• CHAPTER30
    INDUSTRIAL OVENS

    SECTION3001
    GENERAL

    3001.1Scope.

    This chapter shall apply to the installation and operation of industrial ovens and furnaces. Industrial ovens and furnaces shall comply with the applicable provisions of NFPA 86, the International Fuel Gas Code, International Mechanical Code and this chapter. The terms “ovens” and “furnaces” are used interchangeably in this chapter.

    3001.2Permits.

    Permits shall be required as set forth in Sections 105.6 and 105.7.

    SECTION3002
    DEFINITIONS

    3002.1Definitions.

    The following terms are defined in Chapter 2:

    FURNACE CLASS A.

    FURNACE CLASS B.

    FURNACE CLASS C.

    FURNACE CLASS D.

    SECTION3003
    LOCATION

    3003.1Ventilation.

    Enclosed rooms or basements containing industrial ovens or furnaces shall be provided with combustion air in accordance with the International Mechanical Code and the International Fuel Gas Code, and with ventilation air in accordance with the International Mechanical Code.

    3003.2Exposure.

    When locating ovens, oven heaters and related equipment, the possibility of fire resulting from overheating or from the escape of fuel gas or fuel oil and the possibility of damage to the building and injury to persons resulting from explosion shall be considered.

    3003.3Ignition source.

    Industrial ovens and furnaces shall be located so as not to pose an ignition hazard to flammable vapors or mists or combustible dusts.

    3003.4Temperatures.

    Roofs and floors of ovens shall be insulated and ventilated to prevent temperatures at combustible ceilings and floors from exceeding 160°F (71°C).

    SECTION3004
    FUEL PIPING

    3004.1Fuel-gas piping.

    Fuel-gas piping serving industrial ovens shall comply with the International Fuel Gas Code. Piping for other fuel sources shall comply with this section.

    3004.2Shutoff valves.

    Each industrial oven or furnace shall be provided with an approved manual fuel shutoff valve in accordance with the International Mechanical Code or the International Fuel Gas Code.

    3004.2.1Fuel supply lines.

    Valves for fuel supply lines shall be located within 6 feet (1829 mm) of the appliance served.

    Exception: When approved and the valve is located in the same general area as the appliance served.

    3004.3Valve position.

    The design of manual fuel shutoff valves shall incorporate a permanent feature which visually indicates the open or closed position of the valve. Manual fuel shutoff valves shall not be equipped with removable handles or wrenches unless the handle or wrench can only be installed parallel with the fuel line when the valve is in the open position.

    SECTION3005
    INTERLOCKS

    3005.1Shut down.

    Interlocks shall be provided for Class A ovens so that conveyors or sources of flammable or combustible materials shall shut down if either the exhaust or recirculation air supply fails.

    SECTION3006
    FIRE PROTECTION

    3006.1Required protection.

    Class A and B ovens that contain, or are utilized for the processing of, combustible materials shall be protected by an approved automatic fire-extinguishing system complying with Chapter 9.

    3006.2Fixed fire-extinguishing systems.

    Fixed fire-extinguishing systems shall be provided for Class C or D ovens to protect against such hazards as overheating, spillage of molten salts or metals, quench tanks, ignition of hydraulic oil and escape of fuel. It shall be the user’s responsibility to consult with the fire code official concerning the necessary requirements for such protection.

    3006.3Fire extinguishers.

    Portable fire extinguishers complying with Section 906 shall be provided not closer than 15 feet (4572 mm) or not more than 50 feet (15 240 mm) or in accordance with NFPA 10. This shall apply to the oven and related equipment.

    SECTION3007
    OPERATION AND MAINTENANCE

    3007.1Furnace system information.

    An approved, clearly worded, and prominently displayed safety design data form or manufacturer’s nameplate shall be provided stating the safe operating condition for which the furnace system was designed, built, altered or extended.

    3007.2Oven nameplate.

    Safety data for Class A solvent atmosphere ovens shall be furnished on the manufacturer’s nameplate. The nameplate shall provide the following design data:

    1. 1.The solvent used.

    2. 2.The number of gallons (L) used per batch or per hour of solvent entering the oven.

    3. 3.The required purge time.

    4. 4.The oven operating temperature.

    5. 5.The exhaust blower rating for the number of gallons (L) of solvent per hour or batch at the maximum operating temperature.

    Exception: For low-oxygen ovens, the maximum allowable oxygen concentration shall be included in place of the exhaust blower ratings.

    3007.3Training.

    Operating, maintenance and supervisory personnel shall be thoroughly instructed and trained in the operation of ovens or furnaces.

    3007.4Equipment maintenance.

    Equipment shall be maintained in accordance with the manufacturer’s instructions.