• CHAPTER4
    FIXTURES, FAUCETS AND FIXTURE FITTINGS 

    User note:

    About this chapter: Plumbing fixtures are required to be installed for nearly every building as toilet facilities (water closets and lavatories) are needed by the occupants of a building. Additional fixtures for washing, bathing and culinary purposes are also necessary where occupants dwell in buildings. Chapter 4 specifies the minimum number and type of plumbing fixtures for buildings based on the description of use of the building. Because fixture design and quality are paramount to ensure that plumbing fixtures operate properly, this chapter also specifies numerous product and material standards for plumbing fixtures.

    SECTION401
    GENERAL

    401.1Scope.

    This chapter shall govern the materials, design and installation of plumbing fixtures, faucets and fixture fittings in accordance with the type of occupancy, and shall provide for the minimum number of fixtures for various types of occupancies.

    401.2Prohibited fixtures and connections.

    Water closets having a concealed trap seal or an unventilated space or having walls that are not thoroughly washed at each discharge in accordance with ASME A112.19.2/CSA B45.1 shall be prohibited. Any water closet that permits siphonage of the contents of the bowl back into the tank shall be prohibited. Trough urinals shall be prohibited.

    401.3Water conservation.

    The maximum water flow rates and flush volume for plumbing fixtures and fixture fittings shall comply with Section 604.4.

    SECTION402
    FIXTURE MATERIALS

    402.1Quality of fixtures.

    Plumbing fixtures shall be constructed of approved materials, with smooth, impervious surfaces, free from defects and concealed fouling surfaces, and shall conform to standards cited in this code. Porcelain enameled surfaces on plumbing fixtures shall be acid resistant.

    402.2Materials for specialty fixtures.

    Materials for specialty fixtures not otherwise covered in this code shall be of stainless steel, soapstone, chemical stoneware or plastic, or shall be lined with lead, copper-base alloy, nickel-copper alloy, corrosion-resistant steel or other material especially suited to the application for which the fixture is intended.

    402.3Sheet copper.

    Sheet copper for general applications shall conform to ASTM B152 and shall not weigh less than 12 ounces per square foot (3.7 kg/m2).

    402.4Sheet lead.

    Sheet lead for pans shall not weigh less than 4 pounds per square foot (19.5 kg/m2) and shall be coated with an asphalt paint or other approved coating.

    SECTION403
    MINIMUM PLUMBING FACILITIES

    403.1Minimum number of fixtures.

    Plumbing fixtures shall be provided in the minimum number as shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code.

    TABLE 403.1

    MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURESa (See Sections 403.1.1 and 403.2)

    NO.CLASSIFICATIONDESCRIPTIONWATER CLOSETS (URINALS: SEE SECTION 424.2)LAVATORIESBATHTUBS/ SHOWERSDRINKING FOUNTAIN (SEE SECTION 410)OTHER
    MALEFEMALEMALEFEMALE
    1AssemblyTheaters and other buildings for the performing arts and motion picturesd1 per 1251 per 651 per 2001 per 5001 service sink
    Nightclubs, bars, taverns, dance halls and buildings for similar purposesd1 per 401 per 401 per 751 per 5001 service sink
    Restaurants, banquet halls and food courtsd1 per 751 per 751 per 2001 per 5001 service sink
    Gaming areas1 per 100 for the first 400 and 1 per 250 for the remainder exceeding 4001 per 50 for the first 400 and 1 per 150 for the remainder exceeding 4001 per 250 for the first 750 and 1 per 500 for the remainder exceeding 7501 per 1,0001 service sink
    Auditoriums without permanent seating, art galleries, exhibition halls, museums, lecture halls, libraries, arcades and gymnasiumsd1 per 1251 per 651 per 2001 per 5001 service sink
    Passenger terminals and transportation facilitiesd1 per 5001 per 5001 per 7501 per 1,0001 service sink
    Places of worship and other religious servicesd1 per 1501 per 751 per 2001 per 1,0001 service sink
    Coliseums, arenas, skating rinks, pools and tennis courts for indoor sporting events and activities1 per 75 for the first 1,500 and 1 per 120 for the remainder exceeding 1,5001 per 40 for the first 1,520 and 1 per 60 for the remainder exceeding 1,5201 per 2001 per 1501 per 1,0001 service sink
    Stadiums, amusement parks, bleachers and grandstands for outdoor sporting events and activitiesf1 per 75 for the first 1,500 and 1 per 120 for the remainder exceeding 1,5001 per 40 for the first 1,520 and 1 per 60 for the remainder exceeding 1,5201 per 2001 per 1501 per 1,0001 service sink
    2BusinessBuildings for the transaction of business, professional services, other services involving merchandise, office buildings, banks, light industrial and similar uses1 per 25 for the first 50 and 1 per 50 for the remainder exceeding 501 per 40 for the first 80 and 1 per 80 for the remainder exceeding 801 per 1001 service sinke
    3EducationalEducational facilities1 per 501 per 501 per 1001 service sink
    4Factory and industrialStructures in which occupants are engaged in work fabricating, assembly or processing of products or materials1 per 1001 per 1001 per 4001 service sink
    5InstitutionalCustodial care facilities1 per 101 per 101 per 81 per 1001 service sink
    Medical care recipients in hospitals and nursing homes1 per roomc1 per roomc1 per 151 per 1001 service sink per floor
    Employees in hospitals and nursing homesb1 per 251 per 351 per 100
    Visitors in hospitals and nursing homes1 per 751 per 1001 per 500
    Prisonsb1 per cell1 per cell1 per 151 per 1001 service sink
    Reformitories, detention centers, and correctional centersb1 per 151 per 151 per 151 per 1001 service sink
    Employees in reformitories, detention centers and correctional centersb1 per 251 per 351 per 100
    Adult day care and child day care1 per 151 per 1511 per 1001 service sink
    6MercantileRetail stores, service stations, shops, salesrooms, markets and shopping centers1 per 5001 per 7501 per 1,0001 service sinke
    7ResidentialHotels, motels, boarding houses (transient)1 per sleeping unit1 per sleeping unit1 per sleeping unit1 service sink
    Dormitories, fraternities, sororities and boarding houses (not transient)1 per 101 per 101 per 81 per 1001 service sink
    Apartment house1 per dwelling unit1 per dwelling unit1 per dwelling unit1 kitchen sink per dwelling unit; 1 automatic clothes washer connection per 20 dwelling units
    Congregate living facilities with 16 or fewer persons1 per 101 per 101 per 81 per 1001 service sink
    One- and two-family dwellings and lodging houses with five or fewer guestrooms1 per dwelling unit1 per dwelling unit1 per dwelling unit1 kitchen sink per dwelling unit; 1 automatic clothes washer connection per dwelling unit
    Congregate living facilities with 16 or fewer persons1 per 101 per 101 per 81 per 1001 service sink
    8StorageStructures for the storage of goods, warehouses, storehouse and freight depots. Low and Moderate Hazard.1 per 1001 per 1001 per 1,0001 service sink
    1. a.The fixtures shown are based on one fixture being the minimum required for the number of persons indicated or any fraction of the number of persons indicated. The number of occupants shall be determined by the International Building Code.

    2. b.Toilet facilities for employees shall be separate from facilities for inmates or care recipients.

    3. c.A single-occupant toilet room with one water closet and one lavatory serving not more than two adjacent patient sleeping units shall be permitted provided that each patient sleeping unit has direct access to the toilet room and provision for privacy for the toilet room user is provided.

    4. d.The occupant load for seasonal outdoor seating and entertainment areas shall be included when determining the minimum number of facilities required.

    5. e.For business and mercantile classifications with an occupant load of 15 or fewer, service sinks shall not be required.

    6. f.The required number and type of plumbing fixtures for outdoor public swimming pools shall be in accordance with Section 609 of the International Swimming Pool and Spa Code.

    403.1.1Fixture calculations.

    To determine the occupant load of each sex, the total occupant load shall be divided in half. To determine the required number of fixtures, the fixture ratio or ratios for each fixture type shall be applied to the occupant load of each sex in accordance with Table 403.1. Fractional numbers resulting from applying the fixture ratios of Table 403.1 shall be rounded up to the next whole number. For calculations involving multiple occupancies, such fractional numbers for each occupancy shall first be summed and then rounded up to the next whole number.

    Exception: The total occupant load shall not be required to be divided in half where approved statistical data indicates a distribution of the sexes of other than 50 percent of each sex.

    403.1.2Single-user toilet facility and bathing room fixtures.

    The plumbing fixtures located in single-user toilet facilities and bathing rooms, including family or assisteduse toilet and bathing rooms that are required by Section 1109.2.1 of the International Building Code, shall contribute toward the total number of required plumbing fixtures for a building or tenant space. Single-user toilet facilities and bathing rooms, and family or assisted-use toilet rooms and bathing rooms shall be identified for use by either sex.

    403.1.3Lavatory distribution.

    Where two or more toilet rooms are provided for each sex, the required number of lavatories shall be distributed proportionately to the required number of water closets.

    403.2Separate facilities.

    Where plumbing fixtures are required, separate facilities shall be provided for each sex.

    Exceptions:

    1. 1.Separate facilities shall not be required for dwelling units and sleeping units.

    2. 2.Separate facilities shall not be required in structures or tenant spaces with a total occupant load, including both employees and customers, of 15 or fewer.

    3. 3.Separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 100 or fewer.

    4. 4.Separate facilities shall not be required in business occupancies in which the maximum occupant load is 25 or fewer.

    403.2.1Family or assisted-use toilet facilities serving as separate facilities.

    Where a building or tenant space requires a separate toilet facility for each sex and each toilet facility is required to have only one water closet, two family or assisted-use toilet facilities shall be permitted to serve as the required separate facilities. Family or assisted-use toilet facilities shall not be required to be identified for exclusive use by either sex as required by Section 403.4.

    403.3Employee and public toilet facilities.

    For structures and tenant spaces intended for public utilization, customers, patrons and visitors shall be provided with public toilet facilities. Employees associated with structures and tenant spaces shall be provided with toilet facilities. The number of plumbing fixtures located within the required toilet facilities shall be provided in accordance with Section 403 for all users. Employee toilet facilities shall be either separate or combined employee and public toilet facilities.

    Exception: Public toilet facilities shall not be required for:

    1. 1.Parking garages operated without parking attendants.

    2. 2.Structures and tenant spaces intended for quick transactions, including takeout, pickup and drop-off, having a public access area less than or equal to 300 square feet (28 m2).

    403.3.1Access.

    The route to the public toilet facilities required by Section 403.3 shall not pass through kitchens, storage rooms or closets. Access to the required facilities shall be from within the building or from the exterior of the building. Routes shall comply with the accessibility requirements of the International Building Code. The public shall have access to the required toilet facilities at all times that the building is occupied.

    403.3.2Prohibited toilet room location.

    Toilet rooms shall not open directly into a room used for the preparation of food for service to the public.

    403.3.3Location of toilet facilities in occupancies other than malls.

    In occupancies other than covered and open mall buildings, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m).

    Exception: The location and maximum distances of travel to required employee facilities in factory and industrial occupancies are permitted to exceed that required by this section, provided that the location and maximum distance of travel are approved.

    403.3.4Location of toilet facilities in malls.

    In covered and open mall buildings, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed a distance of 300 feet (91 m). In mall buildings, the required facilities shall be based on total square footage within a covered mall building or within the perimeter line of an open mall building, and facilities shall be installed in each individual store or in a central toilet area located in accordance with this section. The maximum distance of travel to central toilet facilities in mall buildings shall be measured from the main entrance of any store or tenant space. In mall buildings, where employees’ toilet facilities are not provided in the individual store, the maximum distance of travel shall be measured from the employees’ work area of the store or tenant space.

    403.3.5Pay facilities.

    Where pay facilities are installed, such facilities shall be in excess of the required minimum facilities. Required facilities shall be free of charge.

    403.3.6Door locking.

    Where a toilet room is provided for the use of multiple occupants, the egress door for the room shall not be lockable from the inside of the room. This section does not apply to family or assisted-use toilet rooms.

    403.4 Signage.

    Required public facilities shall be provided with signs that designate the sex, as required by Section 403.2. Signs shall be readily visible and located near the entrance to each toilet facility. Signs for accessible toilet facilities shall comply with Section 1111 of the International Building Code.

    403.4.1Directional signage.

    Directional signage indicating the route to the required public toilet facilities shall be posted in a lobby, corridor, aisle or similar space, such that the sign can be readily seen from the main entrance to the building or tenant space.

    403.5Drinking fountain location.

    Drinking fountains shall not be required to be located in individual tenant spaces provided that public drinking fountains are located within a distance of travel of 500 feet (152 m) of the most remote location in the tenant space and not more than one story above or below the tenant space. Where the tenant space is in a covered or open mall, such distance shall not exceed 300 feet (91 m). Drinking fountains shall be located on an accessible route.

    SECTION404
    ACCESSIBLE PLUMBING FACILITIES

    404.1Where required.

    Accessible plumbing facilities and fixtures shall be provided in accordance with the International Building Code.

    404.2Accessible fixture requirements.

    Accessible plumbing fixtures shall be installed with the clearances, heights, spacings and arrangements in accordance with ICC A117.1.

    404.3Exposed pipes and surfaces.

    Water supply and drain pipes under accessible lavatories and sinks shall be covered or otherwise configured to protect against contact. Pipe coverings shall comply with ASME A112.18.9.

    SECTION405
    INSTALLATION OF FIXTURES

    405.1Water supply protection.

    The supply lines and fittings for every plumbing fixture shall be installed so as to prevent backflow.

    405.2Access for cleaning.

    Plumbing fixtures shall be installed so as to afford easy access for cleaning both the fixture and the area around the fixture.

    405.3Setting.

    Fixtures shall be set level and in proper alignment with reference to adjacent walls.

    405.3.1Water closets, urinals, lavatories and bidets.

    A water closet, urinal, lavatory or bidet shall not be set closer than 15 inches (381 mm) from its center to any side wall, partition, vanity or other obstruction. Where partitions or other obstructions do not separate adjacent fixtures, fixtures shall not be set closer than 30 inches (762 mm) center to center between adjacent fixtures. There shall be not less than a 21-inch (533 mm) clearance in front of a water closet, urinal, lavatory or bidet to any wall, fixture or door. Water closet compartments shall be not less than 30 inches (762 mm) in width and not less than 60 inches (1524 mm) in depth for floor-mounted water closets and not less than 30 inches (762 mm) in width and 56 inches (1422 mm) in depth for wall-hung water closets.

    Exception: An accessible children’s water closet shall be set not closer than 12 inches (305 mm) from its center to the required partition or to the wall on one side.

    405.3.2Public lavatories.

    In employee and public toilet rooms, the required lavatory shall be located in the same room as the required water closet.

    405.3.3Location of fixtures and piping.

    Piping, fixtures or equipment shall not be located in such a manner as to interfere with the normal operation of windows, doors or other means of egress openings.

    405.3.4Water closet compartment.

    Each water closet utilized by the public or employees shall occupy a separate compartment with walls or partitions and a door enclosing the fixtures to ensure privacy.

    Exceptions:

    1. 1.Water closet compartments shall not be required in a single-occupant toilet room with a lockable door.

    2. 2.Toilet rooms located in child day care facilities and containing two or more water closets shall be permitted to have one water closet without an enclosing compartment.

    3. 3.This provision is not applicable to toilet areas located within Group I-3 housing areas.

    405.3.5Urinal partitions.

    Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The horizontal dimension between walls or partitions at each urinal shall be not less than 30 inches (762 mm). The walls or partitions shall begin at a height not greater than 12 inches (305 mm) from and extend not less than 60 inches (1524 mm) above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal not less than 18 inches (457 mm) or to a point not less than 6 inches (152 mm) beyond the outermost front lip of the urinal measured from the finished backwall surface, whichever is greater.

    Exceptions:

    1. 1.Urinal partitions shall not be required in a singleoccupant or family/assisted-use toilet room with a lockable door.

    2. 2.Toilet rooms located in child day care facilities and containing two or more urinals shall be permitted to have one urinal without partitions.

    405.4Floor and wall drainage connections.

    Connections between the drain and floor outlet plumbing fixtures shall be made with a floor flange or a waste connector and sealing gasket. The waste connector and sealing gasket joint shall comply with the joint tightness test of ASME A112.4.3 and shall be installed in accordance with the manufacturer’s instructions. The flange shall be attached to the drain and anchored to the structure. Connections between the drain and wall-hung water closets shall be made with an approved extension nipple or horn adaptor. The water closet shall be bolted to the hanger with corrosion-resistant bolts or screws. Joints shall be sealed with an approved elastomeric gasket, flange-to-fixture connection complying with ASME A112.4.3 or an approved setting compound.

    405.4.1Floor flanges.

    Floor flanges for water closets or similar fixtures shall be not less than 0.125 inch (3.2 mm) thick for copper alloy, 0.25 inch (6.4 mm) thick for plastic and 0.25 inch (6.4 mm) thick and not less than a 2-inch (51 mm) caulking depth for cast iron or galvanized malleable iron.

    Floor flanges of hard lead shall weigh not less than 1 pound, 9 ounces (0.7 kg) and shall be composed of lead alloy with not less than 7.75-percent antimony by weight. Closet screws and bolts shall be of copper alloy. Flanges shall be secured to the building structure with corrosion-resistant screws or bolts.

    405.4.2Securing floor outlet fixtures.

    Floor outlet fixtures shall be secured to the floor or floor flanges by screws or bolts of corrosion-resistant material.

    405.4.3Securing wall-hung water closet bowls.

    Wall-hung water closet bowls shall be supported by a concealed metal carrier that is attached to the building structural members so that strain is not transmitted to the closet connector or any other part of the plumbing system. The carrier shall conform to ASME A112.6.2.

    405.5Plumbing fixtures with a pumped waste.

    Plumbing fixtures with a pumped waste shall comply with ASME A112.3.4/CSA B45.9. The plumbing fixture with a pumped waste shall be installed in accordance with the manufacturer’s instructions.

    405.6Water-tight joints.

    Joints formed where fixtures come in contact with walls or floors shall be sealed.

    405.7Plumbing in mental health centers.

    In mental health centers, pipes or traps shall not be exposed, and fixtures shall be bolted through walls.

    405.8Design of overflows.

    Where any fixture is provided with an overflow, the waste shall be designed and installed so that standing water in the fixture will not rise in the overflow when the stopper is closed, and water will not remain in the overflow when the fixture is empty.

    405.8.1Connection of overflows.

    The overflow from any fixture shall discharge into the drainage system on the inlet or fixture side of the trap.

    Exception: The overflow from a flush tank serving a water closet or urinal shall discharge into the fixture served.

    405.9Slip joint connections.

    Slip joints shall be made with an approved elastomeric gasket and shall only be installed on the trap outlet, trap inlet and within the trap seal. Fixtures with concealed slip-joint connections shall be provided with an access panel or utility space not less than 12 inches (305 mm) in its smallest dimension or other approved arrangement so as to provide access to the slip joint connections for inspection and repair.

    405.10Design and installation of plumbing fixtures.

    Integral fixture fitting mounting surfaces on manufactured plumbing fixtures or plumbing fixtures constructed on site shall meet the design requirements of ASME A112.19.2/CSA B45.1 or ASME A112.19.3/CSA B45.4.

    SECTION406
    AUTOMATIC CLOTHES WASHERS 

    406.1Water connection.

    The water supply to an automatic clothes washer shall be protected against backflow by an air gap that is integral with the machine or a backflow preventer shall be installed in accordance with Section 608. Air gaps shall comply with ASME A112.1.2 or A112.1.3.

    406.2Waste connection.

    The waste from an automatic clothes washer shall discharge through an air break into a standpipe in accordance with Section 802.3.3 or into a laundry sink. The trap and fixture drain for an automatic clothes washer standpipe shall be not less than 2 inches (51 mm) in diameter. The fixture drain for the standpipe serving an automatic clothes washer shall connect to a 3-inch (76 mm) or larger diameter fixture branch or stack. Automatic clothes washers that discharge by gravity shall be permitted to drain to a waste receptor or an approved trench drain.

    SECTION407
    BATHTUBS 

    407.1Approval.

    Bathtubs shall conform to ASME A112.19.1/CSA B45.2, ASME A112.19.2/CSA B45.1, ASME A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124.

    407.2Bathtub waste outlets and overflows.

    Bathtubs shall be equipped with a waste outlet and an overflow outlet. The outlets shall be connected to waste tubing or piping not less than 11/2 inches (38 mm) in diameter. The waste outlet shall be equipped with a water-tight stopper.

    407.3Glazing.

    Windows and doors within a bathtub enclosure shall conform to the safety glazing requirements of the International Building Code.

    407.4Bathtub enclosure.

    Doors in a bathtub enclosure shall conform to ASME A112.19.15.

    SECTION408
    BIDETS

    408.1Approval.

    Bidets shall conform to ASME A112.19.2/CSA B45.1.

    408.2Water connection.

    The water supply to a bidet shall be protected against backflow by an air gap or backflow preventer in accordance with Section 608.13.1, 608.13.2, 608.13.3, 608.13.5, 608.13.6 or 608.13.8.

    408.3Bidet water temperature.

    The discharge water temperature from a bidet fitting shall be limited to not greater than 110°F (43°C) by a water-temperature-limiting device conforming to ASSE 1070/ASME A112.1070/CSA B125.70 or CSA B125.3.

    SECTION409
    DISHWASHING MACHINES

    409.1Approval.

    Commercial dishwashing machines shall conform to ASSE 1004 and NSF 3. Residential dishwashers shall conform to NSF 184.

    409.2Water connection.

    The water supply to a dishwashing machine shall be protected against backflow by an air gap that is integral with the machine or a backflow preventer shall be installed in accordance with Section 608. Air gaps shall comply with ASME A112.1.2 or A112.1.3.

    409.3Waste connection.

    The waste connection of a commercial dishwashing machine shall comply with Section 802.1.6.

    409.4Residential dishwasher waste connection.

    The waste connection of a residential dishwasher shall connect directly to a wye branch fitting on the tailpiece of the kitchen sink, directly to the dishwasher connection of a food waste disposer, or through an air break to a standpipe. The waste line of a residential dishwasher shall rise and be securely fastened to the underside of the sink rim or counter top.

    SECTION410
    DRINKING FOUNTAINS

    410.1Approval.

    Drinking fountains shall conform to ASME A112.19.1/CSA B45.2 or ASME A112.19.2/CSA B45.1 and water coolers shall conform to ASHRAE 18. Drinking fountains, water coolers and water dispensers shall conform to NSF 61, Section 9. Electrically operated, refrigerated drinking water coolers and water dispensers shall be listed and labeled in accordance with UL 399.

    410.2Small occupancies.

    Drinking fountains shall not be required for an occupant load of 15 or fewer.

    [BE]410.3High and low drinking fountains.

    Where drinking fountains are required, not fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons.

    Exceptions:

    1. 1.A single drinking fountain with two separate spouts that complies with the requirements for people who use a wheelchair and standing persons shall be permitted to be substituted for two separate drinking fountains.

    2. 2.Where drinking fountains are primarily for children’s use, the drinking fountains for people using wheelchairs shall be permitted to comply with the children’s provisions in ICC A117.1 and drinking fountains for standing children shall be permitted to provide the spout at 30 inches (762 mm) minimum above the floor.

    410.4Substitution.

    Where restaurants provide drinking water in a container free of charge, drinking fountains shall not be required in those restaurants. In other occupancies where drinking fountains are required, water dispensers shall be permitted to be substituted for not more than 50 percent of the required number of drinking fountains.

    410.5Prohibited location.

    Drinking fountains, water coolers and water dispensers shall not be installed in public restrooms.

    SECTION411
    EMERGENCY SHOWERS
    AND EYEWASH STATIONS

    411.1Approval.

    Emergency showers and eyewash stations shall conform to ISEA Z358.1.

    411.2Waste connection.

    Waste connections shall not be required for emergency showers and eyewash stations.

    411.3Water supply.

    Where hot and cold water is supplied to an emergency shower or eyewash station, the temperature of the water supply shall only be controlled by a temperature actuated mixing valve complying with ASSE 1071.

    SECTION412
    FAUCETS AND OTHER FIXTURE FITTINGS 

    412.1Approval.

    Faucets and fixture fittings shall conform to ASME A112.18.1/CSA B125.1. Faucets and fixture fittings that supply drinking water for human ingestion shall conform to the requirements of NSF 61, Section 9. Flexible water connectors exposed to continuous pressure shall conform to the requirements of Section 605.6.

    412.1.1Faucets and supply fittings.

    Faucets and supply fittings shall conform to the water consumption requirements of Section 604.4.

    412.1.2Waste fittings.

    Waste fittings shall conform to ASME A112.18.2/CSA B125.2, ASTM F409 or to one of the standards listed in Tables 702.1 and 702.4 for aboveground drainage and vent pipe and fittings.

    412.2Hand showers.

    Hand-held showers shall conform to ASME A112.18.1/CSA B125.1. Hand-held showers shall provide backflow protection in accordance with ASME A112.18.1/CSA B125.1 or shall be protected against backflow by a device complying with ASME A112.18.3.

    412.3Individual shower valves.

    Individual shower and tubshower combination valves shall be balanced-pressure, thermostatic or combination balanced-pressure/thermostatic valves that conform to the requirements of ASSE 1016/ASME A112.1016/CSA B125.16 or ASME A112.18.1/CSA B125.1 and shall be installed at the point of use. Shower and tub-shower combination valves required by this section shall be equipped with a means to limit the maximum setting of the valve to 120°F (49°C), which shall be field adjusted in accordance with the manufacturer’s instructions. In-line thermostatic valves shall not be utilized for compliance with this section.

    412.4Multiple (gang) showers.

    Multiple (gang) showers supplied with a single-tempered water supply pipe shall have the water supply for such showers controlled by an approved automatic temperature control mixing valve that conforms to ASSE 1069 or CSA B125.3, or each shower head shall be individually controlled by a balanced-pressure, thermostatic or combination balanced-pressure/thermostatic valve that conforms to ASSE 1016/ASME A112.1016/CSA B125.16 or ASME A112.18.1/CSA B125.1 and is installed at the point of use. Such valves shall be equipped with a means to limit the maximum setting of the valve to 120°F (49°C), which shall be field adjusted in accordance with the manufacturers’ instructions.

    412.5Bathtub and whirlpool bathtub valves.

    The hot water supplied to bathtubs and whirlpool bathtubs shall be limited to not greater than 120°F (49°C) by a water-temperature limiting device that conforms to ASSE 1070/ASME A112.1070/CSA B125.70 or CSA B125.3, except where such protection is otherwise provided by a combination tub/shower valve in accordance with Section 412.3.

    412.6Hose-connected outlets.

    Faucets and fixture fittings with hose-connected outlets shall conform to ASME A112.18.3 or ASME A112.18.1/CSA B125.1.

    412.7Temperature-actuated, flow-reduction devices for individual fixture fittings.

    Temperature-actuated, flow-reduction devices, where installed for individual fixture fittings, shall conform to ASSE 1062. A temperature-actuated, flow-reduction device shall be an approved method for limiting the water temperature to not greater than 120° F (49° C) at the outlet of a faucet or fixture fitting. Such devices shall not be used alone as a substitute for the balanced-pressure, thermostatic or combination shower valves required in Section 412.3 or as a substitute for bathtub or whirlpool tub watertemperature-limiting valves required in Section 412.5.

    412.8Transfer valves.

    Deck-mounted bath/shower transfer valves containing an integral atmospheric vacuum breaker shall conform to the requirements of ASME A112.18.1/CSA B125.1.

    412.9Water closet personal hygiene devices.

    Personal hygiene devices integral to water closets or water closet seats shall conform to the requirements of ASME A112.4.2/CSA B45.16.

    412.10Head shampoo sink faucets.

    Head shampoo sink faucets shall be supplied with hot water that is limited to not more than 120°F (49°C) by a water-temperature-limiting device that conforms to ASSE 1070/ASME A112.1070/CSA B125.70. Each faucet shall have integral check valves to prevent crossover flow between the hot and cold water supply connections.

    SECTION413
    FLOOR AND TRENCH DRAINS 

    413.1Approval.

    Floor drains shall conform to ASME A112.3.1, ASME A112.6.3 or CSA B79. Trench drains shall comply with ASME A112.6.3.

    413.2Floor drains.

    Floor drains shall have removable strainers. The floor drain shall be constructed so that the drain is capable of being cleaned. Access shall be provided to the drain inlet. Ready access shall be provided to floor drains.

    Exception: Floor drains serving refrigerated display cases shall be provided with access.

    413.3Size of floor drains.

    Floor drains shall have a drain outlet not less than 2 inches (51 mm) in diameter.

    413.4Public laundries and central washing facilities.

    In public coin-operated laundries and in the central washing facilities of multiple-family dwellings, the rooms containing automatic clothes washers shall be provided with floor drains located to readily drain the entire floor area. Such drains shall have an outlet of not less than 3 inches (76 mm) in diameter.

    SECTION414
    FLOOR SINKS

    414.1Approval.

    Sanitary floor sinks shall conform to the requirements of ASME A112.6.7.

    SECTION415
    FLUSHING DEVICES FOR
    WATER CLOSETS AND URINALS
     

    415.1Flushing devices required.

    Each water closet, urinal, clinical sink and any plumbing fixture that depends on trap siphonage to discharge the fixture contents to the drainage system shall be provided with a flushometer valve, flushometer tank or a flush tank designed and installed to supply water in quantity and rate of flow to flush the contents of the fixture, cleanse the fixture and refill the fixture trap.

    415.1.1Separate for each fixture.

    A flushing device shall not serve more than one fixture.

    415.2Flushometer valves and tanks.

    Flushometer valves and tanks shall comply with ASSE 1037/ASME A112.1037/CSA B125.37 or CSA B125.3. Vacuum breakers on flushometer valves shall conform to the performance requirements of ASSE 1001 or CSA B64.1.1. Access shall be provided to vacuum breakers. Flushometer valves shall be of the water conservation type and shall not be used where the water pressure is lower than the minimum required for normal operation. When operated, the valve shall automatically complete the cycle of operation, opening fully and closing positively under the water supply pressure. Each flushometer valve shall be provided with a means for regulating the flow through the valve. The trap seal to the fixture shall be automatically refilled after each flushing cycle.

    415.3Flush tanks.

    Flush tanks equipped for manual flushing shall be controlled by a device designed to refill the tank after each discharge and to shut off completely the water flow to the tank when the tank is filled to operational capacity. The trap seal to the fixture shall be automatically refilled after each flushing. The water supply to flush tanks equipped for automatic flushing shall be controlled with a timing device or sensor control devices.

    415.3.1Fill valves.

    Flush tanks shall be equipped with an antisiphon fill valve conforming to ASSE 1002/ASME A112.1002/CSA B125.12 or CSA B125.3. The fill valve backflow preventer shall be located not less than 1 inch (25 mm) above the full opening of the overflow pipe.

    415.3.2Overflows in flush tanks.

    Flush tanks shall be provided with overflows discharging to the water closet or urinal connected thereto and shall be sized to prevent flooding the tank at the maximum rate at which the tanks are supplied with water according to the manufacturer’s design conditions. The opening of the overflow pipe shall be located above the flood level rim of the water closet or urinal or above a secondary overflow in the flush tank.

    415.3.3Sheet copper.

    Sheet copper utilized for flush tank linings shall conform to ASTM B152 and shall not weigh less than 10 ounces per square foot (0.03 kg/m2).

    415.3.4Access required.

    All parts in a flush tank shall be provided with access for repair and replacement.

    415.4Flush pipes and fittings.

    Flush pipes and fittings shall be of nonferrous material and shall conform to ASME A112.19.5/CSA B45.15.

    SECTION416
    FOOD WASTE DISPOSER UNITS

    416.1Approval.

    Domestic food waste disposers shall conform to ASSE 1008 and shall be listed and labeled in accordance with UL 430. Food waste disposers shall not increase the drainage fixture unit load on the sanitary drainage system.

    416.2Domestic food waste disposer waste outlets.

    Domestic food waste disposers shall be connected to a drain of not less than 11/2 inches (38 mm) in diameter.

    416.3Commercial food waste disposer waste outlets.

    Commercial food waste disposers shall be connected to a drain not less than 11/2 inches (38 mm) in diameter. Commercial food waste disposers shall be connected and trapped separately from any other fixtures or sink compartments.

    416.4Water supply required.

    Food waste disposers shall be provided with a supply of cold water. The water supply shall be protected against backflow by an air gap or backflow preventer in accordance with Section 608.

    SECTION417
    GARBAGE CAN WASHERS 

    417.1Water connection.

    The water supply to a garbage can washer shall be protected against backflow by an air gap or a backflow preventer in accordance with Section 608.13.1, 608.13.2, 608.13.3, 608.13.5, 608.13.6 or 608.13.8.

    417.2Waste connection.

    Garbage can washers shall be trapped separately. The receptacle receiving the waste from the washer shall have a removable basket or strainer to prevent the discharge of large particles into the drainage system.

    SECTION418
    LAUNDRY TRAYS

    418.1Approval.

    Laundry trays shall conform to ASME A112.19.1/CSA B45.2, ASME A112.19.2/CSA B45.1, ASME A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124.

    418.2Waste outlet.

    Each compartment of a laundry tray shall be provided with a waste outlet not less than 11/2 inches (38 mm) in diameter and a strainer or crossbar to restrict the clear opening of the waste outlet.

    SECTION419
    LAVATORIES 

    419.1Approval.

    Lavatories shall conform to ASME A112.19.1/CSA B45.2, ASME A112.19.2/CSA B45.1, ASME A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124. Group wash-up equipment shall conform to the requirements of Section 402. Every 20 inches (508 mm) of rim space shall be considered as one lavatory.

    419.2Cultured marble lavatories.

    Cultured marble vanity tops with an integral lavatory shall conform to CSA B45.5/IAPMO Z124.

    419.3Lavatory waste outlets.

    Lavatories shall have waste outlets not less than 11/4 inches (32 mm) in diameter. A strainer, pop-up stopper, crossbar or other device shall be provided to restrict the clear opening of the waste outlet.

    419.4Moveable lavatory systems.

    Moveable lavatory systems shall comply with ASME A112.19.12.

    419.5Tempered water for public hand-washing facilities.

    Tempered water shall be delivered from lavatories and group wash fixtures located in public toilet facilities provided for customers, patrons and visitors. Tempered water shall be delivered through an approved water-temperature limiting device that conforms to ASSE 1070/ASME A112.1070/CSA B125.70 or CSA B125.3.

    SECTION420
    MANUAL FOOD AND BEVERAGE
    DISPENSING EQUIPMENT
     

    420.1Approval.

    Manual food and beverage dispensing equipment shall conform to the requirements of NSF 18.

    SECTION421
    SHOWERS 

    421.1Approval.

    Prefabricated showers and shower compartments shall conform to ASME A112.19.2/CSA B45.1 or CSA B45.5/IAPMO Z124. Shower valves for individual showers shall conform to the requirements of Section 412.3.

    421.2Water supply riser.

    Water supply risers from the shower valve to the shower head outlet, whether exposed or concealed, shall be attached to the structure. The attachment to the structure shall be made by the use of support devices designed for use with the specific piping material or by fittings anchored with screws.

    421.3Shower waste outlet.

    Waste outlets serving showers shall be not less than 11/2 inches (38 mm) in diameter and, for other than waste outlets in bathtubs, shall have removable strainers not less than 3 inches (76 mm) in diameter with strainer openings not less than 1/4 inch (6.4 mm) in least dimension. Where each shower space is not provided with an individual waste outlet, the waste outlet shall be located and the floor pitched so that waste from one shower does not flow over the floor area serving another shower. Waste outlets shall be fastened to the waste pipe in an approved manner.

    421.4Shower compartments.

    Shower compartments shall be not less than 900 square inches (0.58 m2) in interior crosssectional area. Shower compartments shall be not less than 30 inches (762 mm) in least dimension as measured from the finished interior dimension of the compartment, exclusive of fixture valves, showerheads, soap dishes and safety grab bars or rails. Except as required in Section 404, the minimum required area and dimension shall be measured from the finished interior dimension at a height equal to the top of the threshold and at a point tangent to its centerline and shall be continued to a height not less than 70 inches (1778 mm) above the shower drain outlet.

    Exception: Shower compartments having not less than 25 inches (635 mm) in minimum dimension measured from the finished interior dimension of the compartment, provided that the shower compartment has not less than 1,300 square inches (0.838 m2) of cross-sectional area.

    421.4.1Floor and wall area.

    Bathtub floors, shower floors, wall areas above built-in tubs that have installed shower heads and walls in shower compartments shall be constructed of smooth, corrosion-resistant and nonabsorbent waterproof materials. Wall materials shall extend to a height of not less than 6 feet (1829 mm) above the room floor level, and not less than 70 inches (1778 mm) above the drain of the tub or shower. Such walls shall form a water-tight joint with each other and with either the tub or shower floor.

    421.4.2Access.

    The shower compartment access and egress opening shall have a clear and unobstructed finished width of not less than 22 inches (559 mm). Shower compartments required to be designed in conformance to accessibility provisions shall comply with Section 404.1.

    421.5Shower floors or receptors.

    Floor surfaces shall be constructed of impervious, noncorrosive, nonabsorbent and waterproof materials.

    421.5.1Support.

    Floors or receptors under shower compartments shall be laid on, and supported by, a smooth and structurally sound base.

    421.5.2Shower lining.

    Floors under shower compartments, except where prefabricated receptors have been provided, shall be lined and made water tight utilizing material complying with Sections 421.5.2.1 through 421.5.2.6. Such liners shall turn up on all sides not less than 2 inches (51 mm) above the finished threshold level. Liners shall be recessed and fastened to an approved backing so as not to occupy the space required for wall covering, and shall not be nailed or perforated at any point less than 1 inch (25 mm) above the finished threshold. Liners shall be pitched one-fourth unit vertical in 12 units horizontal (2-percent slope) and shall be sloped toward the fixture drains and be securely fastened to the waste outlet at the seepage entrance, making a water-tight joint between the liner and the outlet. The completed liner shall be tested in accordance with Section 312.9.

    Exceptions:

    1. 1.Floor surfaces under shower heads provided for rinsing laid directly on the ground are not required to comply with this section.

    2. 2.Where a sheet-applied, load-bearing, bonded, waterproof membrane is installed as the shower lining, the membrane shall not be required to be recessed.

    421.5.2.1PVC sheets.

    Plasticized polyvinyl chloride (PVC) sheets shall meet the requirements of ASTM D4551. Sheets shall be joined by solvent welding in accordance with the manufacturer’s installation instructions.

    421.5.2.2Chlorinated polyethylene (CPE) sheets.

    Nonplasticized chlorinated polyethylene sheet shall meet the requirements of ASTM D4068. The liner shall be joined in accordance with the manufacturer’s installation instructions.

    421.5.2.3Sheet lead.

    Sheet lead shall weigh not less than 4 pounds per square foot (19.5 kg/m2) and shall be coated with an asphalt paint or other approved coating. The lead sheet shall be insulated from conducting substances other than the connecting drain by 15-pound (6.80 kg) asphalt felt or an equivalent. Sheet lead shall be joined by burning.

    421.5.2.4Sheet copper.

    Sheet copper shall conform to ASTM B152 and shall weigh not less than 12 ounces per square foot (3.7 kg/m2). The copper sheet shall be insulated from conducting substances other than the connecting drain by 15-pound (6.80 kg) asphalt felt or an equivalent. Sheet copper shall be joined by brazing or soldering.

    421.5.2.5Sheet-applied, load-bearing, bonded, waterproof membranes.

    Sheet-applied, load-bearing, bonded, waterproof membranes shall meet requirements of TCNA A118.10 and shall be applied in accordance with the manufacturer’s installation instructions.

    421.5.2.6Liquid-type, trowel-applied, load-bearing, bonded waterproof materials.

    Liquid-type, trowelapplied, load-bearing, bonded waterproof materials shall meet the requirements of TCNA A118.10 and shall be applied in accordance with the manufacturer’s instructions.

    421.6Glazing.

    Windows and doors within a shower enclosure shall conform to the safety glazing requirements of the International Building Code.

    SECTION422
    SINKS 

    422.1Approval.

    Sinks shall conform to ASME A112.19.1/CSA B45.2, ASME A112.19.2/CSA B45.1, ASME A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124.

    422.2Sink waste outlets.

    Sinks shall be provided with waste outlets having a diameter not less than 11/2 inches (38 mm). A strainer or crossbar shall be provided to restrict the clear opening of the waste outlet.

    422.3Moveable sink systems.

    Moveable sink systems shall comply with ASME A112.19.12.

    SECTION423
    SPECIALTY PLUMBING FIXTURES

    423.1Water connections.

    Baptisteries, ornamental and lily pools, aquariums, ornamental fountain basins, swimming pools, and similar constructions, where provided with water supplies, shall be protected against backflow in accordance with Section 608.

    423.2Approval.

    Specialties requiring water and waste connections shall be submitted for approval.

    423.3 Footbaths and pedicure baths.

    The water supplied to specialty plumbing fixtures, such as pedicure chairs having an integral foot bathtub and footbaths, shall be limited to not greater than 120°F (49°C) by a water-temperature-limiting device that conforms to ASSE 1070/ASME A112.1070/CSA B125.70 or CSA B125.3.

    SECTION424
    URINALS 

    424.1Approval.

    Urinals shall conform to ASME A112.19.2/CSA B45.1, ASME A112.19.19 or CSA B45.5/IAPMO Z124. Urinals shall conform to the water consumption requirements of Section 604.4. Water-supplied urinals shall conform to the hydraulic performance requirements of ASME A112.19.2/CSA B45.1 or CSA B45.5/IAPMO Z124.

    424.2Substitution for water closets.

    In each bathroom or toilet room, urinals shall not be substituted for more than 67 percent of the required water closets in assembly and educational occupancies. Urinals shall not be substituted for more than 50 percent of the required water closets in all other occupancies.

    SECTION425
    WATER CLOSETS 

    425.1Approval.

    Water closets shall conform to the water consumption requirements of Section 604.4 and shall conform to ASME A112.19.2/CSA B45.1, ASME A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124. Water closets shall conform to the hydraulic performance requirements of ASME A112.19.2/CSA B45.1. Water closet tanks shall conform to ASME A112.19.2/CSA B45.1, ASME A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124. Electro-hydraulic water closets shall comply with ASME A112.19.2/CSA B45.1. Water closets equipped with a dual flushing device shall comply with ASME A112.19.14.

    425.2Water closets for public or employee toilet facilities.

    Water closet bowls for public or employee toilet facilities shall be of the elongated type.

    425.3Water closet seats.

    Water closets shall be equipped with seats of smooth, nonabsorbent material. Seats of water closets provided for public or employee toilet facilities shall be of the hinged open-front type. Integral water closet seats shall be of the same material as the fixture. Water closet seats shall be sized for the water closet bowl type.

    425.4Water closet connections.

    A 4-inch by 3-inch (102 mm by 76 mm) closet bend shall be acceptable. Where a 3-inch (76 mm) bend is utilized on water closets, a 4-inch by 3-inch (102 mm by 76 mm) flange shall be installed to receive the fixture horn.

    SECTION426
    WHIRLPOOL BATHTUBS

    426.1Approval.

    Whirlpool bathtubs shall comply with ASME A112.19.7/CSA B45.10 and shall be listed and labeled in accordance with UL 1795.

    426.2Installation.

    Whirlpool bathtubs shall be installed and tested in accordance with the manufacturer’s instructions. The pump shall be located above the weir of the fixture trap.

    426.3Drain.

    The pump drain and circulation piping shall be sloped to drain the water in the volute and the circulation piping when the whirlpool bathtub is empty.

    426.4Suction fittings.

    Suction fittings for whirlpool bathtubs shall comply with ASME A112.19.7/CSA B45.10.

    426.5Access to pump.

    Access shall be provided to circulation pumps in accordance with the fixture or pump manufacturer’s installation instructions. Where the manufacturer’s instructions do not specify the location and minimum size of field-fabricated access openings, an opening not less than 12 inches by 12 inches (305 mm by 305 mm) shall be installed to provide access to the circulation pump. Where pumps are located more than 2 feet (609 mm) from the access opening, an opening not less than 18 inches by 18 inches (457 mm by 457 mm) shall be installed. A door or panel shall be permitted to close the opening. In all cases, the access opening shall be unobstructed and of the size necessary to permit the removal and replacement of the circulation pump.

    426.6Whirlpool enclosure.

    Doors within a whirlpool enclosure shall conform to ASME A112.19.15.