CHAPTER 11 CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
User note:
About this chapter: Chapter 11 applies to existing buildings constructed prior to the adoption of the code and is intended to ensure a minimum degree of fire and life safety to persons occupying existing buildings by providing for alterations to such buildings that do not comply with the minimum requirements of the International Building Code®. The provisions address general fire safety features such as requirements for fire alarm systems in some existing buildings and general means of egress, and include a section dedicated to existing Group I-2 occupancies.
SECTION 1101
GENERAL
1101.1 Scope.
The provisions of this chapter shall apply to existing buildings constructed prior to the adoption of this code.
1101.4 Owner notification.
When a building is found to be in noncompliance with this chapter, the fire code official shall duly notify the owner of the building. Upon receipt of such notice, the owner shall, subject to the following time limits, take necessary actions to comply with the provisions of this chapter.
1101.4.1 Construction documents.
Construction documents necessary to comply with this chapter shall be completed and submitted within a time schedule approved by the fire code official.
1101.4.2 Completion of work.
Work necessary to comply with this chapter shall be completed within a time schedule approved by the fire code official.
1101.4.3 Extension of time.
The fire code official is authorized to grant necessary extensions of time where it can be shown that the specified time periods are not physically practical or pose an undue hardship. The granting of an extension of time for compliance shall be based on the showing of good cause and subject to the filing of an acceptable systematic plan of correction with the fire code official.
SECTION 1102
DEFINITIONS
SECTION 1103
FIRE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS
1103.1 Required construction.
Existing buildings shall comply with not less than the minimum provisions specified in Table 1103.1 and as further enumerated in Sections 1103.2 through 1103.10.
The provisions of this chapter shall not be construed to allow the elimination of fire protection systems or a reduction in the level of fire safety provided in buildings constructed in accordance with previously adopted codes.
TABLE 1103.1
OCCUPANCY AND USE REQUIREMENTSa
R = The building is required to comply.
a.Existing buildings shall comply with the sections identified as “Required” (R) based on occupancy classification or use, or both, whichever is applicable.
b.Only applies to Group I-2, Condition 2 occupancies as established by the adopting ordinance or legislation of the jurisdiction.
c.Only applies to Group A-2 occupancies where alcoholic beverages are consumed.
1103.2 Emergency responder communication coverage in existing buildings.
Existing buildings other than Group R-3, that do not have approved in-building, two-way emergency response communication coverage for emergency responders in the building based on existing coverage levels of the public safety communication systems, shall be equipped with such coverage according to one of the following:
Exception: Where it is determined by the fire code official that the in-building, two-way emergency responder communication coverage system is not needed.
1103.3 Existing elevators.
1103.3.2 Elevator emergency operation.
Existing elevators with a travel distance of 25 feet (7620 mm) or more above or below the main floor or other level of a building and intended to serve the needs of emergency personnel for fire-fighting or rescue purposes shall be provided with emergency operation in accordance with ASME A17.3.
Exceptions:
1.Buildings without occupied floors located more than 55 feet (16 764 mm) above or 25 feet (7620 mm) below the lowest level of fire department vehicle access where protected at the elevator shaft openings with additional fire doors in accordance with Section 716 of the International Building Code and where all of the following conditions are met:
1.1.The doors shall be provided with vision panels of approved fire-protection-rated glazing so located as to furnish clear vision of the approach to the elevator. Such glazing shall not exceed 100 square inches (0.065 m2) in area.
1.2.The doors shall be held open but be automatic-closing by activation of a fire alarm initiating device installed in accordance with the requirements of NFPA 72 as for Phase I Emergency Recall Operation, and shall be located at each floor served by the elevator; in the associated elevator machine room, control space, or control room; and in the elevator hoistway, where sprinklers are located in those hoistways.
1.3.The doors, when closed, shall have signs visible from the approach area stating: “WHEN THESE DOORS ARE CLOSED OR IN FIRE EMERGENCY, DO NOT USE ELEVATOR. USE EXIT STAIRWAYS.”
2.Buildings without occupied floors located more than 55 feet (16 764 mm) above or 25 feet (7620 mm) below the lowest level of fire department vehicle access where provided with automatic sprinkler systems installed in accordance with Section 903.3.1.1 or 903.3.1.2.
3.Freight elevators in buildings provided with both automatic sprinkler systems installed in accordance with Section 903.3.1.1 or 903.3.1.2 and not less than one ASME 17.3-compliant elevator serving the same floors.
Elimination of previously installed Phase I emergency recall or Phase II emergency in-car systems shall not be permitted.
1103.4 Vertical openings.
1103.4.1 Group I-2 and I-3 occupancies.
In Group I-2 and I-3 occupancies, interior vertical openings connecting two or more stories shall be protected with 1-hour fire-resistance-rated construction.
Exceptions:
1.In Group I-2, unenclosed vertical openings not exceeding two connected stories and not concealed within the building construction shall be permitted as follows:
1.1.The unenclosed vertical openings shall be separated from other unenclosed vertical openings serving other floors by a smoke barrier.
1.2.The unenclosed vertical openings shall be separated from corridors by smoke partitions.
1.3.The unenclosed vertical openings shall be separated from other fire or smoke compartments on the same floors by a smoke barrier.
1.4.On other than the lowest level, the unenclosed vertical openings shall not serve as a required means of egress.
2.In Group I-2, atriums connecting three or more stories shall not require 1-hour fire-resistance-rated construction where the building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3, and all of the following conditions are met:
2.1.For other than existing approved atriums with a smoke control system, where the atrium was constructed and is maintained in accordance with the code in effect at the time the atrium was created, the atrium shall have a smoke control system that is in compliance with Section 909.
2.2.Glass walls forming a smoke partition or a glass-block wall assembly shall be permitted where in compliance with Condition 2.2.1 or 2.2.2.
2.2.1.Glass walls forming a smoke partition shall be permitted where all of the following conditions are met:
2.2.1.1.Automatic sprinklers are provided along both sides of the separation wall and doors, or on the room side only if there is not a walkway or occupied space on the atrium side.
2.2.1.2.The sprinklers shall be not more than 12 inches (305 mm) away from the face of the glass and at intervals along the glass of not greater than 72 inches (1829 mm).
2.2.1.3.Windows in the glass wall shall be nonoperating type.
2.2.1.4.The glass wall and windows shall be installed in a gasketed frame in a manner that the framing system deflects without breaking (loading) the glass before the sprinkler system operates.
2.2.1.5.The sprinkler system shall be designed so that the entire surface of the glass is wet upon activation of the sprinkler system without obstruction.
2.2.2.A fire barrier is not required where a glass-block wall assembly complying with Section 2110 of the International Building Code and having a 3/4-hour fire protection rating is provided.
2.3.Where doors are provided in the glass wall, they shall be either self-closing or automatic-closing and shall be constructed to resist the passage of smoke.
3.In Group I-3 occupancies, exit stairways or ramps and exit access stairways or ramps constructed in accordance with Section 408 of the International Building Code.
1103.4.2 Three to five stories.
In other than Group I-2 and I-3 occupancies, interior vertical openings connecting three to five stories shall be protected by either 1-hour fire-resistance-rated construction or an automatic sprinkler system shall be installed throughout the building in accordance with Section 903.3.1.1 or 903.3.1.2.
Exceptions:
1.Vertical opening protection is not required for Group R-3 occupancies.
2.Vertical opening protection is not required for open parking garages.
3.Vertical opening protection for escalators shall be in accordance with Section 1103.4.5, 1103.4.6 or 1103.4.7.
4.Exit access stairways and ramps shall be in accordance with Section 1103.4.8.
1103.4.3 More than five stories.
In other than Group I-2 and I-3 occupancies, interior vertical openings connecting more than five stories shall be protected by 1-hour fire-resistance-rated construction.
Exceptions:
1.Vertical opening protection is not required for Group R-3 occupancies.
2.Vertical opening protection is not required for open parking garages.
3.Vertical opening protection for escalators shall be in accordance with Section 1103.4.5, 1103.4.6 or 1103.4.7.
4.Exit access stairways and ramps shall be in accordance with Section 1103.4.8.
1103.4.4 Atriums and covered malls.
In other than Group I-2 and I-3 occupancies, interior vertical openings in a covered mall building or a building with an atrium shall be protected by either 1-hour fire-resistance-rated construction or an automatic sprinkler system shall be installed throughout the building in accordance with Section 903.3.1.1 or 903.3.1.2.
1103.4.5 Escalators in Group B and M occupancies.
1103.4.6 Escalators connecting four or fewer stories.
1103.4.7 Escalators connecting more than four stories.
In other than Group B and M occupancies, escalators creating vertical openings connecting five or more stories shall be protected by 1-hour fire-resistance-rated construction.
1103.4.8 Occupancies other than Groups I-2 and I-3.
In other than Group I-2 and I-3 occupancies, floor openings containing exit access stairways or ramps that do not comply with one of the conditions listed in this section shall be protected by 1-hour fire-resistance-rated construction.
1.Exit access stairways and ramps that serve, or atmospherically communicate between, only two stories. Such interconnected stories shall not be open to other stories.
2.In Group R-1, R-2 or R-3 occupancies, exit access stairways and ramps connecting four stories or less serving and contained within an individual dwelling unit or sleeping unit or live/work unit.
3.Exit access stairways and ramps in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, where the area of the vertical opening between stories does not exceed twice the horizontal projected area of the stairway or ramp, and the opening is protected by a draft curtain and closely spaced sprinklers in accordance with NFPA 13. In other than Group B and M occupancies, this provision is limited to openings that do not connect more than four stories.
4.Exit access stairways and ramps within an atrium complying with the provisions of Section 404 of the International Building Code.
5.Exit access stairways and ramps in open parking garages that serve only the parking garage.
6.Exit access stairways and ramps serving open-air seating complying with the exit access travel distance requirements of Section 1030.7 of the International Building Code.
7.Exit access stairways and ramps serving the balcony, gallery or press box and the main assembly floor in occupancies such as theaters, places of religious worship, auditoriums and sports facilities.
1103.4.9 Waste and linen chutes.
1103.4.9.2.2 Chute intake via a chute-intake room.
1103.4.9.4 Chute discharge rooms.
1103.4.10 Flue-fed incinerators.
1103.5 Sprinkler systems.
1103.5.3 Group I-2, Condition 2.
1103.5.4 High-rise buildings.
1.The high-rise building has an occupied floor located more than 120 feet (36 576 mm) above the lowest level of fire department vehicle access.
2.The high-rise building has occupied floors located more than 75 feet (22 860 mm) and not more than 120 feet (36 576 mm) above the lowest level of fire department vehicle access, and the building does not have at least two interior exit stairways complying with Section 1104.10 that are separated from the building interior by fire assemblies having a fire-resistance rating of not less than 2 hours with opening protection in accordance with Table 716.1(2) of the International Building Code.
3.The high-rise building has occupied floors located more than 75 feet (22 860 mm) and not more than 120 feet (36 576 mm) above the lowest level of fire department vehicle access, and the building does not have a fire alarm system that includes smoke detection in mechanical equipment, electrical, transformer, telephone equipment and similar rooms; corridors; elevator lobbies; and at doors penetrating interior exit stairway enclosures. Building owners shall file a compliance schedule with the fire code official not later than 365 days after receipt of a written notice. The compliance schedule shall not exceed 12 years for completion of the automatic sprinkler system retrofit.
1103.5.5 Pyroxylin plastics.
1103.6 Standpipes.
1103.6.1 Existing multiple-story buildings.
Existing buildings with occupied floors located more than 50 feet (15 240 mm) above the lowest level of fire department access or more than 50 feet (15 240 mm) below the highest level of fire department access shall be equipped with standpipes.
1103.6.2 Existing helistops and heliports.
1103.7 Fire alarm systems.
An approved fire alarm system shall be installed in existing buildings and structures in accordance with Sections 1103.7.1 through 1103.7.6 and provide occupant notification in accordance with Section 907.5 unless other requirements are provided by other sections of this code.
Exception: Occupancies with an existing, previously approved fire alarm system.
1103.7.1 Group E.
A fire alarm system shall be installed in existing Group E occupancies in accordance with Section 907.2.3.
Exceptions:
1.A manual fire alarm system is not required in a building with a maximum area of 1,000 square feet (93 m2) that contains a single classroom and is located not closer than 50 feet (15 240 mm) from another building.
2.A manual fire alarm system is not required in Group E occupancies with an occupant load less than 50.
1103.7.5 Group R-1.
1103.7.5.1 Group R-1 hotel and motel manual fire alarm system.
A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in existing Group R-1 hotels and motels more than one story in height or with more than 20 sleeping units.
Exceptions:
1.A manual fire alarm system is not required in buildings less than two stories in height where all sleeping units, attics and crawl spaces are separated by 1-hour fire-resistance-rated construction and each sleeping unit has direct access to a public way, egress court or yard.
2.A manual fire alarm system is not required in buildings not more than three stories in height with not more than 20 sleeping units and equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
3.Manual fire alarm boxes are not required throughout the building where the following conditions are met:
1103.7.5.1.1 Group R-1 hotel and motel automatic smoke detection system.
An automatic smoke detection system that activates the occupant notification system in accordance with Section 907.5 shall be installed in existing Group R-1 hotels and motels throughout all interior corridors serving sleeping rooms not equipped with an approved, supervised automatic sprinkler system installed in accordance with Section 903.
Exception: An automatic smoke detection system is not required in buildings that do not have interior corridors serving sleeping units and where each sleeping unit has a means of egress door opening directly to an exit or to an exterior exit access that leads directly to an exit.
1103.7.5.2 Group R-1 boarding and rooming houses manual fire alarm system.
A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in existing Group R-1 boarding and rooming houses.
Exception: Buildings less than two stories in height where all sleeping units, attics and crawl spaces are separated by 1-hour fire-resistance-rated construction and each sleeping unit has direct access to a public way, egress court or yard.
1103.7.5.2.1 Group R-1 boarding and rooming houses automatic smoke detection system.
An automatic smoke detection system that activates the occupant notification system in accordance with Section 907.5 shall be installed in existing Group R-1 boarding and rooming houses throughout all interior corridors serving sleeping units not equipped with an approved, supervised sprinkler system installed in accordance with Section 903.
1103.7.6 Group R-2.
A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in existing Group R-2 occupancies more than three stories in height or with more than 16 dwelling or sleeping units.
Exceptions:
1.Where each living unit is separated from other contiguous living units by fire barriers having a fire-resistance rating of not less than 3/4 hour, and where each living unit has either its own independent exit or its own independent stairway or ramp discharging at grade.
2.A separate fire alarm system is not required in buildings that are equipped throughout with an approved supervised automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 and having a local alarm to notify all occupants.
3.A fire alarm system is not required in buildings that do not have interior corridors serving dwelling units and are protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, provided that dwelling units either have a means of egress door opening directly to an exterior exit access that leads directly to the exits or are served by open-ended corridors designed in accordance with Section 1027.6, Exception 3.
4.A fire alarm system is not required in buildings that do not have interior corridors serving dwelling units, do not exceed three stories in height and comply with both of the following:
1103.8 Single- and multiple-station smoke alarms.
1103.8.1 Where required.
Existing Group I-1 and R occupancies shall be provided with single-station smoke alarms in accordance with Section 907.2.11. Interconnection and power sources shall be in accordance with Sections 1103.8.2 and 1103.8.3, respectively.
Exceptions:
1.Where the code that was in effect at the time of construction required smoke alarms and smoke alarms complying with those requirements are already provided.
2.Where smoke alarms have been installed in occupancies and dwellings that were not required to have them at the time of construction, additional smoke alarms shall not be required provided that the existing smoke alarms comply with requirements that were in effect at the time of installation.
3.Where smoke detectors connected to a fire alarm system have been installed as a substitute for smoke alarms.
1103.8.2 Interconnection.
Where more than one smoke alarm is required to be installed within an individual dwelling or sleeping unit, the smoke alarms shall be interconnected in such a manner that the activation of one alarm will activate all of the alarms in the individual unit. Physical interconnection of smoke alarms shall not be required where listed wireless alarms are installed and all alarms sound upon activation of one alarm. The alarm shall be clearly audible in all bedrooms over background noise levels with all intervening doors closed.
Exceptions:
1.Interconnection is not required in buildings that are not undergoing alterations, repairs or construction of any kind.
2.Smoke alarms in existing areas are not required to be interconnected where alterations or repairs do not result in the removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available that could provide access for interconnection without the removal of interior finishes.
1103.8.3 Power source.
Single-station smoke alarms shall receive their primary power from the building wiring provided that such wiring is served from a commercial source and shall be equipped with a battery backup. Smoke alarms with integral strobes that are not equipped with battery backup shall be connected to an emergency electrical system. Smoke alarms shall emit a signal when the batteries are low. Wiring shall be permanent and without a disconnecting switch other than as required for overcurrent protection.
Exceptions:
1.Smoke alarms are permitted to be solely battery operated in existing buildings where construction is not taking place.
2.Smoke alarms are permitted to be solely battery operated in buildings that are not served from a commercial power source.
3.Smoke alarms are permitted to be solely battery operated in existing areas of buildings undergoing alterations or repairs that do not result in the removal of interior walls or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available that could provide access for building wiring without the removal of interior finishes.
1103.9 Carbon monoxide detection.
Carbon monoxide detection shall be installed in existing Group I-1, I-2, I-4 and R occupancies and in classrooms in Group E occupancies where those units include any of the conditions identified in Sections 915.1.2 through 915.1.6. The carbon monoxide alarms shall be installed in the locations specified in Section 915.2 and the installation shall be in accordance with Section 915.4.
Exceptions:
1.Carbon monoxide alarms are permitted to be solely battery operated where the code that was in effect at the time of construction did not require carbon monoxide detectors to be provided.
2.Carbon monoxide alarms are permitted to be solely battery operated in dwelling units that are not served from a commercial power source.
3.A carbon monoxide detection system in accordance with Section 915.5 shall be an acceptable alternative to carbon monoxide alarms.
SECTION 1104
MEANS OF EGRESS FOR EXISTING BUILDINGS
1104.1 General.
1104.2 Elevators, escalators and moving walks.
1104.3 Exit sign illumination.
Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 footcandles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose.
Exception: Approved self-luminous signs that provide evenly illuminated letters shall have a minimum luminance of 0.06 foot-lamberts (0.21 cd/m2).
1104.4 Power source.
1104.5 Illumination emergency power.
Where means of egress illumination is provided, the power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress:
1.Group A having 50 or more occupants.
Exception: Assembly occupancies used exclusively as a place of worship and having an occupant load of less than 300.
2.Group B buildings three or more stories in height, buildings with 100 or more occupants above or below a level of exit discharge serving the occupants or buildings with 1,000 or more total occupants.
3.Group E in interior exit access and exit stairways and ramps, corridors, windowless areas with student occupancy, shops and laboratories.
4.Group F having more than 100 occupants.
5.Group I.
6.Group M.
Exception: Buildings less than 3,000 square feet (279 m2) in gross sales area on one story only, excluding mezzanines.
7.Group R-1.
Exception: Where each sleeping unit has direct access to the outside of the building at grade.
8.Group R-2.
Exception: Where each dwelling unit or sleeping unit has direct access to the outside of the building at grade.
1104.6 Guards.
Guards complying with this section shall be provided at the open sides of means of egress that are more than 30 inches (762 mm) above the floor or grade below.
1104.6.1 Height of guards.
Guards shall form a protective barrier not less than 42 inches (1067 mm) high.
Exceptions:
1.Existing guards on the open side of exit access and exit stairways and ramps shall be not less than 30 inches (760 mm) high.
2.Existing guards within dwelling units shall be not less than 36 inches (910 mm) high.
3.Existing guards in assembly seating areas.
1104.6.2 Opening limitations.
Open guards shall have balusters or ornamental patterns such that a 6-inch-diameter (152 mm) sphere cannot pass through any opening up to a height of 34 inches (864 mm).
Exceptions:
1.At elevated walking surfaces for access to, and use of, electrical, mechanical or plumbing systems or equipment, guards shall have balusters or be of solid materials such that a sphere with a diameter of 21 inches (533 mm) cannot pass through any opening.
2.In occupancies in Group I-3, F, H or S, the clear distance between intermediate rails measured at right angles to the rails shall not exceed 21 inches (533 mm).
3.Approved existing open guards.
1104.7 Size of doors.
The required capacity of each door opening shall be sufficient for the occupant load thereof and shall provide a minimum clear opening width of 28 inches (711 mm). Where this section requires a minimum clear opening width of 28 inches (711 mm) and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 28 inches (711 mm). The minimum clear opening height of doorways shall be 80 inches (2032 mm).
Exceptions:
1.The minimum and maximum width shall not apply to door openings that are not part of the required means of egress in occupancies in Group R-2 and R-3 units that are not required to be an Accessible Type A unit or Type B unit.
2.Door openings to storage closets less than 10 square feet (0.93 m2) in area shall not be limited by the minimum clear opening width.
3.The width of door leaves in revolving doors that comply with Section 1010.3.1 shall not be limited.
4.The maximum width of door leaves in power-operated doors that comply with Section 1010.3.2 shall not be limited.
5.Door openings within a dwelling unit shall have a minimum clear opening height of 78 inches (1981 mm).
6.In dwelling and sleeping units that are not required to be Accessible units, Type A units or Type B units, exterior door openings, other than the required exit door, shall have a minimum clear opening height of 76 inches (1930 mm).
7.Exit access doors serving a room not larger than 70 square feet (6.5 m2) shall have a minimum door leaf width of 24 inches (610 mm).
8.The minimum clear opening width shall not apply to doors for nonaccessible showers or sauna compartments.
9.The minimum clear opening width shall not apply to the doors for nonaccessible toilet stalls.
10.Door closers and door stops shall be permitted to be 78 inches (1980 mm) minimum above the floor.
1104.7.1 Group I-2.
In Group I-2 occupancies, means of egress doors where used for the movement of beds shall provide a minimum clear opening width of 411/2 inches (1054 mm).
Doors serving as means of egress doors and not used for movement of beds shall provide a minimum clear opening width of 32 inches (813 mm).
1104.7.2 Ambulatory care.
In ambulatory care facilities, doors serving as means of egress from patient treatment rooms shall provide a minimum clear opening width of 32 inches (813 mm).
1104.8 Opening force for doors.
The opening force for interior side-swinging doors without closers shall not exceed a 5-pound (22 N) force. The opening forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door in a closed position. For other side-swinging, sliding and folding doors, the door latch shall release when subjected to a force of not more than 15 pounds (66 N). The door shall be set in motion when subjected to a force not exceeding 30 pounds (133 N). The door shall swing to a full-open position when subjected to a force of not more than 50 pounds (222 N). Forces shall be applied to the latch side.
1104.9 Revolving doors.
Revolving doors shall comply with the following:
1.A revolving door shall not be located within 10 feet (3048 mm) of the foot or top of stairways or escalators. A dispersal area shall be provided between the stairways or escalators and the revolving doors.
2.The revolutions per minute for a revolving door shall not exceed those shown in Table 1104.9.
3.Each revolving door shall have a conforming side-hinged swinging door in the same wall as the revolving door and within 10 feet (3048 mm).
Exceptions:
1.A revolving door is permitted to be used without an adjacent swinging door for street-floor elevator lobbies provided that a stairway, escalator or door from other parts of the building does not discharge through the lobby and the lobby does not have any occupancy or use other than as a means of travel between elevators and a street.
2.Existing revolving doors where the number of revolving doors does not exceed the number of swinging doors within 20 feet (6096 mm).
TABLE 1104.9
REVOLVING DOOR SPEEDS
INSIDE DIAMETER (feet-inches) | POWER-DRIVEN-TYPE SPEED CONTROL (rpm) | MANUAL-TYPE SPEED CONTROL (rpm) |
6-6 | 11 | 12 |
7-0 | 10 | 11 |
7-6 | 9 | 11 |
8-0 | 9 | 10 |
8-6 | 8 | 9 |
9-0 | 8 | 9 |
9-6 | 7 | 8 |
10-0 | 7 | 8 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
1104.9.1 Egress component.
A revolving door used as a component of a means of egress shall comply with Section 1104.9 and all of the following conditions:
1.Revolving doors shall not be given credit for more than 50 percent of the required egress capacity.
2.Each revolving door shall be credited with not more than a 50-person capacity.
3.Revolving doors shall be capable of being collapsed when a force of not more than 130 pounds (578 N) is applied within 3 inches (76 mm) of the outer edge of a wing.
1104.10 Stair dimensions for existing stairways.
Existing stairways in buildings shall be permitted to remain if the rise does not exceed 81/4 inches (210 mm) and the run is not less than 9 inches (229 mm). Existing stairways can be rebuilt.
1104.11 Winders.
Existing winders shall be allowed to remain in use if they have a minimum tread depth of 6 inches (152 mm) and a minimum tread depth of 9 inches (229 mm) at a point 12 inches (305 mm) from the narrowest edge.
1104.12 Curved stairways.
Existing curved stairways shall be allowed to continue in use, provided that the minimum depth of tread is 10 inches (254 mm) and the smallest radius shall be not less than twice the width of the stairway.
1104.13 Stairway handrails.
Stairways shall have handrails on at least one side. Handrails shall be located so that all portions of the stairway width required for egress capacity are within 44 inches (1118 mm) of a handrail.
1104.13.1 Height.
Handrail height, measured above stair tread nosings, shall be uniform, not less than 30 inches (762 mm) and not more than 42 inches (1067 mm).
1104.14 Slope of ramps.
1104.15 Width of ramps.
[BE] 1104.16 Fire escape stairways.
[BE] 1104.16.1 Existing means of egress.
Fire escape stairways shall be permitted in existing buildings but shall not constitute more than 50 percent of the required exit capacity.
[BE] 1104.16.2 Opening protectives.
Doors and windows within 10 feet (3048 mm) of fire escape stairways shall be protected with 3/4-hour opening protectives.
Exception: Opening protectives shall not be required in buildings equipped throughout with an approved automatic sprinkler system.
[BE] 1104.16.4 Access.
[BE] 1104.16.5 Materials and strength.
Components of fire escape stairways shall be constructed of noncombustible materials. Fire escape stairways and balconies shall support the dead load plus a live load of not less than 100 pounds per square foot (4.78 kN/m2). Fire escape stairways and balconies shall be provided with a top and intermediate handrail on each side.
[BE] 1104.16.5.1 Examination.
[BE] 1104.16.6 Termination.
The lowest balcony shall not be more than 18 feet (5486 mm) from the ground. Fire escape stairways shall extend to the ground or be provided with counterbalanced stairs reaching the ground.
[BE] 1104.16.7 Maintenance.
Fire escape stairways shall be kept clear and unobstructed at all times and shall be maintained in good working order.
1104.17 Corridor construction.
Corridors serving an occupant load greater than 30 and the openings therein shall provide an effective barrier to resist the movement of smoke. Transoms, louvers, doors and other openings shall be kept closed or be self-closing. In Group I-2, corridors in areas housing patient sleeping or care rooms shall comply with Section 1105.5.
Exceptions:
1.Corridors in occupancies other than in Group H, that are equipped throughout with an approved automatic sprinkler system.
2.Corridors in occupancies in Group E where each room utilized for instruction or assembly has not less than one-half of the required means of egress doors opening directly to the exterior of the building at ground level.
3.Corridors that are in accordance with the International Building Code.
1104.17.1 Corridor openings.
Openings in corridor walls shall comply with the requirements of the International Building Code.
Exceptions:
1.Where 20-minute fire door assemblies are required, solid wood doors not less than 1.75 inches (44 mm) thick or insulated steel doors are allowed.
2.Openings protected with fixed wire glass set in steel frames.
3.Openings covered with 0.5-inch (12.7 mm) gypsum wallboard or 0.75-inch (19.1 mm) plywood on the room side.
4.Opening protection is not required where the building is equipped throughout with an approved automatic sprinkler system.
1104.18 Dead ends.
Where more than one exit or exit access doorway is required, the exit access shall be arranged such that dead ends do not exceed the limits specified in Table 1104.18.
Exceptions:
1.A dead-end corridor shall not be limited in length where the length of the dead-end corridor is less than 2.5 times the least width of the dead-end corridor.
2.In existing buildings, existing dead-end corridors shall be permitted to comply with lengths established in Section 804.7 of the International Existing Building Code. Any newly constructed dead-end corridors within an existing building shall be limited to the lengths allowed by the International Building Code.
TABLE 1104.18
COMMON PATH, DEAD-END AND TRAVEL DISTANCE LIMITS (by occupancy)
OCCUPANCY | COMMON PATH OF EGRESS TRAVEL LIMIT | DEAD-END LIMIT | EGRESS ACCESS TRAVEL DISTANCE LIMIT | |||
Unsprinklered (feet) | Sprinklered (feet) | Unsprinklered (feet) | Sprinklered (feet)j | Unsprinklered (feet) | Sprinklered (feet) | |
Group A | 75 | 20/75j | 20a | 20a | 200 | 250j |
Group Bh | 75g | 100j | 50 | 50 | 200 | 300j |
Group E | 75 | 75j | 20 | 50 | 200 | 250j |
Group F-1, S-1 | 75g | 100j | 50 | 50 | 200c | 250c, h, j |
Group F-2, S-2 | 75g | 100j | 50 | 50 | 300 | 400l |
Group H-1 | 25 | 25l | 0 | 0 | 75 | 75j, l |
Group H-2 | 50 | 100l | 0 | 0 | 75 | 100 j, l |
Group H-3 | 50 | 100l | 20 | 20 | 100 | 150j, l |
Group H-4 | 75 | 75l | 20 | 20 | 150 | 175j, l |
Group H-5 | 75 | 75l | 20 | 50 | 150 | 200j |
Group I-1 | 75 | 75l | 20 | 50 | 200 | 250j |
Group I-2 | Notes d, e, f | Notes d, e, f, j | Note e | Note e | 150 | 200b, j |
Group I-3 | 100 | 100j | NR | NR | 150b | 200b, j |
Group I-4 | NR | NR | 20 | 20 | 200 | 250j |
Group M | 75 | 100j | 50 | 50 | 200 | 250i, j |
Group R-1 | 75 | 75j, k | 50 | 50 | 200 | 250j, k |
Group R-2 | 75 | 125j, k | 50 | 50 | 200 | 250j, k |
Group R-3 | NR | NR | NR | NR | NR | NR |
Group R-4 | NR | NR | NR | NR | NR | NR |
Group U | 75g | 100j | 20 | 50 | 300 | 400j |
NR = No Requirements.
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2.
a.See Section 1030.9.5 for dead-end aisles in Group A occupancies.
b.This dimension is for the total travel distance, assuming incremental portions have fully utilized their allowable maximums. For travel distance within the room, and from the room exit access door to the exit, see the appropriate occupancy chapter.
c.See Section 412 of the International Building Code for special requirements on spacing of doors in aircraft hangars.
d.Separation of exit access doors within a care recipient sleeping room, or any suite that includes care recipient sleeping rooms, shall comply with Section 1105.5.6.
e.In smoke compartments containing care recipient sleeping rooms and treatment rooms, dead-end corridors shall comply with Section 1105.6.5.
f.In Group I-2, Condition 2, care recipient sleeping rooms or any suite that includes care recipient sleeping rooms shall comply with Section 1105.7.
g.Where a tenant space in Group B, S and U occupancies has an occupant load of not more than 30, the length of a common path of egress travel shall be not more than 100 feet.
h.Where the building, or portion of the building, is limited to one story and the height from the finished floor to the bottom of the ceiling or roof slab or deck is 24 feet or more, the exit access travel distance is increased to 400 feet.
i.For covered and open malls, the exit access travel distance is increased to 400 feet.
j.Buildings equipped with an approved automatic sprinkler system in accordance with Section 903.3.1.1.
k.Buildings equipped with an approved automatic sprinkler system in accordance with Section 903.3.1.2.
l.Group H occupancies equipped with an approved automatic sprinkler system in accordance with Section 903.2.5.
1104.21 Stairway discharge identification.
An interior exit stairway or ramp that continues below its level of exit discharge shall be arranged and marked to make the direction of egress to a public way readily identifiable.
1104.22 Exterior stairway protection.
Exterior exit stairways shall be separated from the interior of the building as required in Section 1027.6. Openings shall be limited to those necessary for egress from normally occupied spaces.
Exceptions:
1.Separation from the interior of the building is not required for buildings that are two stories or less above grade where the level of exit discharge serving such occupancies is the first story above grade.
2.Separation from the interior of the building is not required where the exterior stairway is served by an exterior balcony that connects two remote exterior stairways or other approved exits, with a perimeter that is not less than 50 percent open. To be considered open, the opening shall be not less than 50 percent of the height of the enclosing wall, with the top of the opening not less than 7 feet (2134 mm) above the top of the balcony.
3.Separation from the interior of the building is not required for an exterior stairway located in a building or structure that is permitted to have unenclosed interior stairways in accordance with Section 1023.
4.Separation from the open-ended corridors of the building is not required for exterior stairways provided that:
4.2.The open-ended corridors are connected on each end to an exterior exit stairway complying with Section 1027.
4.3.At any location in an open-ended corridor where a change of direction exceeding 45 degrees (0.79 rad) occurs, a clear opening of not less than 35 square feet (3 m2) or an exterior stairway shall be provided. Where clear openings are provided, they shall be located so as to minimize the accumulation of smoke or toxic gases.
1104.23 Minimum aisle width.
The minimum clear width of aisles shall comply with the following:
1.Forty-two inches (1067 mm) for stepped aisles having seating on each side.
Exception: Thirty-six inches (914 mm) where the stepped aisle serves fewer than 50 seats.
2.Thirty-six inches (914 mm) for stepped aisles having seating on only one side.
Exceptions:
1.Thirty inches (760 mm) for catchment areas serving not more than 60 seats.
2.Twenty-three inches (584 mm) between a stepped aisle handrail and seating where a stepped aisle does not serve more than five rows on one side.
3.Twenty inches (508 mm) between a stepped aisle handrail or guard and seating where the aisle is subdivided by a mid-aisle handrail.
4.Forty-two inches (1067 mm) for level or ramped aisles having seating on both sides.
Exceptions:
1.Thirty-six inches (914 mm) where the aisle serves fewer than 50 seats.
2.Thirty inches (760 mm) where the aisle serves fewer than 15 seats and does not serve as part of an accessible route.
5.Thirty-six inches (914 mm) for level or ramped aisles having seating on only one side.
Exception: Thirty inches (760 mm) for catchment areas serving not more than 60 seats and not serving as part of an accessible route.
6.In Group I-2, where aisles are used for movement of patients in beds, aisles shall comply with Section 1105.6.8.
1104.25 Egress path markings.
SECTION 1105
CONSTRUCTION REQUIREMENTS FOR EXISTING GROUP I-2
1105.1 General.
Existing Group I-2 shall meet all of the following requirements:
Where the provisions of this chapter conflict with the construction requirements that applied at the time of construction, the most restrictive provision shall apply.
1105.3 Construction.
TABLE 1105.3
FLOOR LEVEL LIMITATIONS FOR GROUP I-2, CONDITION 2
CONSTRUCTION TYPE | AUTOMATIC SPRINKLER SYSTEM | ALLOWABLE FLOOR LEVELa | |||
1 | 2 | 3 | 4 or more | ||
IA | Note b | P | P | P | P |
Note c | P | P | P | P | |
IB | Note b | P | P | P | P |
Note c | P | P | P | P | |
IIA | Note b | P | P | P | NP |
Note c | P | NP | NP | NP | |
IIB | Note b | P | P | NP | NP |
Note c | NP | NP | NP | NP | |
IIIA | Note b | P | P | NP | NP |
Note c | P | NP | NP | NP | |
IIIB | Note b | P | NP | NP | NP |
Note c | NP | NP | NP | NP | |
IV | Note b | P | P | NP | NP |
Note c | NP | NP | NP | NP | |
VA | Note b | P | P | NP | NP |
Note c | NP | NP | NP | NP | |
VB | Note b | P | NP | NP | NP |
Note c | NP | NP | NP | NP |
P = Permitted; NP = Not Permitted.
1105.4 Incidental uses in existing Group I-2.
TABLE 1105.4
INCIDENTAL USES IN EXISTING GROUP I-2 OCCUPANCIES
ROOM OR AREA | SEPARATION AND/OR PROTECTION |
Furnace room where any piece of equipment is over 400,000 Btu per hour input | 1 hour or provide automatic sprinkler system |
Rooms with boilers where the largest piece of equipment is over 15 psi and 10 horsepower | 1 hour or provide automatic sprinkler system |
Refrigerant machinery room | 1 hour or provide automatic sprinkler system |
Hydrogen fuel gas rooms, not classified as Group H | 2 hours |
Incinerator rooms | 2 hours and provide automatic sprinkler system |
Paint shops not classified as Group H | 2 hours; or 1 hour and provide automatic sprinkler system |
Laboratories and vocational shops, not classified as Group H | 1 hour or provide automatic sprinkler system |
Laundry rooms over 100 square feet | 1 hour or provide automatic sprinkler system |
Patient rooms equipped with padded surfaces | 1 hour or provide automatic sprinkler system |
Physical plant maintenance shops | 1 hour or provide automatic sprinkler system |
Waste and linen collection rooms with containers with total volume of 10 cubic feet or greater | 1 hour or provide automatic sprinkler system |
Storage rooms greater than 100 square feet | 1 hour or provide automatic sprinkler system |
Stationary storage battery systems having a liquid electrolyte capacity of more than 50 gallons for flooded lead-acid, nickel cadmium or VRLA, or more than 1,000 pounds for lithium-ion and lithium metal polymer used for facility standby power, emergency power or uninterruptable power supplies | 2 hours |
For SI: 1 square foot = 0.0929 m2, 1 pound per square inch (psi) = 6.9 kPa, 1 British thermal unit (Btu) per hour = 0.293 watts, 1 horsepower = 746 watts, 1 gallon = 3.785 L.
1105.4.2 Area limitations.
Incidental uses shall not occupy more than 10 percent of the building area of the story in which they are located.
1105.4.3 Separation and protection.
1105.4.3.2 Protection.
1105.5 Corridor construction.
1105.5.1 Materials.
The walls shall be of materials permitted by the building type of construction.
1105.5.2 Fire-resistance rating.
1105.5.3 Corridor wall continuity.
Corridor walls shall extend from the top of the foundation or floor below to one of the following:
1.The underside of the floor or roof sheathing, deck or slab above.
2.The underside of a ceiling above where the ceiling membrane is constructed to limit the passage of smoke.
3.The underside of a lay-in ceiling system where the ceiling system is constructed to limit the passage of smoke and where the ceiling tiles weigh not less than 1 pound per square foot (4.88 kg/m2) of tile.
1105.5.4 Openings in corridor walls.
1105.5.4.1 Windows.
Windows in corridor walls shall be sealed to limit the passage of smoke, or the window shall be automatic-closing upon detection of smoke, or the window opening shall be protected by an automatic closing device that closes upon detection of smoke.
1105.5.4.2 Doors.
1105.5.4.2.1 Louvers.
Doors in corridor walls shall not include louvers, transfer grills or similar openings.
1105.5.4.2.2 Corridor doors.
Doors in corridor walls shall limit the transfer of smoke by complying with the following:
1.Doors shall be constructed of not less than 13/4 inch-thick (44 mm) solid bonded-core wood or capable of resisting fire not less than 1/3 hour.
Exception:Corridor doors in buildings equipped throughout with an automatic sprinkler system.
2.Frames for side-hinged swinging doors shall have stops on the sides and top to limit transfer of smoke.
3.Where provided, vision panels in doors shall be a fixed glass window assembly installed to limit the passage of smoke. Existing wired glass panels with steel frames shall be permitted to remain in place.
4.The clearance between the bottom of the door and floor shall not exceed 1 inch (25 mm).
5.Doors shall be positive latching with devices that resist not less than 5 pounds (22.2 N). Roller latches are prohibited.
6.Mail slots or similar openings shall be permitted in accordance with Section 1105.5.4.3.
1105.5.4.2.3 Dutch doors.
1105.5.4.2.4 Self- or automatic-closing doors.
1105.5.4.2.5 Protective plates.
1105.5.4.3 Openings in corridor walls and doors.
In other than smoke compartments containing patient sleeping rooms, mail slots, pass-through windows or similar openings shall not be required to be protected where the aggregate area of the openings between the corridor and a room are not greater than 80 square inches (51 613 mm2) and are located with the top edge of any opening not higher than 48 inches above the floor.
1105.5.5 Penetrations.
The space around penetrating items shall be filled with an approved material to limit the passage of smoke.
1105.5.6 Joints.
Joints shall be filled with an approved material to limit the passage of smoke.
1105.5.7 Ducts and air transfer openings.
1105.6 Means of egress.
1105.6.1 Two means of egress.
1105.6.2 Size of door.
Means of egress doors used for the movement of patients in beds shall provide a minimum clear width of 411/2 inches (1054 mm). The height of the door opening shall be not less than 80 inches (2032 mm).
Exceptions:
1.Door closers and door stops shall be permitted to be 78 inches (1981 mm) minimum above the floor.
2.In Group I-2, Condition 1, existing means of egress doors used for the movement of patients in beds that provide a minimum clear width of 32 inches (813 mm) shall be permitted to remain.
1105.6.3 Group I-2 occupancies.
In Group I-2, where a door serves as an opening protective in a fire barrier, smoke barrier or fire wall and where the door is equipped with a hold-open device, such door shall automatically close upon any of the following conditions:
1.Actuation of smoke detectors initiating the hold-open device.
2.Activation of the fire alarm system within the zone.
3.Activation of an automatic sprinkler system within the zone.
1105.6.4 Ramps.
1105.6.5 Corridor width.
1105.6.6 Dead-end corridors.
1105.6.7 Separation of exit access doors.
1105.6.8 Aisles.
1105.7 Smoke compartments.
1105.7.1 Design.
1105.7.1.1 Refuge areas.
Refuge areas shall be provided within each smoke compartment. The size of the refuge area shall accommodate the occupants and care recipients from the adjoining smoke compartment. Where a smoke compartment is adjoined by two or more smoke compartments, the minimum area of the refuge area shall accommodate the largest occupant load of the adjoining compartments.
The size of the refuge area shall provide the following:
1.Not less than 30 net square feet (2.8 m2) for each care recipient confined to a bed or stretcher.
2.Not less than 15 square feet (1.4 m2) for each resident in a Group I-2 using mobility assistance devices.
3.Not less than 6 square feet (0.56 m2) for each occupant not addressed in Items 1 and 2.
Areas of spaces permitted to be included in the calculation of the refuge area are corridors, sleeping areas, treatment rooms, lounge or dining areas and other low-hazard areas.
1105.7.3 Opening protectives.
Openings in smoke barriers shall be protected in accordance with Section 716 of the International Building Code. Opening protectives shall have a minimum fire protection rating of 1/3 hour.
Exceptions:
1.Existing wired glass vision panels in doors shall be permitted to remain.
2.Existing nonlabeled protection plates shall be permitted to remain.
1105.9 Group I-2 automatic sprinkler system.
An automatic sprinkler system installed in accordance with Section 903.3.1.1 shall be provided throughout the floor containing the Group I-2 fire area. The sprinkler system shall be provided throughout the floor where the Group I-2 occupancy is located, on all floors between the Group I-2 occupancy fire area and the level of exit discharge, the level of exit discharge, and all floors below the level of exit discharge.
Exception: Floors classified as an open parking garage are not required to be sprinklered.
1105.10 Group I-2 automatic fire alarm system.
An automatic fire alarm system shall be installed in existing Group I-2 occupancies in accordance with Section 907.2.6.2.
Exception: Manual fire alarm boxes in patient sleeping areas shall not be required at exits if located at all nurses’ control stations or other constantly attended staff locations, provided such that manual fire alarm boxes are visible, are provided with ready access, and travel distances required in Section 907.4.2.1 are not exceeded.
1105.11 Essential electrical systems.
SECTION 1106
REQUIREMENTS FOR OUTDOOR OPERATIONS
1106.1 Tire storage yards.
1106.1.1 Access to piles.
Access roadways shall be within 150 feet (45 720 mm) of any point in the storage yard where storage piles are located not less than 20 feet (6096 mm) from any storage pile.