• CHAPTER6
    SPECIFIC APPLIANCES

    User note:

    About this chapter: Similar to Chapter 9 of the International Mechanical Code®, Chapter 6 of this code addresses specific types of appliances in detail. Requirements include listing and labeling, installation, location, clearances, venting and exhausting, controls, support and combustion and ventilation air.

    SECTION601 (IFGC)
    GENERAL

    601.1 Scope.

    This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein.

    SECTION602 (IFGC)
    DECORATIVE APPLIANCES
    FOR INSTALLATION IN FIREPLACES

    602.1 General.

    Decorative appliances for installation in approved solid fuel-burning fireplaces shall be tested in accordance with ANSI Z21.60/CSA 6.26 and shall be installed in accordance with the manufacturer’s instructions. Manually lighted natural gas decorative appliances shall be tested in accordance with ANSI Z21.84.

    602.2 Flame safeguard device.

    Decorative appliances for installation in approved solid fuel-burning fireplaces, with the exception of those tested in accordance with ANSI Z21.84, shall utilize a direct ignition device, an ignitor or a pilot flame to ignite the fuel at the main burner, and shall be equipped with a flame safeguard device. The flame safeguard device shall automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inoperative.

    602.3 Prohibited installations.

    Decorative appliances for installation in fireplaces shall not be installed where prohibited by Section 303.3.

    SECTION603 (IFGC)
    LOG LIGHTERS

    603.1 General.

    Log lighters shall be tested in accordance with CSA 8 and installed in accordance with the manufacturer’s instructions.

    SECTION604 (IFGC)
    VENTED GAS FIREPLACES
    (DECORATIVE APPLIANCES)

    604.1 General.

    Vented gas fireplaces shall be tested in accordance with ANSI Z21.50/CSA 2.22, shall be installed in accordance with the manufacturer’s instructions and shall be designed and equipped as specified in Section 602.2.

    604.2 Access.

    Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building.

    SECTION605 (IFGC)
    VENTED GAS FIREPLACE HEATERS

    605.1 General.

    Vented gas fireplace heaters shall be installed in accordance with the manufacturer’s instructions, shall be tested in accordance with ANSI Z21.88/CSA 2.33 and shall be designed and equipped as specified in Section 602.2.

    SECTION606 (IFGC)
    INCINERATORS AND CREMATORIES

    606.1 General.

    Incinerators and crematories shall be installed in accordance with the manufacturer’s instructions.

    SECTION607 (IFGC)
    COMMERCIAL-INDUSTRIAL INCINERATORS

    607.1 Incinerators, commercial-industrial.

    Commsercial-industrial-type incinerators shall be constructed and installed in accordance with NFPA 82.

    SECTION608 (IFGC)
    VENTED WALL FURNACES

    608.1 General.

    Vented wall furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions.

    608.2 Venting.

    Vented wall furnaces shall be vented in accordance with Section 503.

    608.3 Location.

    Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible furnishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building.

    608.4 Door swing.

    Vented wall furnaces shall be located so that a door cannot swing within 12 inches (305 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance.

    608.5 Ducts prohibited.

    Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance.

    608.6 Access.

    Vented wall furnaces shall be provided with access for cleaning of heating surfaces, removal of burners, replacement of sections, motors, controls, filters and other working parts, and for adjustments and lubrication of parts requiring such attention. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building construction.

    SECTION609 (IFGC)
    FLOOR FURNACES

    609.1 General.

    Floor furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions.

    609.2 Placement.

    The following provisions apply to floor furnaces:

    1. 1.Floors. Floor furnaces shall not be installed in the floor of any doorway, stairway landing, aisle or passageway of any enclosure, public or private, or in an exitway from any such room or space.

    2. 2.Walls and corners. The register of a floor furnace with a horizontal warm-air outlet shall not be placed closer than 6 inches (152 mm) to the nearest wall. A distance of not less than 18 inches (457 mm) from two adjoining sides of the floor furnace register to walls shall be provided to eliminate the necessity of occupants walking over the warm-air discharge. The remaining sides shall be permitted to be placed not closer than 6 inches (152 mm) to a wall. Wall-register models shall not be placed closer than 6 inches (152 mm) to a corner.

    3. 3.Draperies. The furnace shall be placed so that a door, drapery or similar object cannot be nearer than 12 inches (305 mm) to any portion of the register of the furnace.

    4. 4.Floor construction. Floor furnaces shall not be installed in concrete floor construction built on grade.

    5. 5.Thermostat. The controlling thermostat for a floor furnace shall be located within the same room or space as the floor furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace.

    609.3 Bracing.

    The floor around the furnace shall be braced and headed with a support framework designed in accordance with the International Building Code.

    609.4 Clearance.

    The lowest portion of the floor furnace shall have not less than a 6-inch (152 mm) clearance from the grade level; except where the lower 6-inch (152 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be not less than 2 inches (51 mm). Where such clearances cannot be provided, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12-inch (305 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18-inch (457 mm) minimum clearance.

    609.5 First floor installation.

    Where the basement story level below the floor in which a floor furnace is installed is utilized as habitable space, such floor furnaces shall be enclosed as specified in Section 609.6 and shall project into a nonhabitable space.

    609.6 Upper floor installations.

    Floor furnaces installed in upper stories of buildings shall project below into nonhabitable space and shall be separated from the nonhabitable space by an enclosure constructed of noncombustible materials. The floor furnace shall be provided with access, clearance to all sides and bottom of not less than 6 inches (152 mm) and combustion air in accordance with Section 304.

    SECTION610 (IFGC)
    DUCT FURNACES

    610.1 General.

    Duct furnaces shall be tested in accordance with ANSI Z83.8/CSA 2.6 or UL 795 and shall be installed in accordance with the manufacturer’s instructions.

    610.2 Access panels.

    Ducts connected to duct furnaces shall have removable access panels on both the upstream and downstream sides of the furnace.

    610.3 Location of draft hood and controls.

    The controls, combustion air inlets and draft hoods for duct furnaces shall be located outside of the ducts. The draft hood shall be located in the same enclosure from which combustion air is taken.

    610.4 Circulating air.

    Where a duct furnace is installed so that supply ducts convey air to areas outside the space containing the furnace, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.

    The duct furnace shall be installed on the positive pressure side of the circulating air blower.

    SECTION611 (IFGC)
    NONRECIRCULATING DIRECT-FIRED
    INDUSTRIAL AIR HEATERS

    611.1 General.

    Nonrecirculating direct-fired industrial air heaters shall be listed to ANSI Z83.4/CSA 3.7 and shall be installed in accordance with the manufacturer’s instructions.

    611.2 Installation.

    Nonrecirculating direct-fired industrial air heaters shall not be used to supply any area containing sleeping quarters. Nonrecirculating direct-fired industrial air heaters shall be installed only in industrial or commercial occupancies. Nonrecirculating direct-fired industrial air heaters shall be permitted to provide ventilation air.

    611.3 Clearance from combustible materials.

    Nonrecirculating direct-fired industrial air heaters shall be installed with a clearance from combustible materials of not less than that shown on the rating plate and in the manufacturer’s instructions.

    611.4 Supply air.

    All air handled by a nonrecirculating direct-fired industrial air heater, including combustion air, shall be ducted directly from the outdoors.

    611.5 Outdoor air louvers.

    If outdoor air louvers of either the manual or automatic type are used, such devices shall be proven to be in the open position prior to allowing the main burners to operate.

    611.6 Atmospheric vents and gas reliefs or bleeds.

    Nonrecirculating direct-fired industrial air heaters with valve train components equipped with atmospheric vents or gas reliefs or bleeds shall have their atmospheric vent lines or gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter.

    611.7 Relief opening.

    The design of the installation shall include provisions to permit nonrecirculating direct-fired industrial air heaters to operate at rated capacity without overpressurizing the space served by the heaters by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a combination of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Where motorized dampers or closable louvers are used, they shall be verified to be in their full open position prior to main burner operation.

    611.8 Access.

    Nonrecirculating direct-fired industrial air heaters shall be provided with access for removal of burners; replacement of motors, controls, filters and other working parts; and for adjustment and lubrication of parts requiring maintenance.

    611.9 Purging.

    Inlet ducting, where used, shall be purged by not less than four air changes prior to an ignition attempt.

    SECTION612 (IFGC)
    RECIRCULATING DIRECT-FIRED
    INDUSTRIAL AIR HEATERS

    612.1 General.

    Recirculating direct-fired industrial air heaters shall be listed to ANSI Z83.18 and shall be installed in accordance with the manufacturer’s instructions.

    612.2 Location.

    Recirculating direct-fired industrial air heaters shall be installed only in industrial and commercial occupancies. Recirculating direct-fired air heaters shall not serve any area containing sleeping quarters. Recirculating direct-fired industrial air heaters shall not be installed in hazardous locations or in buildings that contain flammable solids, liquids or gases, explosive materials or substances that can become toxic when exposed to flame or heat.

    612.3 Installation.

    Direct-fired industrial air heaters shall be permitted to be installed in accordance with their listing and the manufacturer’s instructions. Direct-fired industrial air heaters shall be installed only in industrial or commercial occupancies. Direct-fired industrial air heaters shall be permitted to provide fresh air ventilation.

    612.4 Clearance from combustible materials.

    Direct-fired industrial air heaters shall be installed with a clearance from combustible material of not less than that shown on the label and in the manufacturer’s instructions.

    612.5 Air supply.

    Air to direct-fired industrial air heaters shall be taken from the building, ducted directly from outdoors, or a combination of both. Direct-fired industrial air heaters shall incorporate a means to supply outside ventilation air to the space at a rate of not less than 4 cubic feet per minute per 1,000 Btu per hour (0.38 m3 per min per kW) of rated input of the heater. If a separate means is used to supply ventilation air, an interlock shall be provided so as to lock out the main burner operation until the mechanical means is verified. Where outside air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation.

    612.6 Atmospheric vents, gas reliefs or bleeds.

    Direct-fired industrial air heaters with valve train components equipped with atmospheric vents, gas reliefs or bleeds shall have their atmospheric vent lines and gas reliefs or bleeds lead to the outdoors.

    Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter.

    612.7 Relief opening.

    The design of the installation shall include adequate provision to permit direct-fired industrial air heaters to operate at rated capacity by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a combination of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Where motorized dampers or closable louvers are used, they shall be verified to be in their full open position prior to main burner operation.

    SECTION613 (IFGC)
    CLOTHES DRYERS

    613.1 General.

    Clothes dryers shall be tested in accordance with ANSI Z21.5.1/CSA 7.1 or ANSI Z21.5.2/CSA 7.2 and shall be installed in accordance with the manufacturer’s instructions.

    SECTION614 (IFGC)
    CLOTHES DRYER EXHAUST

    [M]614.1Installation.

    Clothes dryers shall be exhausted in accordance with the manufacturer’s instructions. Dryer exhaust systems shall be independent of all other systems, and shall convey the moisture and any products of combustion to the outside of the building.

    [M]614.2Duct penetrations.

    Ducts that exhaust clothes dryers shall not penetrate or be located within any fireblocking, draftstopping or any wall, floor/ceiling or other assembly required by the International Building Code to be fire-resistance rated, unless such duct is constructed of galvanized steel or aluminum of the thickness specified in Table 603.4 of the International Mechanical Code and the fire-resistance rating is maintained in accordance with the International Building Code. Fire dampers shall not be installed in clothes dryer exhaust duct systems.

    [M]614.3Cleaning access.

    Each vertical duct riser for dryers listed to ANSI Z21.5.2/CSA 7.2 shall be provided with a cleanout or other means for cleaning the interior of the duct.

    [M]614.4Exhaust installation.

    Exhaust ducts for clothes dryers shall terminate on the outside of the building and shall be equipped with a backdraft damper. Screens shall not be installed at the duct termination. Ducts shall not be connected or installed with sheet metal screws or other fasteners that will obstruct the flow. Clothes dryer exhaust ducts shall not be connected to a vent connector, vent or chimney. Clothes dryer exhaust ducts shall not extend into or through ducts or plenums. Clothes dryer exhaust ducts shall be sealed in accordance with Section 603.9 of the International Mechanical Code.

    614.4.1Exhaust termination outlet and passageway.

    The passageway of dryer exhaust duct terminals shall be undiminished in size and shall provide an open area of not less than 12.5 square inches (8065 mm2).

    [M]614.5Dryer exhaust duct power ventilators.

    Domestic dryer exhaust duct power ventilators shall be listed and labeled to UL 705 for use in dryer exhaust duct systems. The dryer exhaust duct power ventilator shall be installed in accordance with the manufacturer’s instructions.

    [M]614.6Makeup air.

    Installations exhausting more than 200 cfm (0.09 m3/s) shall be provided with makeup air. Where a closet is designed for the installation of a clothes dryer, an opening having an area of not less than 100 square inches (645 mm2) for makeup air shall be provided in the closet enclosure, or makeup air shall be provided by other approved means.

    [M]614.7Protection required.

    Protective shield plates shall be placed where nails or screws from finish or other work are likely to penetrate the clothes dryer exhaust duct. Shield plates shall be placed on the finished face of all framing members where there is less than 11/4 inches (32 mm) between the duct and the finished face of the framing member. Protective shield plates shall be constructed of steel, shall have a minimum thickness of 0.062 inch (1.6 mm) and shall extend not less than 2 inches (51 mm) above sole plates and below top plates.

    [M]614.8Domestic clothes dryer exhaust ducts.

    Exhaust ducts for domestic clothes dryers shall conform to the requirements of Sections 614.8.1 through 614.8.6.

    [M]614.8.1Material and size.

    Exhaust ducts shall have a smooth interior finish and shall be constructed of metal not less than 0.016 inch (0.4 mm) in thickness. The exhaust duct size shall be 4 inches (102 mm) nominal in diameter.

    [M]614.8.2Duct installation.

    Exhaust ducts shall be supported at 4-foot (1219 mm) intervals and secured in place. The insert end of the duct shall extend into the adjoining duct or fitting in the direction of airflow. Ducts shall not be joined with screws or similar fasteners that protrude more than 1/8 inch (3.2 mm) into the inside of the duct. Where dryer exhaust ducts are enclosed in wall or ceiling cavities, such cavities shall allow the installation of the duct without deformation.

    [M]614.8.3Transition ducts.

    Transition ducts used to connect the dryer to the exhaust duct system shall be a single length that is listed and labeled in accordance with UL 2158A. Transition ducts shall be not more than 8 feet (2438 mm) in length, and shall not be concealed within construction.

    [M]614.8.4Duct length.

    The maximum allowable exhaust duct length shall be determined by one of the methods specified in Sections 614.8.4.1 through 614.8.4.3.

    [M]614.8.4.1Specified length.

    The maximum length of the exhaust duct shall be 35 feet (10 668 mm) from the connection to the transition duct from the dryer to the outlet terminal. Where fittings are utilized, the maximum length of the exhaust duct shall be reduced in accordance with Table 614.8.4.1.

    [M] TABLE 614.8.4.1

    DRYER EXHAUST DUCT FITTING EQUIVALENT LENGTH

    DRYER EXHAUST DUCT FITTING TYPEEQUIVALENT LENGTH
    4 inch radius mitered 45-degree elbow2 feet, 6 inches
    4 inch radius mitered 90-degree elbow5 feet
    6 inch radius smooth 45-degree elbow1 foot
    6 inch radius smooth 90-degree elbow1 foot, 9 inches
    8 inch radius smooth 45-degree elbow1 foot
    8 inch radius smooth 90-degree elbow1 foot, 7 inches
    10 inch radius smooth 45-degree elbow9 inches
    10 inch radius smooth 90-degree elbow1 foot, 6 inches

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.01745 rad.

    [M]614.8.4.2Manufacturer’s instructions.

    The maximum length of the exhaust duct shall be determined by the dryer manufacturer’s installation instructions. The code official shall be provided with a copy of the installation instructions for the make and model of the dryer. Where the exhaust duct is to be concealed, the installation instructions shall be provided to the code official prior to the concealment inspection. In the absence of fitting equivalent length calculations from the clothes dryer manufacturer, Table 614.8.4.1 shall be utilized.

    [M]614.8.4.3Dryer exhaust duct power ventilator length.

    The maximum length of the exhaust duct shall be determined by the dryer exhaust duct power ventilator manufacturer’s installation instructions.

    [M]614.8.5Length identification.

    Where the exhaust duct equivalent length exceeds 35 feet (10 668 mm), the equivalent length of the exhaust duct shall be identified on a permanent label or tag. The label or tag shall be located within 6 feet (1829 mm) of the exhaust duct connection.

    [M]614.8.6Exhaust duct required.

    Where space for a clothes dryer is provided, an exhaust duct system shall be installed.

    Where the clothes dryer is not installed at the time of occupancy, the exhaust duct shall be capped at the location of the future dryer.

    Exception: Where a listed condensing clothes dryer is installed prior to occupancy of the structure.

    [M]614.9Commercial clothes dryers.

    The installation of dryer exhaust ducts serving Type 2 clothes dryers shall comply with the appliance manufacturer’s instructions. Exhaust fan motors installed in exhaust systems shall be located outside of the airstream. In multiple installations, the fan shall operate continuously or be interlocked to operate when any individual unit is operating. Ducts shall have a minimum clearance of 6 inches (152 mm) to combustible materials.

    [M]614.10Common exhaust systems for clothes dryers located in multistory structures.

    Where a common multi-story duct system is designed and installed to convey exhaust from multiple clothes dryers, the construction of such system shall be in accordance with all of the following:

    1. 1.The shaft in which the duct is installed shall be constructed and fire-resistance rated as required by the International Building Code.

    2. 2.Dampers shall be prohibited in the exhaust duct. Penetrations of the shaft and ductwork shall be protected in accordance with Section 607.5.5, Exception 2, of the International Mechanical Code.

    3. 3.Rigid metal ductwork shall be installed within the shaft to convey the exhaust. The ductwork shall be constructed of sheet steel having a minimum thickness of 0.0187 inch (0.471 mm) (No. 26 gage) and in accordance with SMACNA Duct Construction Standards.

    4. 4.The ductwork within the shaft shall be designed and installed without offsets.

    5. 5.The exhaust fan motor design shall be in accordance with Section 503.2 of the International Mechanical Code.

    6. 6.The exhaust fan motor shall be located outside of the airstream.

    7. 7.The exhaust fan shall run continuously, and shall be connected to a standby power source.

    8. 8.The exhaust fan operation shall be monitored in an approved location and shall initiate an audible or visual signal when the fan is not in operation.

    9. 9.Makeup air shall be provided for the exhaust system.

    10. 10.A cleanout opening shall be located at the base of the shaft to provide access to the duct to allow for cleaning and inspection. The finished opening shall be not less than 12 inches by 12 inches (305 mm by 305 mm).

    11. 11.Screens shall not be installed at the termination.

    SECTION615 (IFGC)
    SAUNA HEATERS

    615.1 General.

    Sauna heaters shall be installed in accordance with the manufacturer’s instructions.

    615.2 Location and protection.

    Sauna heaters shall be located so as to minimize the possibility of accidental contact by a person in the room.

    615.2.1 Guards.

    Sauna heaters shall be protected from accidental contact by an approved guard or barrier of material having a low coefficient of thermal conductivity. The guard shall not substantially affect the transfer of heat from the heater to the room.

    615.3 Access.

    Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building.

    615.4 Combustion and dilution air intakes.

    Sauna heaters of other than the direct-vent type shall be installed with the draft hood and combustion air intake located outside the sauna room. Where the combustion air inlet and the draft hood are in a dressing room adjacent to the sauna room, there shall be provisions to prevent physically blocking the combustion air inlet and the draft hood inlet, and to prevent physical contact with the draft hood and vent assembly, or warning notices shall be posted to avoid such contact. Any warning notice shall be easily readable, shall contrast with its background and the wording shall be in letters not less than 1/4 inch (6.4 mm) high.

    615.5 Combustion and ventilation air.

    Combustion air shall not be taken from inside the sauna room. Combustion and ventilation air for a sauna heater not of the direct-vent type shall be provided to the area in which the combustion air inlet and draft hood are located in accordance with Section 304.

    615.6 Heat and time controls.

    Sauna heaters shall be equipped with a thermostat that will limit room temperature to 194°F (90°C). If the thermostat is not an integral part of the sauna heater, the heat-sensing element shall be located within 6 inches (152 mm) of the ceiling. If the heat-sensing element is a capillary tube and bulb, the assembly shall be attached to the wall or other support, and shall be protected against physical damage.

    615.6.1 Timers.

    A timer, if provided to control main burner operation, shall have a maximum operating time of 1 hour. The control for the timer shall be located outside the sauna room.

    615.7 Sauna room.

    A ventilation opening into the sauna room shall be provided. The opening shall be not less than 4 inches by 8 inches (102 mm by 203 mm) located near the top of the door into the sauna room.

    615.7.1 Warning notice.

    The following permanent notice, constructed of approved material, shall be mechanically attached to the sauna room on the outside:

    WARNING: DO NOT EXCEED 30 MINUTES IN
    SAUNA. EXCESSIVE EXPOSURE CAN BE HARMFUL
    TO HEALTH. ANY PERSON WITH POOR HEALTH
    SHOULD CONSULT A PHYSICIAN BEFORE USING
    SAUNA.

    The words shall contrast with the background and the wording shall be in letters not less than 1/4 inch (6.4 mm) high.

    Exception: This section shall not apply to one- and two-family dwellings.

    SECTION616 (IFGC)
    ENGINE AND GAS
    TURBINE-POWERED EQUIPMENT

    616.1 Powered equipment.

    Permanently installed equipment powered by internal combustion engines and turbines shall be installed in accordance with the manufacturer’s instructions and NFPA 37. Stationary engine generator assemblies shall meet the requirements of UL 2200.

    616.2 Gas supply connection.

    Equipment powered by internal combustion engines and turbines shall not be rigidly connected to the gas supply piping.

    SECTION617 (IFGC)
    POOL AND SPA HEATERS

    617.1 General.

    Pool and spa heaters shall be tested in accordance with ANSI Z21.56/CSA 4.7 and shall be installed in accordance with the manufacturer’s instructions.

    SECTION618 (IFGC)
    FORCED-AIR WARM-AIR FURNACES

    618.1 General.

    Forced-air warm-air furnaces shall be tested in accordance with ANSI Z21.47/CSA 2.3 or UL 795 and shall be installed in accordance with the manufacturer’s instructions.

    618.2 Dampers.

    Volume dampers shall not be placed in the air inlet to a furnace in a manner that will reduce the required air to the furnace.

    618.3 Prohibited sources.

    Outdoor or return air for forced-air heating and cooling systems shall not be taken from the following locations:

    1. 1.Closer than 10 feet (3048 mm) from an appliance vent outlet, a vent opening from a plumbing drainage system or the discharge outlet of an exhaust fan, unless the outlet is 3 feet (914 mm) above the outside air inlet.

    2. 2.Where there is the presence of objectionable odors, fumes or flammable vapors; or where located less than 10 feet (3048 mm) above the surface of any abutting public way or driveway; or where located at grade level by a sidewalk, street, alley or driveway.

    3. 3.A hazardous or insanitary location or a refrigeration machinery room as defined in the International Mechanical Code.

    4. 4.A room or space, the volume of which is less than 25 percent of the entire volume served by such system. Where connected by a permanent opening having an area sized in accordance with this code, adjoining rooms or spaces shall be considered to be a single room or space for the purpose of determining the volume of such rooms or spaces.

      Exception: The minimum volume requirement shall not apply where the amount of return air taken from a room or space is less than or equal to the amount of supply air delivered to such room or space.

    5. 5.A room or space containing an appliance where such a room or space serves as the sole source of return air.

      Exception: This shall not apply where:

      1. 1.The appliance is a direct-vent appliance or an appliance not requiring a vent in accordance with Section 501.8.

      2. 2.The room or space complies with the following requirements:

        1. 2.1.The return air shall be taken from a room or space having a volume exceeding 1 cubic foot for each 10 Btu/h (9.6 L/W) of combined input rating of all fuel-burning appliances therein.

        2. 2.2.The volume of supply air discharged back into the same space shall be approximately equal to the volume of return air taken from the space.

        3. 2.3.Return-air inlets shall not be located within 10 feet (3048 mm) of a draft hood in the same room or space or the combustion chamber of any atmospheric burner appliance in the same room or space.

      3. 3.Rooms or spaces containing solid fuel-burning appliances, provided that return-air inlets are located not less than 10 feet (3048 mm) from the firebox of such appliances.

    6. 6.A closet, bathroom, toilet room, kitchen, garage, boiler room, furnace room or unconditioned attic.

      Exceptions:

      1. 1.Where return air intakes are located not less than 10 feet (3048 mm) from cooking appliances and serve only the kitchen area, taking return air from a kitchen area shall not be prohibited.

      2. 2.Dedicated forced air systems serving only a garage shall not be prohibited from obtaining return air from the garage.

    7. 7.A crawl space by means of direct connection to the return side of a forced-air system. Transfer openings in the crawl space enclosure shall not be prohibited.

    618.4 Screen.

    Required outdoor air inlets for residential portions of a building shall be covered with a screen having 1/4-inch (6.4 mm) openings. Required outdoor air inlets serving a nonresidential portion of a building shall be covered with screen having openings larger than 1/4 inch (6.4 mm) and not larger than 1 inch (25 mm).

    618.5 Return-air limitation.

    Return air from one dwelling unit shall not be discharged into another dwelling unit.

    618.6 (IFGS) Furnace plenums and air ducts.

    Where a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside of the space containing the furnace, the return air shall be handled by a duct(s) sealed to the furnace casing and terminating outside of the space containing the furnace.

    SECTION619 (IFGC)
    CONVERSION BURNERS

    619.1 Conversion burners.

    The installation of conversion burners shall conform to ANSI Z21.8.

    SECTION620 (IFGC)
    UNIT HEATERS

    620.1 General.

    Unit heaters shall be tested in accordance with ANSI Z83.8/CSA 2.6 and shall be installed in accordance with the manufacturer’s instructions.

    620.2 Support.

    Suspended-type unit heaters shall be supported by elements that are designed and constructed to accommodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible material.

    620.3 Ductwork.

    Ducts shall not be connected to a unit heater unless the heater is listed for such installation.

    620.4 Clearance.

    Suspended-type unit heaters shall be installed with clearances to combustible materials of not less than 18 inches (457 mm) at the sides, 12 inches (305 mm) at the bottom and 6 inches (152 mm) above the top where the unit heater has an internal draft hood or 1 inch (25 mm) above the top of the sloping side of the vertical draft hood.

    Floor-mounted-type unit heaters shall be installed with clearances to combustible materials at the back and one side only of not less than 6 inches (152 mm). Where the flue gases are vented horizontally, the 6-inch (152 mm) clearance shall be measured from the draft hood or vent instead of the rear wall of the unit heater. Floor-mounted-type unit heaters shall not be installed on combustible floors unless listed for such installation.

    Clearances for servicing all unit heaters shall be in accordance with the manufacturer’s installation instructions.

    Exception: Unit heaters listed for reduced clearance shall be permitted to be installed with such clearances in accordance with their listing and the manufacturer’s instructions.

    620.5 (IFGS) Installation in commercial garages and aircraft hangars.

    Unit heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11.

    SECTION621 (IFGC)
    UNVENTED ROOM HEATERS

    621.1 General.

    Unvented room heaters shall be tested in accordance with ANSI Z21.11.2 and shall be installed in accordance with the conditions of the listing and the manufacturer’s instructions. Unvented room heaters utilizing fuels other than fuel gas shall be regulated by the International Mechanical Code.

    621.2 Prohibited use.

    One or more unvented room heaters shall not be used as the sole source of comfort heating in a dwelling unit.

    621.3 Input rating.

    Unvented room heaters shall not have an input rating in excess of 40,000 Btu/h (11.7 kW).

    621.4 Prohibited locations.

    Unvented room heaters shall not be installed within occupancies in Groups A, E and I. The location of unvented room heaters shall comply with Section 303.3.

    621.5 Room or space volume.

    The aggregate input rating of all unvented appliances installed in a room or space shall not exceed 20 Btu/h per cubic foot (207 W/m3) of volume of such room or space. Where the room or space in which the appliances are installed is directly connected to another room or space by a doorway, archway or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be included in the calculations.

    621.6 Oxygen-depletion safety system.

    Unvented room heaters shall be equipped with an oxygen-depletion-sensitive safety shutoff system. The system shall shut off the gas supply to the main and pilot burners when the oxygen in the surrounding atmosphere is depleted to the percent concentration specified by the manufacturer, but not lower than 18 percent. The system shall not incorporate field adjustment means capable of changing the set point at which the system acts to shut off the gas supply to the room heater.

    621.7 Unvented decorative room heaters.

    An unvented decorative room heater shall not be installed in a factory-built fireplace unless the fireplace system has been specifically tested, listed and labeled for such use in accordance with UL 127.

    621.7.1 Ventless firebox enclosures.

    Ventless firebox enclosures used with unvented decorative room heaters shall be listed as complying with ANSI Z21.91.

    SECTION622 (IFGC)
    VENTED ROOM HEATERS

    622.1 General.

    Vented room heaters shall be tested in accordance with ANSI Z21.86/CSA 2.32, shall be designed and equipped as specified in Section 602.2 and shall be installed in accordance with the manufacturer’s instructions.

    SECTION623 (IFGC)
    COOKING APPLIANCES

    623.1 Cooking appliances.

    Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles, hot plates and barbecues, shall be tested in accordance with ANSI Z21.1, ANSI Z21.58/CSA 1.6 or ANSI Z83.11/CSA 1.8 and shall be installed in accordance with the manufacturer’s instructions.

    623.2 Prohibited location.

    Cooking appliances designed, tested, listed and labeled for use in commercial occupancies shall not be installed within dwelling units or within any area where domestic cooking operations occur.

    Exceptions:

    1. 1. Appliances that are also listed as domestic cooking appliances.

    2. 2. Where the installation is designed by a licensed Professional Engineer, in compliance with the manufacturer’s installation instructions.

    623.3 Domestic appliances.

    Cooking appliances installed within dwelling units and within areas where domestic cooking operations occur shall be listed and labeled as household-type appliances for domestic use.

    623.4 Domestic range installation.

    Domestic ranges installed on combustible floors shall be set on their own bases or legs and shall be installed with clearances of not less than that shown on the label.

    623.5 Open-top broiler unit hoods.

    A ventilating hood shall be provided above a domestic open-top broiler unit, unless otherwise listed for forced down draft ventilation.

    623.5.1 Clearances.

    A minimum clearance of 24 inches (610 mm) shall be maintained between the cooking top and combustible material above the hood. The hood shall be at least as wide as the open-top broiler unit and be centered over the unit.

    623.6 Commercial cooking appliance venting.

    Commercial cooking appliances, other than those exempted by Section 501.8, shall be vented by connecting the appliance to a vent or chimney in accordance with this code and the appliance manufacturer’s instructions or the appliance shall be vented in accordance with Section 505.1.1.

    623.7 (IFGS) Vertical clearance above cooking top.

    Household cooking appliances shall have a vertical clearance above the cooking top of not less than 30 inches (760 mm) to combustible material and metal cabinets. A minimum clearance of 24 inches (610 mm) is permitted where one of the following is installed:

    1. 1.The underside of the combustible material or metal cabinet above the cooking top is protected with not less than 1/4-inch (6.4 mm) insulating millboard covered with sheet metal not less than 0.0122 inch (0.3 mm) thick.

    2. 2.A metal ventilating hood constructed of sheet metal not less than 0.0122 inch (0.3 mm) thick is installed above the cooking top with a clearance of not less than 1/4 inch (6.4 mm) between the hood and the underside of the combustible material or metal cabinet. The hood shall have a width not less than the width of the appliance and shall be centered over the appliance.

    3. 3.A listed cooking appliance or microwave oven is installed over a listed cooking appliance and in compliance with the terms of the manufacturer’s installation instructions for the upper appliance.

    SECTION624 (IFGC)
    WATER HEATERS

    624.1 General.

    Water heaters shall be tested in accordance with ANSI Z21.10.1/CSA 4.1 and ANSI Z21.10.3/CSA 4.3 and shall be installed in accordance with the manufacturer’s instructions.

    Water heaters utilizing fuels other than fuel gas shall be regulated by the International Mechanical Code.

    624.1.1 Installation requirements.

    The requirements for water heaters relative to sizing, relief valves, drain pans and scald protection shall be in accordance with the International Plumbing Code.

    624.2 Water heaters utilized for space heating.

    Water heaters utilized both to supply potable hot water and provide hot water for space-heating applications shall be listed and labeled for such applications by the manufacturer and shall be installed in accordance with the manufacturer’s instructions and the International Plumbing Code.

    SECTION625 (IFGC)
    REFRIGERATORS

    625.1 General.

    Refrigerators shall be tested in accordance with ANSI Z21.19/CSA 1.4 and shall be installed in accordance with the manufacturer’s instructions.

    Refrigerators shall be provided with adequate clearances for ventilation at the top and back, and shall be installed in accordance with the manufacturer’s instructions. If such instructions are not available, not less than 2 inches (51 mm) shall be provided between the back of the refrigerator and the wall and not less than 12 inches (305 mm) above the top.

    SECTION626 (IFGC)
    GAS-FIRED TOILETS

    626.1 General.

    Gas-fired toilets shall be tested in accordance with ANSI Z21.61 and installed in accordance with the manufacturer’s instructions.

    626.2 Clearance.

    A gas-fired toilet shall be installed in accordance with its listing and the manufacturer’s instructions, provided that the clearance shall in any case be sufficient to afford ready access for use, cleanout and necessary servicing.

    SECTION627 (IFGC)
    AIR-CONDITIONING APPLIANCES

    627.1 General.

    Gas-fired air-conditioning appliances shall be tested in accordance with ANSI Z21.40.1/CGA 2.91 or ANSI Z21.40.2/CGA 2.92 and shall be installed in accordance with the manufacturer’s instructions.

    627.2 Independent piping.

    Gas piping serving heating appliances shall be permitted to also serve cooling appliances where such heating and cooling appliances cannot be operated simultaneously (see Section 402).

    627.3 Connection of gas engine-powered air conditioners.

    To protect against the effects of normal vibration in service, gas engines shall not be rigidly connected to the gas supply piping.

    627.4 Clearances for indoor installation.

    Air-conditioning appliances installed in rooms other than alcoves and closets shall be installed with clearances not less than those specified in Section 308.3 except that air-conditioning appliances listed for installation at lesser clearances than those specified in Section 308.3 shall be permitted to be installed in accordance with such listing and the manufacturer’s instructions and air-conditioning appliances listed for installation at greater clearances than those specified in Section 308.3 shall be installed in accordance with such listing and the manufacturer’s instructions.

    Air-conditioning appliances installed in rooms other than alcoves and closets shall be permitted to be installed with reduced clearances to combustible material, provided that the combustible material is protected in accordance with Table 308.2.

    627.5 Alcove and closet installation.

    Air-conditioning appliances installed in spaces such as alcoves and closets shall be specifically listed for such installation and installed in accordance with the terms of such listing. The installation clearances for air-conditioning appliances in alcoves and closets shall not be reduced by the protection methods described in Table 308.2.

    627.6 Installation.

    Air-conditioning appliances shall be installed in accordance with the manufacturer’s instructions. Unless the appliance is listed for installation on a combustible surface such as a floor or roof, or unless the surface is protected in an approved manner, the appliance shall be installed on a surface of noncombustible construction with noncombustible material and surface finish, and combustible material shall not be against the underside thereof.

    627.7 Plenums and air ducts.

    A plenum supplied as a part of the air-conditioning appliance shall be installed in accordance with the appliance manufacturer’s instructions. Where a plenum is not supplied with the appliance, such plenum shall be installed in accordance with the fabrication and installation instructions provided by the plenum and appliance manufacturer. The method of connecting supply and return ducts shall facilitate proper circulation of air.

    Where the air-conditioning appliance is installed within a space separated from the spaces served by the appliance, the air circulated by the appliance shall be conveyed by ducts that are sealed to the casing of the appliance and that separate the circulating air from the combustion and ventilation air.

    627.8 Refrigeration coils.

    A refrigeration coil shall not be installed in conjunction with a forced-air furnace where circulation of cooled air is provided by the furnace blower, unless the blower has sufficient capacity to overcome the external static resistance imposed by the duct system and cooling coil at the air throughput necessary for heating or cooling, whichever is greater. Furnaces shall not be located upstream from cooling units, unless the cooling unit is designed or equipped so as not to develop excessive temperature or pressure. Refrigeration coils shall be installed in parallel with or on the downstream side of central furnaces to avoid condensation in the heating element, unless the furnace has been specifically listed for downstream installation. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be sufficiently tight to prevent any circulation of cooled air through the furnace.

    Means shall be provided for disposal of condensate and to prevent dripping of condensate onto the heating element.

    627.9 Cooling units used with heating boilers.

    Boilers, where used in conjunction with refrigeration systems, shall be installed so that the chilled medium is piped in parallel with the heating boiler with appropriate valves to prevent the chilled medium from entering the heating boiler. Where hot water heating boilers are connected to heating coils located in air-handling units where they might be exposed to refrigerated air circulation, such boiler piping systems shall be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.

    627.10 Switches in electrical supply line.

    Means for interrupting the electrical supply to the air-conditioning appliance and to its associated cooling tower (if supplied and installed in a location remote from the air conditioner) shall be provided within sight of and not over 50 feet (15 240 mm) from the air conditioner and cooling tower.

    SECTION628 (IFGC)
    ILLUMINATING APPLIANCES

    628.1 General.

    Illuminating appliances shall be tested in accordance with ANSI Z21.42 and shall be installed in accordance with the manufacturer’s instructions.

    628.2 Mounting on buildings.

    Illuminating appliances designed for wall or ceiling mounting shall be securely attached to substantial structures in such a manner that they are not dependent on the gas piping for support.

    628.3 Mounting on posts.

    Illuminating appliances designed for post mounting shall be securely and rigidly attached to a post. Posts shall be rigidly mounted. The strength and rigidity of posts greater than 3 feet (914 mm) in height shall be at least equivalent to that of a 21/2-inch-diameter (64 mm) post constructed of 0.064-inch-thick (1.6-mm) steel or a 1-inch (25.4 mm) Schedule 40 steel pipe. Posts 3 feet (914 mm) or less in height shall not be smaller than a 3/4-inch (19.1 mm) Schedule 40 steel pipe. Drain openings shall be provided near the base of posts where there is a possibility of water collecting inside them.

    628.4 Appliance pressure regulators.

    Where an appliance pressure regulator is not supplied with an illuminating appliance and the service line is not equipped with a service pressure regulator, an appliance pressure regulator shall be installed in the line to the illuminating appliance. For multiple installations, one regulator of adequate capacity shall be permitted to serve more than one illuminating appliance.

    SECTION629 (IFGC)
    SMALL CERAMIC KILNS

    629.1 General.

    Kilns shall be installed in accordance with the manufacturer’s instructions and the provisions of this code. Kilns shall comply with Section 301.3.

    SECTION630 (IFGC)
    INFRARED RADIANT HEATERS

    630.1 General.

    Infrared radiant heaters shall be tested in accordance with ANSI Z83.19 or Z83.20 and shall be installed in accordance with the manufacturer’s instructions.

    630.2 Support.

    Infrared radiant heaters shall be fixed in a position independent of gas and electric supply lines. Hangers and brackets shall be of noncombustible material.

    630.3 (IFGS) Combustion and ventilation air.

    Where unvented infrared heaters are installed, natural or mechanical means shall provide outdoor ventilation air at a rate of not less than 4 cfm per 1,000 Btu/h (0.38 m3/min/kW) of the aggregate input rating of all such heaters installed in the space. Exhaust openings for removing flue products shall be above the level of the heaters.

    630.4 (IFGS) Installation in commercial garages and aircraft hangars.

    Overhead infrared heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11.

    SECTION631 (IFGC)
    BOILERS

    631.1 Standards.

    Boilers shall be listed in accordance with the requirements of ANSI Z21.13/CSA 4.9 or UL 795. If applicable, the boiler shall be designed and constructed in accordance with the requirements of ASME CSD-1 and as applicable, the ASME Boiler and Pressure Vessel Code, Sections I, II, IV, V and IX and NFPA 85.

    631.2 Installation.

    In addition to the requirements of this code, the installation of boilers shall be in accordance with the manufacturer’s instructions and the International Mechanical Code. Operating instructions of a permanent type shall be attached to the boiler. Boilers shall have all controls set, adjusted and tested by the installer. A complete control diagram together with complete boiler operating instructions shall be furnished by the installer. The manufacturer’s rating data and the nameplate shall be attached to the boiler.

    631.3 Clearance to combustible materials.

    Clearances to combustible materials shall be in accordance with Section 308.4.

    SECTION632 (IFGC)
    EQUIPMENT INSTALLED IN EXISTING
    UNLISTED BOILERS

    632.1 General.

    Gas equipment installed in existing unlisted boilers shall comply with Section 631.1 and shall be installed in accordance with the manufacturer’s instructions and the International Mechanical Code.

    SECTION633 (IFGC)
    STATIONARY FUEL-CELL POWER SYSTEMS

    [F]633.1General.

    Stationary fuel-cell power systems having a power output not exceeding 10 MW shall be tested in accordance with ANSI CSA America FC 1 and shall be installed in accordance with the manufacturer’s instructions, NFPA 853, the International Building Code and the International Fire Code.

    SECTION634 (IFGS)
    CHIMNEY DAMPER OPENING AREA

    634.1 Free opening area of chimney dampers.

    Where an unlisted decorative appliance for installation in a vented fireplace is installed, the fireplace damper shall have a permanent free opening equal to or greater than specified in Table 634.1.

    TABLE 634.1

    FREE OPENING AREA OF CHIMNEY DAMPER FOR VENTING FLUE GASES FROM UNLISTED DECORATIVE APPLIANCES FOR INSTALLATION IN VENTED FIREPLACES

    CHIMNEY HEIGHT (feet)MINIMUM PERMANENT FREE OPENING (square inches)a
    8132029395164
    Appliance input rating (Btu per hour)
    67,80014,00023,20034,00046,40062,40080,000
    88,40015,20025,20037,00050,40068,00086,000
    109,00016,80027,60040,40055,80074,40096,400
    159,80018,20030,20044,60062,40084,000108,800
    2010,60020,20032,60050,40068,40094,000122,200
    3011,20021,60036,60055,20076,800105,800138,600

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square inch = 645.16 m2, 1 British thermal unit per hour = 0.2931 W.

    1. a.The first six minimum permanent free openings (8 to 51 square inches) correspond approximately to the cross-sectional areas of chimneys having diameters of 3 through 8 inches, respectively. The 64-square-inch opening corresponds to the cross-sectional area of standard 8-inch by 8-inch chimney tile.

    SECTION635 (IFGC)
    GASEOUS HYDROGEN SYSTEMS

    635.1 Installation.

    The installation of gaseous hydrogen systems shall be in accordance with the applicable requirements of this code, the International Fire Code and the International Building Code.

    SECTION636 (IFGC)
    OUTDOOR DECORATIVE APPLIANCES

    636.1 General.

    Permanently fixed-in-place outdoor decorative appliances shall be tested in accordance with ANSI Z21.97 and shall be installed in accordance with the manufacturer’s instructions.