• CHAPTER22
    STEEL

    User note: Code change proposals to this chapter will be considered by the IBC – Structural Code

    Development Committee during the 2016 (Group B) Code Development Cycle. See explanation on page iv.

    SECTION2201
    GENERAL

    2201.1 Scope.

    The provisions of this chapter govern the quality, design, fabrication and erection of steel construction.

    SECTION2202
    DEFINITIONS

    2202.1 Definitions.

    The following terms are defined in Chapter 2:

    STEEL CONSTRUCTION, COLD-FORMED.

    STEEL JOIST.

    STEEL ELEMENT, STRUCTURAL.

    SECTION2203
    IDENTIFICATION AND PROTECTION OF STEEL FOR STRUCTURAL PURPOSES

    2203.1 Identification.

    Identification of structural steel elements shall be in accordance with AISC 360. Identification of cold-formed steel members shall be in accordance with AISI S100. Identification of cold-formed steel light-frame construction shall also comply with the requirements contained in AISI S200 or AISI S220, as applicable. Other steel furnished for structural load-carrying purposes shall be properly identified for conformity to the ordered grade in accordance with the specified ASTM standard or other specification and the provisions of this chapter. Steel that is not readily identifiable as to grade from marking and test records shall be tested to determine conformity to such standards.

    2203.2 Protection.

    Painting of structural steel elements shall be in accordance with AISC 360. Painting of open-web steel joists and joist girders shall be in accordance with SJI CJ, SJI JG, SJI K and SJI LH/DLH. Individual structural members and assembled panels of cold-formed steel construction shall be protected against corrosion in accordance with the requirements contained in AISI S100. Protection of cold-formed steel light-frame construction shall be in accordance with AISI S200 or AISI S220, as applicable.

    SECTION2204
    CONNECTIONS

    2204.1 Welding.

    The details of design, workmanship and technique for welding and qualification of welding personnel shall be in accordance with the specifications listed in Sections 2205, 2206, 2207, 2208, 2210 and 2211. For special inspection of welding, see Section 1705.2.

    2204.2 Bolting.

    The design, installation and inspection of bolts shall be in accordance with the requirements of Sections 2205, 2206, 2207, 2210 and 2211. For special inspection of the installation of high-strength bolts, see Section 1705.2.

    2204.3 Anchor rods.

    Anchor rods shall be set in accordance with the approved construction documents. The protrusion of the threaded ends through the connected material shall fully engage the threads of the nuts but shall not be greater than the length of the threads on the bolts.

    SECTION2205
    STRUCTURAL STEEL

    2205.1 General.

    The design, fabrication and erection of structural steel elements in buildings, structures and portions thereof shall be in accordance with AISC 360.

    2205.2 Seismic design.

    Where required, the seismic design, fabrication and erection of buildings, structures and portions thereof shall be in accordance with Section 2205.2.1 or 2205.2.2, as applicable.

    2205.2.1 Structural steel seismic force-resisting systems.

    The design, detailing, fabrication and erection of structural steel seismic force-resisting systems shall be in accordance with the provisions of Section 2205.2.1.1 or 2205.2.1.2, as applicable.

    2205.2.1.1 Seismic Design Category B or C.

    Structures assigned to Seismic Design Category B or C shall be of any construction permitted in Section 2205. Where a response modification coefficient, R, in accordance with ASCE 7, Table 12.2-1, is used for the design of structures assigned to Seismic Design Category B or C, the structures shall be designed and detailed in accordance with the requirements of AISC 341.

    Exception: The response modification coefficient, R, designated for “Steel systems not specifically detailed for seismic resistance, excluding cantilever column systems” in ASCE 7, Table 12.2-1, shall be permitted for systems designed and detailed in accordance with AISC 360, and need not be designed and detailed in accordance with AISC 341.

    2205.2.1.2 Seismic Design Category D, E or F.

    Structures assigned to Seismic Design Category D, E or F shall be designed and detailed in accordance with AISC 341, except as permitted in ASCE 7, Table 15.4-1.

    2205.2.2 Structural steel elements.

    The design, detailing, fabrication and erection of structural steel elements in seismic force-resisting systems other than those covered in Section 2205.2.1, including struts, collectors, chords and foundation elements, shall be in accordance with AISC 341 where either of the following applies:

    1. 1.The structure is assigned to Seismic Design Category D, E or F, except as permitted in ASCE 7, Table 15.4-1.

    2. 2.A response modification coefficient, R, greater than 3 in accordance with ASCE 7, Table 12.2-1, is used for the design of the structure assigned to Seismic Design Category B or C.

    SECTION2206
    COMPOSITE STRUCTURAL STEEL AND CONCRETE STRUCTURES

    2206.1 General.

    Systems of structural steel elements acting compositely with reinforced concrete shall be designed in accordance with AISC 360 and ACI 318, excluding ACI 318 Chapter 14.

    2206.2 Seismic design.

    Where required, the seismic design, fabrication and erection of composite steel and concrete systems shall be in accordance with Section 2206.2.1.

    2206.2.1 Seismic requirements for composite structural steel and concrete construction.

    Where a response modification coefficient, R, in accordance with ASCE 7, Table 12.2-1, is used for the design of systems of structural steel acting compositely with reinforced concrete, the structures shall be designed and detailed in accordance with the requirements of AISC 341.

    SECTION2207
    STEEL JOISTS

    2207.1 General.

    The design, manufacture and use of open-web steel joists and joist girders shall be in accordance with one of the following Steel Joist Institute (SJI) specifications:

    1. 1.SJI CJ

    2. 2.SJI K

    3. 3.SJI LH/DLH

    4. 4.SJI JG

    2207.1.1 Seismic design.

    Where required, the seismic design of buildings shall be in accordance with the additional provisions of Section 2205.2 or 2211.6.

    2207.2 Design.

    The registered design professional shall indicate on the construction documents the steel joist and steel joist girder designations from the specifications listed in Section 2207.1; and shall indicate the requirements for joist and joist girder design, layout, end supports, anchorage, bridging design that differs from the SJI specifications listed in Section 2207.1, bridging termination connections and bearing connection design to resist uplift and lateral loads. These documents shall indicate special requirements as follows:

    1. 1.Special loads including:

      1. 1.1.Concentrated loads.

      2. 1.2.Nonuniform loads.

      3. 1.3.Net uplift loads.

      4. 1.4.Axial loads.

      5. 1.5.End moments.

      6. 1.6.Connection forces.

    2. 2.Special considerations including:

      1. 2.1.Profiles for joist and joist girder configurations that differ from those defined by the SJI specifications listed in Section 2207.1.

      2. 2.2.Oversized or other nonstandard web openings.

      3. 2.3.Extended ends.

    3. 3.Live and total load deflection criteria for joists and joist girder configurations that differ from those defined by the SJI specifications listed in Section 2207.1.

    2207.3 Calculations.

    The steel joist and joist girder manufacturer shall design the steel joists and steel joist girders in accordance with the SJI specifications listed in Section 2207.1 to support the load requirements of Section 2207.2. The registered design professional shall be permitted to require submission of the steel joist and joist girder calculations as prepared by a registered design professional responsible for the product design. Where requested by the registered design professional, the steel joist manufacturer shall submit design calculations with a cover letter bearing the seal and signature of the joist manufacturer’s registered design professional. In addition to the design calculations submitted under seal and signature, the following shall be included:

    1. 1.Bridging design that differs from the SJI specifications listed in Section 2207.1, such as cantilevered conditions and net uplift.

    2. 2.Connection design for:

      1. 2.1.Connections that differ from the SJI specifications listed in Section 2207.1, such as flush-framed or framed connections.

      2. 2.2.Field splices.

      3. 2.3.Joist headers.

    2207.4 Steel joist drawings.

    Steel joist placement plans shall be provided to show the steel joist products as specified on the approved construction documents and are to be utilized for field installation in accordance with specific project requirements as stated in Section 2207.2. Steel joist placement plans shall include, at a minimum, the following:

    1. 1.Listing of applicable loads as stated in Section 2207.2 and used in the design of the steel joists and joist girders as specified in the approved construction documents.

    2. 2.Profiles for joist and joist girder configurations that differ from those defined by the SJI specifications listed in Section 2207.1.

    3. 3.Connection requirements for:

      1. 3.1.Joist supports.

      2. 3.2.Joist girder supports.

      3. 3.3.Field splices.

      4. 3.4.Bridging attachments.

    4. 4.Live and total load deflection criteria for joists and joist girder configurations that differ from those defined by the SJI specifications listed in Section 2207.1.

    5. 5.Size, location and connections for bridging.

    6. 6.Joist headers.

    Steel joist placement plans do not require the seal and signature of the joist manufacturer’s registered design professional.

    2207.5 Certification.

    At completion of manufacture, the steel joist manufacturer shall submit a certificate of compliance to the owner or the owner’s authorized agent for submittal to the building official as specified in Section 1704.5 stating that work was performed in accordance with approved construction documents and with SJI specifications listed in Section 2207.1.

    SECTION2208
    STEEL CABLE STRUCTURES

    2208.1 General.

    The design, fabrication and erection including related connections, and protective coatings of steel cables for buildings shall be in accordance with ASCE 19.

    2208.2 Seismic requirements for steel cable.

    The design strength of steel cables shall be determined by the provisions of ASCE 19 except as modified by these provisions.

    1. 1.A load factor of 1.1 shall be applied to the prestress force included in T3 and T4 as defined in Section 3.12.

    2. 2.In Section 3.2.1, Item (c) shall be replaced with “1.5 T3” and Item (d) shall be replaced with “1.5 T4.”

    SECTION2209
    STEEL STORAGE RACKS

    2209.1 Storage racks.

    The design, testing and utilization of storage racks made of cold-formed or hot-rolled steel structural members shall be in accordance with RMI/ANSI MH 16.1. Where required by ASCE 7, the seismic design of storage racks shall be in accordance with Section 15.5.3 of ASCE 7.

    SECTION2210
    COLD-FORMED STEEL

    2210.1 General.

    The design of cold-formed carbon and low-alloy steel structural members shall be in accordance with AISI S100. The design of cold-formed stainless-steel structural members shall be in accordance with ASCE 8. Cold-formed steel light-frame construction shall also comply with Section 2211. Where required, the seismic design of cold-formed steel structures shall be in accordance with the additional provisions of Section 2210.2.

    2210.1.1 Steel decks.

    The design and construction of cold-formed steel decks shall be in accordance with this section.

    2210.1.1.1 Noncomposite steel floor decks.

    Noncomposite steel floor decks shall be permitted to be designed and constructed in accordance with ANSI/SDI-NC1.0.

    2210.1.1.2 Steel roof deck.

    Steel roof decks shall be permitted to be designed and constructed in accordance with ANSI/SDI-RD1.0.

    2210.1.1.3 Composite slabs on steel decks.

    Composite slabs of concrete and steel deck shall be permitted to be designed and constructed in accordance with SDI-C.

    2210.2 Seismic requirements for cold-formed steel structures.

    Where a response modification coefficient, R, in accordance with ASCE 7, Table 12.2-1, is used for the design of cold-formed steel structures, the structures shall be designed and detailed in accordance with the requirements of AISI S100, ASCE 8, or, for cold-formed steel special-bolted moment frames, AISI S110.

    SECTION2211
    COLD-FORMED STEEL LIGHT-FRAME CONSTRUCTION

    2211.1 General.

    The design and installation of structural and nonstructural members utilized in cold-formed steel light-frame construction where the specified minimum base steel thickness is not greater than 0.1180 inches (2.997 mm) shall be in accordance with AISI S200 and Sections 2211.2 through 2211.7, or AISI S220, as applicable.

    2211.2 Header design.

    Headers, including box and back-to-back headers, and double and single L-headers shall be designed in accordance with AISI S212 or AISI S100.

    2211.3 Truss design.

    Cold-formed steel trusses shall be designed in accordance with AISI S214, Sections 2211.3.1 through 2211.3.4 and accepted engineering practice.

    2211.3.1 Truss design drawings.

    The truss design drawings shall conform to the requirements of Section B2.3 of AISI S214 and shall be provided with the shipment of trusses delivered to the job site. The truss design drawings shall include the details of permanent individual truss member restraint/bracing in accordance with Section B6(a) or B 6(c) of AISI S214 where these methods are utilized to provide restraint/bracing.

    2211.3.2 Deferred submittals.

    AISI S214 Section B4.2 shall be deleted.

    2211.3.3 Trusses spanning 60 feet or greater.

    The owner or the owner’s authorized agent shall contract with a registered design professional for the design of the temporary installation restraint/bracing and the permanent individual truss member restraint/bracing for trusses with clear spans 60 feet (18 288 mm) or greater. Special inspection of trusses over 60 feet (18 288 mm) in length shall be in accordance with Section 1705.2.

    2211.3.4 Truss quality assurance.

    Trusses not part of a manufacturing process that provides requirements for quality control done under the supervision of a third-party quality control agency, shall be manufactured in compliance with Sections 1704.2.5 and 1705.2, as applicable.

    2211.4 Structural wall stud design.

    Structural wall studs shall be designed in accordance with either AISI S211 or AISI S100.

    2211.5 Floor and roof system design.

    Framing for floor and roof systems in buildings shall be designed in accordance with either AISI S210 or AISI S100.

    2211.6 Lateral design.

    Light-frame shear walls, diagonal strap bracing that is part of a structural wall and diaphragms used to resist wind, seismic and other in-plane lateral loads shall be designed in accordance with AISI S213.

    2211.7 Prescriptive framing.

    Detached one- and two-family dwellings and townhouses, less than or equal to three stories above grade plane, shall be permitted to be constructed in accordance with AISI S230 subject to the limitations therein.