connections (e.g.flush-framed or framed connections);

    2.2. Field splices; and

    2.3. Joist headers.

    2207.4 Steel joist drawings.
    Steel joist placement plans shall be provided to show the steel joist products as specified on the construction documents and are to be utilized for field installation in accordance with specific project requirements as stated in Section 2207.2. Steel placement plans shall include, at a minimum, the following:

    1. Listing of all applicable loads as stated in Section 2207.2 and used in the design of the steel joists and joist girders as specified in the construction documents.

    2. Profiles for nonstandard joist and joist girder configurations (standard joist and joist girder configurations are as indicated in the SJI catalog).

    3. Connection requirements for:

    3.1. Joist supports;

    3.2. Joist girder supports;

    3.3. Field splices; and

    3.4. Bridging attachments.

    4. Deflection criteria for live and total loads for non-SJI standard joists.

    5. Size, location and connections for all bridging.

    6. Joist headers.

    Steel joist placement plans do not require the seal and signature of the joist manufacturer’s registered design professional.

    2207.5 Certification.
    At completion of manufacture, the steel joist manufacturer shall submit a certificate of compliance in accordance with Section 1704.2.5.2 stating that work was performed in accordance with approved construction documents and with SJI standard specifications.

    SECTION 2208
    STEEL CABLE STRUCTURES

    2208.1 General.
    The design, fabrication and erection including related connections, and protective coatings of steel cables for buildings shall be in accordance with ASCE 19.

    2208.2 Seismic requirements for steel cable.
    The design strength of steel cables shall be determined by the provisions of ASCE 19 except as modified by these provisions.

    1. A load factor of 1.1 shall be applied to the prestress force included in T3 and T4 as defined in Section 3.12.

    2. In Section 3.2.1, Item (c) shall be replaced with “1.5 T3” and Item (d) shall be replaced with “1.5 T4.”

    SECTION 2209
    STEEL STORAGE RACKS

    2209.1 Storage racks.
    The design, testing and utilization of industrial steel storage racks made of cold-formed or hot-rolled steel structural members, shall be in accordance with RMI/ANSI MH 16.1. Where required by ASCE 7, the seismic design of storage racks shall be in accordance with the provisions of Section 15.5.3 of ASCE 7, except that the mapped acceleration parameters, Ss and S1, shall be determined in accordance with Section 1613.3.1.

    SECTION 2210
    COLD-FORMED STEEL

    2210.1 General.
    The design of cold-formed carbon and low-alloy steel structural members shall be in accordance with AISI S100. The design of cold-formed stainless-steel structural members shall be in accordance with ASCE 8. Cold-formed steel light-frame construction shall also comply with Section 2211. Where required, the seismic design of cold-formed steel structures shall be in accordance with the additional provisions of Section 2210.2.

    2210.1.1 Steel decks.
    The design and construction of cold-formed steel decks shall be in accordance with this section.

    Deleted

    2210.1.1.1 Noncomposite steel floor decks.
    Noncomposite steel floor decks shall be permitted to be designed and constructed in accordance with ANSI/SDI-NC1.0.

    Deleted

    2210.1.1.2 Steel roof deck.
    Steel roof decks shall be permitted to be designed and constructed in accordance with ANSI/SDI-RD1.0.

    2210.2 Seismic requirements for cold-formed steel structures.
    Where a response modification coefficient, R, in accordance with ASCE 7, Table 12.2-1 is used for the design of cold-formed steel structures, the structures shall be designed and detailed in accordance with the requirements of AISI S100, ASCE 8, and, for cold-formed steel special-bolted moment frames, AISI S110.

    SECTION 2211
    COLD-FORMED STEEL LIGHT-FRAME
    CONSTRUCTION

    2211.1 General.
    The design and installation of structural members and nonstructural members utilized in cold-formed steel light-frame construction where the specified minimum base steel thickness is between 0.0179 inches (0.455 mm) and 0.1180 inches (2.997 mm) shall be in accordance with AISI S200 and Sections 2211.2 through 2211.7, as applicable.

    2211.2 Header design.
    Headers, including box and back- to-back headers, and double and single L-headers shall be designed in accordance with AISI S212 or AISI S100.

    Deleted

    2211.3 Truss design.
    Cold-formed steel trusses shall be designed in accordance with AISI S214, Sections 2211.3.1 through 2211.3.4 and accepted engineering practice.

    2211.3.1 Truss design drawings.
    The truss design drawings shall conform to the requirements of Section B2.3 of AISI S214 and shall be provided with the shipment of trusses delivered to the job site. The truss design drawings shall include the details of permanent individual truss member restraint/bracing in accordance with Section B6(a) or B 6(c) of AISI S214 where these methods are utilized to provide restraint/bracing.

    2211.3.2 Deferred submittals.
    AISI S214 Section B4.2 shall be deleted.

    2211.3.3 Trussses spanning 60 feet or greater.
    The owner shall contract with a registered design professional for the design of the temporary installation restraint/bracing and the permanent individual truss member restraint/bracing for trusses with clear spans 60 feet (18 288 mm) or greater. Special inspection of trusses over 60 feet (18 288 mm) in length shall conform to Section 1705.

    2211.3.4 Truss quality assurance.
    Trusses not part of a manufacturing process that provides requirements for quality control done under the supervision of a third-party quality control agency, shall be manufactured in compliance with Sections 1704.2.5 and 1705.2, as applicable.

    2211.4 Wall stud design.
    Wall studs shall be designed in accordance with either AISI S211 or AISI S100.

    2211.5 Floor and roof system design.
    Framing for floor and roof systems in buildings shall be designed in accordance with either AISI S210 or AISI S100.

    2211.6 Lateral design.
    Light-frame shear walls, diagonal strap bracing that is part of a structural wall and diaphragms used to resist wind, seismic and other in-plane lateral loads shall be designed in accordance with AISI S213.

    2211.7 Prescriptive framing.
    Detached one- and two-family dwellings and townhouses, less than or equal to three stories above grade plane, shall be permitted to be constructed in accordance with AISI S230 subject to the limitations therein.

FEEDBACK LIVE CHAT