• CHAPTER5
    SITE SUSTAINABILITY

    501.1 (5.1)Scope.

    This section addresses requirements for building projects that pertain to site selection, site development, mitigation of heat island effect, light pollution reduction, and mitigation of transportation impacts.

    501.2 (5.2)Compliance.

    All of the provisions of Chapter 5 (Section 5) are mandatory provisions.

    501.3 (5.3)Mandatory Provisions.

    501.3.1 (5.3.1)Site Selection.

    The building project shall comply with Sections 501.3.1.1 (5.3.1.1) and 501.3.1.2 (5.3.1.2).

    501.3.1.1 (5.3.1.1)Allowable Sites.

    The building project shall take place in or on one of the following:

    1. a.An existing building envelope.

    2. b.A brownfield.

    3. c.A greyfield.

    4. d.A greenfield that is within 1/2 mi (800 m) of residential land that is developed, or that has one or more buildings under construction, with an average density of ten dwelling units per acre (4 units per ha) unless that site is agricultural land or forest land. Proximity is determined by drawing a circle with a 1/2 mi (800 m) radius around the center of the proposed site.

    5. e.A greenfield where the proposed building complies with ASTM E2843, unless that site is agricultural land or forest land.

    6. f.A greenfield where the proposed building complies with ASTM E2844, unless that site is agricultural land or forest land.

    7. g.A greenfield that is agricultural land, and the purpose of the proposed building is related to the agricultural use of the land.

    8. h.A greenfield that is forest land, and the purpose of the proposed building is related to the forestry use of the land.

    9. i.A greenfield that is designated park land, and the purpose of the proposed building is related to the use of the land as a park.

    501.3.1.2 (5.3.1.2)Prohibited Development Activity.

    There shall be no site disturbance or development of the following:

    1. a.Previously undeveloped land having an elevation lower than 5 ft (1.5 m) above the elevation of the 100-year flood, as defined by USFEMA.

      Exceptions:

      1. 1.Development of low-impact trails shall be allowed anywhere within a flood zone.

      2. 2.Development of building structures shall be allowed in alluvial “AO” designated flood zones, provided that such structures include engineered floodproofing up to an elevation that is at least as high as the minimum lowest floor elevation determined by the authority having jurisdiction (AHJ) and provided that the site includes drainage paths constructed to guide floodwaters around and away from the structures.

    2. b.Land within 150 ft (50 m) of any fish and wildlife habitat conservation area.

      Exceptions:

      1. 1.Development of low-impact trails shall be allowed, provided that such trails are located at least 15 ft (4.5 m) from the area.

      2. 2.Site disturbance or development shall be allowed for habitat enhancement measures.

    3. c.Land within 100 ft (35 m) of any wetland

      Exceptions:

      1. 1.Development of low-impact trails shall be allowed, provided that such trails are located at least 15 ft (4.5 m) from the wetland.

      2. 2.Site disturbance or development shall be allowed for habitat enhancement measures or for restoration of the functions of the wetland.

    501.3.2 (5.3.2)Predesign Site Inventory and Assessment.

    A predesign inventory and assessment of the natural resources of the building project site shall be submitted with the site design and construction documents. The inventory and assessment shall include all of the following:

    1. a.Location of any prohibited development areas identified in Section 501.3.1.2 (5.3.1.2) that are located on or adjacent to the building project site.

    2. b.Identification of invasive plant species on the site.

    3. c.Identification of native plant species on the site.

    4. d.Identification of site features designated for preservation.

    501.3.3 (5.3.3)Plants.

    501.3.3.1 (5.3.3.1)Invasive Plants.

    Invasive plants shall be removed from the building project site and destroyed or disposed of in a land fill. Invasive plants shall not be planted on the building project site.

    501.3.3.2 (5.3.3.2)Greenfield Sites.

    1. a.More than 20% existing native or adapted plants: Where more than 20% of the area of the predevelopment site has existing native plants or adapted plants, a minimum of 20% of the area of native plants or adapted plants shall be retained.

    2. b.Less than 20% existing native or adapted plants:

      1. 1.Where 20% or less of the area of the predevelopment site has existing native plants or adapted plants, a minimum of 20% of the site shall be developed or retained as vegetated area. Such vegetated areas include bioretention facilities, rain gardens, filter strips, grass swales, vegetated level spreaders, constructed wetlands, planters, and open space with plantings.

      2. 2.A minimum of 60% of the vegetated area shall consist of biodiverse planting of native plants and/or adapted plants other than turfgrass.

        Exception: The following areas shall not be included in the calculations: dedicated sports fields, driving ranges, burial grounds, vegetated pavers, and the minimum fire lanes required by the jurisdiction.

    501.3.4 (5.3.4)Stormwater Management.

    Stormwater management systems shall be provided on the building site. Except to the extent that other stormwater management approaches are required by a local, state, or federal jurisdiction, these systems shall be limited to one or more of the following management methods:

    1. a.Infiltration.

    2. b.Evapotranspiration.

    3. c.Rainwater harvesting.

    4. d.Stormwater collection and use.

    501.3.4.1 (5.3.4.1)Projects on Greenfields.

    Projects on greenfields shall comply with at least one of the following:

    1. a.Stormwater management systems shall retain on site no less than the volume of precipitation during a single 24 h period equal to the 95th percentile precipitation event. Building projects with stormwater management systems that are designed to retain volumes greater than that of the 98th percentile precipitation event shall conduct a hydrologic analysis of the building site to determine the water balance of the site prior to its development, clearing, and filling and to demonstrate that the stormwater management system will not cause ecological impairment by starving receiving waters downstream of the site.

    2. b.The stormwater management system design shall maintain site water balance (the combined runoff,infiltration, and evapotranspiration) based on a hydrologic analysis of the site’s conditions prior to development, clearing, and filling. Postconstruction runoff rate, volume, and duration shall not exceed rates preceding development, clearing, or filling of the site.

    501.3.4.2 (5.3.4.2)Projects on Greyfields.

    Projects on greyfields shall retain on site no less than the volume of precipitation during a single 24 h period equal to or greater than the 60th percentile precipitation event.

    Exception: Where any fraction of the 60th percentile precipitation event cannot be retained, that fraction shall be treated to limit total suspended solids to 25 mg/L in the remaining discharge.

    501.3.4.3 (5.3.4.3)Discharge Rate.

    Building project sites shall be designed and constructed to comply with one of the following requirements:

    1. a.The discharge of the design storm shall occur over a period of not less than 48 h.

    2. b.The discharge flow duration curve at any point in time shall be plus or minus 10% of the flow duration curve for channel-forming discharges for the site prior to its development, clearing, or filling.

    501.3.4.4 (5.3.4.4)Adjoining Lots.

    The stormwater management system shall direct or concentrate off-site discharge to avoid increased erosion or other drainagerelated damage to adjoining lots or public property.

    501.3.4.5 (5.3.4.5)Discharges from Contaminated Soils.

    Stormwater management systems on areas of brownfields where contaminated soils are left in place shall not use infiltration practices that will result in pollutant discharges to groundwater. Stormwater discharge from brownfields shall be treated to limit total suspended solids to 25 mg/L. Stormwater management systems shall not penetrate, damage, or otherwise compromise remediation actions at the building site.

    501.3.4.6 (5.3.4.6)Coal Tar Sealants.

    The use of tar sealants shall be prohibited in any application exposed to stormwater, wash waters, condensates, irrigation water, snowmelt, or icemelt.

    501.3.5 (5.3.5)Mitigation of Heat Island Effect.

    501.3.5.1 (5.3.5.1)Site Hardscape.

    At least 50% of the site hardscape that is not covered by solar energy systems shall be provided with one or any combination of the following:

    1. a.Existing trees and vegetation or new biodiverse plantings of native plants and adapted plants, which shall be planted either prior to the final approval by the AHJ or in accordance with a contract established to require planting no later than 12 months after the final approval by the AHJ so as to provide the required shade no later than ten years after the final approval. The effective shade coverage on the hardscape shall be the arithmetic mean of the shade coverage calculated at 10 a.m., noon, and 3 p.m. on the summer solstice.

    2. b.Paving materials with a minimum initial solar reflectance index (SRI) of 29. A default SRI value of 35 for new concrete without added color pigment is allowed to be used instead of measurements.

    3. c.Open-graded (uniform-sized) aggregate, permeable pavement, permeable pavers, and porous pavers (open-grid pavers). Permeable pavement and permeable pavers shall have a percolation rate of not less than 2 gal/min·ft2 (100 L/min·m2).

    4. d.Shading through the use of structures, provided that the top surface of the shading structure complies with the provisions of Section 501.3.5.3 (5.3.5.3).

    5. e.Parking under a building, provided that the roof of the building complies with the provisions of Section 501.3.5.3 (5.3.5.3).

    6. f.Buildings or structures that provide shade to the site hardscape. The effective shade coverage on the hardscape shall be the arithmetic mean of the shade coverage calculated at 10 a.m., noon, and 3 p.m. on the summer solstice.

    Exception: Section 501.3.5.1 (5.3.5.1) shall not apply to building projects in Climate Zones 6, 7, and 8.

    501.3.5.2 (5.3.5.2)Walls.

    Above-grade building walls and retaining walls shall be shaded in accordance with this section. The building is allowed to be rotated up to 45 degrees to the nearest cardinal orientation for purposes of calculations and showing compliance. Compliance with this section shall be achieved through the use of shade-providing plants, man-made structures, existing buildings, hillsides, permanent building projections, on-site renewable energy systems, or a combination of these, using the following criteria:

    1. a.Shade shall be provided on at least 30% of the east and west above-grade walls and retaining walls from grade level to a height of 20 ft (6 m) above grade, or the top of the exterior wall, whichever is less. Shade coverage shall be calculated at 10 a.m. for the east walls and 3 p.m. for the west walls on the summer solstice.

    2. b.Where shading is provided by vegetation, such vegetation shall be existing trees and vegetation or new biodiverse plantings of native plants and adapted plants. Such planting shall occur prior to the final approval by the AHJ or in accordance with a contract established to require planting no later than 12 months after the final approval by the AHJ so as to provide the required shade no later than ten years after the final approval. Vegetation shall be appropriately sized, selected, planted, and maintained so that it does not interfere with overhead or underground utilities. Trees shall be placed a minimum of 5 ft (1.5 m) from and within 50 ft (15 m) of the building or retaining wall.

    Exceptions:

    1. 1.The requirements of this section are satisfied if 75% or more of the opaque wall surfaces on the east and west have a minimum SRI of 29. Each wall is allowed to be considered separately for this exception.

    2. 2.East wall shading is not required for buildings located in Climate Zones 5, 6, 7, and 8. West wall shading is not required for buildings located in Climate Zones 7 and 8.

    501.3.5.3 (5.3.5.3)Roofs.

    This section applies to the building and covered parking roof surfaces for building projects in Climate Zones 0, 1, 2, and 3. A minimum of 75% of the roof surface shall be covered with products that:

    1. a.have a minimum three-year-aged SRI of 64 in accordance with Section 501.3.5.4 (5.3.5.4) for roofs with a slope of less than or equal to 2:12.

    2. b.have a minimum three-year-aged SRI of 25 in accordance with Section 501.3.5.4 (5.3.5.4) for roofs with a slope of more than 2:12.

    The area occupied by one or more of the following shall be excluded from the calculation to determine the roof surface area required to comply with this section:

    1. a.Roof penetrations and associated equipment.

    2. b.On-site renewable energy systems, including photovoltaics, solar thermal energy collectors, and required access around the panels or collectors.

    3. c.Portions of the roof used to capture heat for building energy technologies.

    4. d.Roof decks and rooftop walkways.

    5. e.Vegetated terrace and roofing systems complying with Section 501.3.5.5 (5.3.5.5).

    Exceptions:

    1. 1.Building projects where an annual energy analysis simulation demonstrates that the total annual building energy cost and total annual CO2e, as calculated in accordance with Section 701.5.2 (7.5.2), are both a minimum of 2% less for the proposed roof than for a roof material complying with the SRI requirements of Section 501.3.5.3 (5.3.5.3).

    2. 2.Roofs used to shade or cover parking and roofs over semiheated spaces, provided that they have a minimum initial SRI of 29. A default SRI value of 35 for new concrete without added color pigment is allowed to be used instead of measurements.

    501.3.5.4 (5.3.5.4)Solar Reflectance Index (SRI).

    The SRI shall be calculated in accordance with ASTM E1980 for medium-speed wind conditions using a convection coefficient of 2.1 Btu/h·ft2·°F (11.9 W/m2·°C) for the following conditions:

    1. a.For materials other than roofs, the SRI shall be based on solar reflectance, as measured in accordance with ASTM E1918 or ASTM C1549, and the thermal emittance, as measured in accordance with ASTM E408 or ASTM C1371. The values for solar reflectance and thermal emittance shall be determined and certified by an independent third party.

    2. b.For roofing products, the SRI values shall be based on a minimum three-year-aged solar reflectance and thermal emittance, as measured in accordance with CRRC S100, and shall be certified by the manufacturer.

    501.3.5.5 (5.3.5.5)Vegetated Terrace and Roofing Systems.

    Vegetated terrace and roofing systems, where provided in accordance with Section 501.3.5.3 (5.3.5.3), shall comply with the following:

    1. a.All plantings shall be capable of withstanding the microclimate conditions of the vegetated area, including but not limited to wind, precipitation, and temperature. Plants shall be selected and placed to provide foliage coverage of not less than 50% of designed area of vegetation based on the anticipated plant growth within two years of the issuance of the final certificate of occupancy. Construction documents shall be submitted that show the planting location and anticipated two-year foliage coverage of the plantings. Duplicate coverage shall not be credited where multiple plants cover the same area. Invasive plants shall not be planted.

    2. b.The growing medium shall be designed for the physical conditions and local climate to support the plants selected. The planting design shall include measures to protect the growing medium until the plants are established. The maximum wet weight and water-holding capacity of a growing medium shall be determined in accordance with ASTM E2399.

    3. c.Nonvegetated clearances and borders shall be provided in accordance with the International Fire Code, Section 317.

    4. d.Plantings shall be capable of maintaining the function of the vegetated roof or terrace as required by Section 1001.3.2.1.1 (10.3.2.1.1).

    5. e.Irrigation of the vegetated roofs and terraces shall comply with Section 601.3.2.4 (6.3.2.4).

    6. f.Installation of plantings shall be in accordance with the roof-covering manufacturer’s installation instructions.

    501.3.6 (5.3.6)Reduction of Light Pollution.

    501.3.6.1 (5.3.6.1)General.

    Exterior lighting systems shall comply with ANSI/ASHRAE/IES Standard 90.1, Sections 9.1, 9.4.1.4, 9.4.2, 9.4.3, and 9.7, and with Sections 501.3.6.2 (5.3.6.2) and 501.3.6.3 (5.3.6.3) of this code.

    501.3.6.2 (5.3.6.2)Backlight and Glare.

    1. a.All building-mounted luminaires located less than two mounting heights from any property line shall meet the maximum allowable glare ratings in Table 501.3.6.2A (5.3.6.2A).

    2. b.All other luminaires shall meet the maximum allowable backlight and glare ratings in Table 501.3.6.2B (5.3.6.2B).

    Exceptions:

    1. 1.Specialized signal, directional, and marker lighting associated with transportation.

    2. 2.Advertising signage or directional signage.

    3. 3.Lighting integral to equipment or instrumentation and installed by its manufacturer.

    4. 4.Lighting for theatrical purposes, including performance, stage, film production, and video production.

    5. 5.Lighting for athletic playing areas.

    6. 6.Lighting that is in use for no more than 60 continuous days and is not reinstalled any sooner than 60 days after being uninstalled.

    7. 7.Lighting for industrial production, material handling, transportation sites, and associated storage areas.

    8. 8.Theme elements in theme/amusement parks.

    9. 9.Roadway lighting required by governmental authorities.

    10. 10.Lighting classified for and used in hazardous locations as specified in NFPA 70.

    11. 11.Lighting for swimming pools and water features.

    TABLE 501.3.6.2A (TABLE 5.3.6.2A)

    MAXIMUM ALLOWABLE GLARE RATINGS FOR BUILDING-MOUNTED LUMINAIRES WITHIN TWO MOUNTING HEIGHTS OF ANY PROPERTY LINEa,b

    DISTANCE IN MOUNTING HEIGHTS TO NEAREST PROPERTY LINELZ0LZ1LZ2LZ3LZ4
    ≥ 1 and < 2G0G0G1G1G2
    ≥ 0.5 and < 1G0G0G0G1G1
    < 0.5G0G0G0G0G1
    1. a.For property lines that abut public walkways, bikeways, plazas, and parking lots, the property line may be considered to be 5 ft (1.5 m) beyond the actual property line for the purpose of determining compliance with this section. For property lines that abut public roadways and public transit corridors, the property line may be considered to be the centerline of the public roadway or public transit corridor for the purpose of determining compliance with this section.

    2. b.Backlight, uplight, and glare ratings are defined based on specific lumen limits per IES TM-15 Addendum A.

    TABLE 501.3.6.2B (TABLE 5.3.6.2B)

    MAXIMUM ALLOWABLE BACKLIGHT, UPLIGHT, AND GLARE (BUG) RATINGSa,b,c,d

    LZ0LZ1LZ2LZ3LZ4
    Allowed Backlight Rating
    > 2 mounting heights from property lineB1B3B4B5B5
    1 to 2 mounting heights from property lineB1B2B3B4B4
    0.5 to 1 mounting height to property lineB0B1B2B3B3
    < 0.5 mounting height to property lineB0B0B0B1B2
    Allowed Uplight RatingU0U1U2U3U4
    Allowed Glare RatingG0G1G2G3G4
    1. a.Except where installed on a building surface, luminaires that are located at a distance of two times the mounting height of the luminaire or less from a property line shall have the backlight of the luminaire aimed toward and perpendicular to the nearest property line. Backlight is that part of the luminaire’s lumen output that was used to determine the backlight rating in its final angular position.

    2. b.For property lines that abut public walkways, bikeways, plazas, and parking lots, the property line may be considered to be 5 ft (1.5 m) beyond the actual property line for the purpose of determining compliance with this section. For property lines that abut public roadways and public transit corridors, the property line may be considered to be the centerline of the public roadway or public transit corridor for the purpose of determining compliance with this section.

    3. c.If the luminaire is installed in other than the intended manner, or is an adjustable luminaire for which the aiming is specified, the rating shall be determined by the actual photometric geometry in the aimed orientation.

    4. d.Backlight, uplight, and glare ratings are defined based on specific lumen limits per IES TM-15 Addendum A.

    501.3.6.3 (5.3.6.3)Uplight.

    All exterior lighting shall meet one of the following uplight requirements:

    1. a.Exterior luminaires shall meet the maximum allowable Uplight Ratings of Table 501.3.6.2B (5.3.6.2B).

    2. b.Exterior lighting shall meet the uplight requirements of Table 501.3.6.3 (5.3.6.3).

    Exceptions:

    1. 1.Specialized signal, directional, and marker lighting associated with transportation.

    2. 2.Advertising signage or directional signage.

    3. 3.Lighting integral to equipment or instrumentation and installed by its manufacturer.

    4. 4.Lighting for theatrical purposes, including performance, stage, film production, and video production.

    5. 5.Lighting for athletic playing areas.

    6. 6.Lighting that is in use for no more than 60 continuous days and is not reinstalled any sooner than 60 days after being uninstalled.

    7. 7.Lighting for industrial production, material handling, transportation sites, and associated storage areas.

    8. 8.Theme elements in theme/amusement parks.

    9. 9.Roadway lighting required by governmental authorities.

    10. 10.Lighting classified for and used in hazardous locations as specified in NFPA 70.

    11. 11.Lighting for swimming pools and water features.

    12. 12.Lighting in LZ3 and LZ4, solely for uplighting structures, building façades, or landscaping.

    13. 13.Lighting in LZ1 and LZ2, solely for uplighting structures, building façades, or landscaping, provided the applicable lighting power densities (LPDs) do not exceed 50% of the lighting power allowances in ANSI/ASHRAE/IES Standard 90.1, Table 9.4.2-2.

    TABLE 501.3.6.3 (TABLE 5.3.6.3)

    MAXIMUM ALLOWABLE PERCENTAGE OF UPLIGHT

    LZ0LZ1LZ2LZ3LZ4
    Percentage of total exterior fixture lumens allowed to be emitted above 90 degrees or higher from nadir (straight down)0%0%1%2%5%

    501.3.7 (5.3.7)Mitigation of Transportation Impacts.

    501.3.7.1 (5.3.7.1)Pedestrian and Bicycle Connectivity.

    501.3.7.1.1 (5.3.7.1.1)Pedestrian Walkways.

    Each primary building entrance shall be provided with a pedestrian walkway that extends to either a public way or a transit stop. Walkways shall not be less than 5 ft (1.5 m) in width and shall be clearly delineated.

    A public-use walkway shall be provided along the length of the adjoining public-way frontage of the building project site, and such walkways shall connect to adjacent public-use walkways.

    501.3.7.1.2 (5.3.7.1.2)Bicycle Paths.

    On-site bicycle paths shall be designed to connect bicycle parking areas to existing and planned off-site bicycle paths adjacent to the building project.

    501.3.7.2 (5.3.7.2)Bicycle Parking.

    501.3.7.2.1 (5.3.7.2.1)Minimum Number of Spaces.

    Bicycle parking spaces shall be provided for at least 5% of the occupant load of each building but not less than two parking spaces. Occupants who are nonambulatory, under restraint, or under custodial care need not be included in the total occupant load for the building. Building projects with dwelling units shall be provided with at least 0.5 bicycle parking spaces per bedroom for each building but not less than two parking spaces.

    Exceptions:

    1. 1.Building projects with dwelling units that provide each unit with a private garage or private, locked storage space of sufficient size to store a bicycle.

    2. 2.The number of bicycle parking spaces shall be allowed to be reduced subject to AHJ approval of a transportation plan, prepared by a design professional, that demonstrates the likelihood that building occupants will use public transportation and/or walk to the building project site.

    501.3.7.2.2 (5.3.7.2.2)Location.

    Not fewer than two bicycle parking spaces shall be located within 50 ft (15.2 m) of, and be visible from, the building entrance being served. All other bicycle parking spaces shall be located inside the building, or the nearest point of the bicycle parking areas shall be within 50 ft (15.2 m) of the building entrance being served. Bicycle parking shall not obstruct pedestrian access to the building.

    501.3.7.2.3 (5.3.7.2.3) Horizontal Parking Racks.

    Horizontal bicycle parking racks shall provide a space for each bicycle that is not less than 18 in. (305 mm) in width and not less than 72 in. (1829 mm) in length. Each space shall provide at least two points of contact between the bicycle frame and rack. Each space shall have access to a clear exit pathway not less than 36 in. (914 mm) in width.

    501.3.7.2.4 (5.3.7.2.4)Ability to Lock.

    Each bicycle parking space shall be provided with a securely mounted rack or other facilities for locking or securing a bicycle. A rack shall allow the locking of the frame and the front or rear wheel of the bicycle to the rack using a U-shaped shackle lock.

    501.3.7.2.5 (5.3.7.2.5)Security and Visibility.

    All bicycle parking spaces shall be visible from the entrance being served; secured in a locker, cage, or room; or provided with valet service or security cameras. Signage shall be provided to identify parking that is not visible from the building entrance.

    501.3.7.2.6 (5.3.7.2.6)Documentation.

    Construction documents shall include plans and details showing compliance with Sections 501.3.7.2.1 (5.3.7.2.1) through 501.3.7.2.5 (5.3.7.2.5).

    501.3.7.3 (5.3.7.3)Site Vehicle Provisions.

    Where onsite vehicle parking is provided for a building that has a building occupant load greater than 100, at least one of the following shall be provided:

    1. a.Provisions for preferred parking spaces. Not less than 5% of the parking spaces provided shall be designated as preferred parking for vehicles that meet both the minimum greenhouse gas and air pollution scores as required for USEPA SmartWay designation. Where calculation of the parking spaces yields a fraction, such fractions shall be rounded up to the next whole number. Preferred parking spaces shall be located on the shortest route of travel from the parking facility to a building entrance but shall not take precedence over parking spaces that are required to be accessible for individuals with disabilities. Where buildings have multiple entrances with adjacent parking, parking spaces shall be dispersed and located near the entrances. Such parking spaces shall be provided with signage approved by the AHJ that specifies the permitted use.

    2. b.Provisions for electric-vehicle charging infrastructure. The building project shall comply with one of the following:

      1. 1.Two or more electric-vehicle charging stations shall be available to the building occupants and shall be located not more than 1/4 mi (400 m) from the building project.

      2. 2.Electrical raceways shall be installed and extend from one or more of the building’s electrical power distribution panels to not less than the number of parking spaces specified in Table 501.3.7.3 (5.3.7.3) to facilitate the future installation of vehicle charging stations. Electrical power distribution panels serving such raceways shall be sized to supply the future charging stations based on a design load of not less than 40 amp per required parking space at a supply voltage of not less than 208/240 VAC.

    TABLE 501.3.7.3 (TABLE 5.3.7.3)

    NUMBER OF SPACES REQUIRED TO HAVE RACEWAYS

    TOTAL NUMBER OF PARKING SPACES PROVIDEDNUMBER OF SPACES REQUIRED TO HAVE RACEWAY
    1 through 251
    26 through 502
    51 through 754
    76 through 1005
    101 through 1507
    151 through 20010
    201 and over5% of total

    501.3.8 (5.3.8) Building Site Waste Management.

    501.3.8.1 (5.3.8.1)Building Site Waste Management Plan.

    A building site waste management plan shall be developed and implemented for excavated soil, rock, and land-clearing debris. Land-clearing debris is limited to stumps and vegetation. Diverted land-clearing debris and removed rock and soil shall not be sent to sites where development activity is prohibited by Section 501.3.1.2 (5.3.1.2) or to greenfields other than those being used for agricultural purposes or being developed as part of a building project.

    Not less than 90% of the land-clearing debris, excluding invasive plant materials, shall be diverted from disposal in landfills and incinerators other than waste-to-energy systems with an energy-recovery efficiency rate higher than 60%. Land-clearing debris calculations shall be based on either weight or volume but not both. Receipts or other documentation related to diversion shall be maintained through the course of construction.

    The plan shall address all of the following:

    1. a.Land-clearing debris, rock, and soil to be diverted from disposal by composting, recycling, or reuse.

    2. b.Waste materials that will be diverted on-site.

    3. c.The locations to which waste materials will be diverted off-site.

    4. d.Soils to be stockpiled for future use at any location.

    5. e.Woody waste to be used as fuel.

    6. f.The destruction and disposal of invasive plant materials.

    7. g.The methods of removal of any contaminated soils.

    8. h.The treatment of vegetation to comply with the rules of government-designated quarantine zones for invasive insect species.