CHAPTER 36
SERVICES


  • SECTION E3601
    GENERAL SERVICES

    E3601.1 Scope.
    This chapter covers service conductors and equipment for the control and protection of services and their installation requirements.

    E3601.2 Number of services.
    One- and two-family dwellings shall be supplied by only one service.

    E3601.3 One building or other structure not to be supplied through another.
    Service conductors supplying a building or other structure shall not pass through the interior of another building or other structure.

    E3601.4 Other conductors in raceway or cable.
    Conductors other than service conductors shall not be installed in the same service raceway or service cable.

    Exceptions:

    1. Grounding conductors and bonding jumpers.

    2. Load management control conductors having overcurrent protection.

    E3601.5 Raceway seal.
    Where a service raceway enters from an underground distribution system, it shall be sealed in accordance with Section E3803.6.

    E3601.6 Service disconnect required.
    Means shall be provided to disconnect all conductors in a building or other structure from the service entrance conductors.

    E3601.6.1 Marking of service equipment and disconnects.
    Service disconnects shall be permanently marked as a service disconnect.

    E3601.6.2 Service disconnect location.
    The service disconnecting means shall be installed at a readily accessible location either outside of a building or inside nearest the point of entrance of the service conductors. Service disconnecting means shall not be installed in bathrooms. Each occupant shall have access to the disconnect serving the dwelling unit in which they reside.

    E3601.7 Maximum number of disconnects.
    The service disconnecting means shall consist of not more than six switches or six circuit breakers mounted in a single enclosure or in a group of separate enclosures.

    SECTION E3602
    SERVICE SIZE AND RATING

    E3602.1 Ampacity of ungrounded conductors.
    Ungrounded service conductors shall have an ampacity of not less than the load served. For one-family dwellings, the ampacity of the ungrounded conductors shall be not less than 100 amperes, 3 wire. For all other installations, the ampacity of the ungrounded conductors shall be not less than 60 amperes.

    E3602.2 Service load.
    The minimum load for ungrounded service conductors and service devices that serve 100 percent of the dwelling unit load shall be computed in accordance with Table E3602.2. Ungrounded service conductors and service devices that serve less than 100 percent of the dwelling unit load shall be computed as required for feeders in accordance with Chapter 37.

    TABLE E3602.2
    MINIMUM SERVICE LOAD CALCULATION

    LOADS AND PROCEDURE
    3 volt-amperes per square foot of floor area for general lighting and general use receptacle outlets.
    Plus
    1,500 volt-amperes multiplied by total number of 20-ampere-rated small appliance and laundry circuits.
    Plus
    The nameplate volt-ampere rating of all fastened-in-place, permanently connected or dedicated circuit-supplied appliances such as ranges, ovens, cooking units, clothes dryers not connected to the laundry branch circuit and water heaters.
    Apply the following demand factors to the above subtotal:
    The minimum subtotal for the loads above shall be 100 percent of the first 10,000 volt-amperes of the sum of the above loads plus 40 percent of any portion of the sum that is in excess of 10,000 volt-amperes.
    Plus the largest of the following:
    One-hundred percent of the nameplate rating(s) of the air-conditioning and cooling equipment.
    One hundred percent of the nameplate rating(s) of the heat pump where a heat pump is used without any supplemental electric heating.
    One-hundred percent of the nameplate rating of the electric thermal storage and other heating systems where the usual load is expected to be continuous at the full nameplate value. Systems qualifying under this selection shall not be figured under any other category in this table.
    One-hundred percent of nameplate rating of the heat pump compressor and sixty-five percent of the supplemental electric heating load for central electric space-heating systems. If the heat pump compressor is prevented from operating at the same time as the supplementary heat, the compressor load does not need to be added to the supplementary heat load for the total central electric space-heating load.
    Sixty-five percent of nameplate rating(s) of electric space-heating units if less than four separately controlled units.
    Forty percent of nameplate rating(s) of electric space-heating units of four or more separately controlled units.
    The minimum total load in amperes shall be the
    volt-ampere sum calculated above divided by 240 volts.

    E3602.2.1 Services under 100 amperes.
    Services that are not required to be 100 amperes shall be sized in accordance with Chapter 37.

    E3602.3 Rating of service disconnect.
    The combined rating of all individual service disconnects serving a single dwelling unit shall not be less than the load determined from Table E3602.2 and shall not be less than as specified in Section E3602.1.

    E3602.4 Voltage rating.
    Systems shall be three-wire, 120/240-volt, single-phase with a grounded neutral.

    SECTION E3603
    SERVICE, FEEDER AND GROUNDING ELECTRODE
    CONDUCTOR SIZING

    E3603.1 Grounded and ungrounded service conductor size.
    Conductors used as ungrounded service entrance conductors, service lateral conductors, and feeder conductors that serve as the main power feeder to a dwelling unit shall be those listed in Table E3603.1. The main power feeder shall be the feeder(s) between the main disconnect and the panelboard that supplies, either by branch circuits or by feeders, or both, all loads that are part of or are associated with the dwelling unit. The feeder conductors to a dwelling unit shall not be required to have an allowable ampacity greater than that of the service-entrance conductors that supply them. Ungrounded service conductors shall have a minimum size in accordance with Table E3603.1. The grounded conductor ampacity shall be not less than the maximum unbalance of the load and its size shall be not smaller than the required minimum grounding electrode conductor size specified in Table E3603.1.

    TABLE E3603.1
    SERVICE CONDUCTOR AND GROUNDING ELECTRODE CONDUCTOR SIZING

    CONDUCTOR TYPES AND SIZES-THHN, THHW, THW, THWN, USE, RHH,
    RHW, XHHW, RHW-2, THW-2, THWN-2, XHHW-2, SE, USE-2
    (Parallel sets of 1/0 and larger conductors are permitted in either a single
    raceway or in separate raceways)
    SERVICE OR FEEDER
    RATING (AMPERES)
    MINIMUM GROUNDING
    ELECTRODE CONDUCTOR SIZEa
    Copper
    (AWG)
    Aluminum and copper-clad aluminum
    (AWG)
    Maximum load
    (amps)
    Copper
    (AWG)
    Aluminum
    (AWG)
    421008b6c
    311108b6c
    21/01258b6c
    12/01506c4
    1/03/01756c4
    2/04/0 or two sets of 1/02004d2d
    3/0250 kcmil or two sets of 2/02254d2d
    4/0 or two sets of 1/0300 kcmil ortwo sets of 3/02502d1/0d
    250 kcmil or two sets of 2/0350 kcmil or two sets of 4/03002d1/0d
    350 kcmil or two sets of 3/0500 kcmil or two sets of 250 kcmil3502d1/0d
    400 kcmil or two sets of 4/0600 kcmil or two sets of 300 kcmil4001/0d3/0d
    For SI: 1 inch = 25.4 mm.
    a. Where protected by a ferrous metal raceway, grounding electrode conductors shall be electrically bonded to the ferrous metal raceway at both ends.
    b. An 8 AWG grounding electrode conductor shall be protected with rigid metal conduit, intermediate metal conduit, rigid polyvinyl chloride (Type PVC) nonmetallic conduit, rigid thermosetting resin (Type RTRC) nonmetallic conduit, electrical metallic tubing or cable armor.
    c. Where not protected, 6 AWG grounding electrode conductor shall closely follow a structural surface for physical protection. The supports shall be spaced not more than 24 inches on center and shall be within 12 inches of any enclosure or termination.
    d. Where the sole grounding electrode system is a ground rod or pipe as covered in Section E3608.2, the grounding electrode conductor shall not be required to be larger than 6 AWG copper or 4 AWG aluminum. Where the sole grounding electrode system is the footing steel as covered in Section E3608.1.2, the grounding electrode conductor shall not be required to be larger than 4 AWG copper conductor.

    E3603.2 Ungrounded service conductors for accessory buildings and structures.
    Ungrounded conductors for other than dwelling units shall have an ampacity of not less than 60 amperes and shall be sized as required for feeders in Chapter 37.

    Exceptions:

    1. For limited loads of a single branch circuit, the service conductors shall have an ampacity of not less than 15 amperes.

    2. For loads consisting of not more than two two-wire branch circuits, the service conductors shall have an ampacity of not less than 30 amperes.

    E3603.3 Overload protection.
    Each ungrounded service conductor shall have overload protection.

    E3603.3.1 Ungrounded conductor.
    Overload protection shall be provided by an overcurrent device installed in series with each ungrounded service conductor. The overcurrent device shall have a rating or setting not higher than the allowable service or feeder rating specified in Table E3603.1. A set of fuses shall be considered all the fuses required to protect all of the ungrounded conductors of a circuit. Single pole circuit breakers, grouped in accordance with Section E3601.7, shall be considered as one protective device.

    Exception: Two to six circuit breakers or sets of fuses shall be permitted as the overcurrent device to provide the overload protection. The sum of the ratings of the circuit breakers or fuses shall be permitted to exceed the ampacity of the service conductors, provided that the calculated load does not exceed the ampacity of the service conductors.

    E3603.3.2 Not in grounded conductor.
    Overcurrent devices shall not be connected in series with a grounded service conductor except where a circuit breaker is used that simultaneously opens all conductors of the circuit.

    E3603.3.3 Location.
    The service overcurrent device shall be an integral part of the service disconnecting means or shall be located immediately adjacent thereto.

    E3603.4 Grounding electrode conductor size.
    The grounding electrode conductors shall be sized based on the size of the service entrance conductors as required in Table E3603.1.

    E3603.5 Temperature limitations.
    Except where the equipment is marked otherwise, conductor ampacities used in determining equipment termination provisions shall be based on Table E3603.1.

    SECTION E3604
    OVERHEAD SERVICE AND SERVICE-
    ENTRANCE CONDUCTOR INSTALLATION

    E3604.1 Clearances on buildings.
    Open conductors and multiconductor cables without an overall outer jacket shall have a clearance of not less than 3 feet (914 mm) from the sides of doors, porches, decks, stairs, ladders, fire escapes and balconies, and from the sides and bottom of windows that open. See Figure E3604.1.

    For SI: 1 foot = 304.8 mm.

    FIGURE E3604.1
    CLEARANCES FROM BUILDING OPENINGS

    E3604.2 Vertical clearances.
    Overhead service conductors shall not have ready access and shall comply with Sections E3604.2.1 and E3604.2.2.

    E3604.2.1 Above roofs.
    Conductors shall have a vertical clearance of not less than 8 feet (2438 mm) above the roof surface. The vertical clearance above the roof level shall be maintained for a distance of not less than 3 feet (914 mm) in all directions from the edge of the roof. See Figure E3604.2.1.

    Exceptions:

    1. Conductors above a roof surface subject to pedestrian traffic shall have a vertical clearance from the roof surface in accordance with Section E3604.2.2.

    2. Where the roof has a slope of 4 inches (102 mm) in 12 inches (305 mm), or greater, the minimum clearance shall be 3 feet (914 mm).

    3. The minimum clearance above only the overhanging portion of the roof shall not be less than 18 inches (457 mm) where not more than 6 feet (1829 mm) of overhead service conductor length passes over 4 feet (1219 mm) or less of roof surface measured horizontally and such conductors are terminated at a through-the-roof raceway or approved support.

    4. The requirement for maintaining the vertical clearance for a distance of 3 feet (914 mm) from the edge of the roof shall not apply to the final conductor span where the service drop is attached to the side of a building.

    5. Where the voltage between conductors does not exceed 300 and the roof area is guarded or isolated, a reduction in clearance to 3 feet (914 mm) shall be permitted.

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

    FIGURE E3604.2.1
    CLEARANCES FROM ROOFS

    E3604.2.2 Vertical clearance from grade.
    Overhead service conductors shall have the following minimum clearances from final grade:

    1. For conductors supported on and cabled together with a grounded bare messenger wire, the minimum vertical clearance shall be 10 feet (3048 mm) at the electric service entrance to buildings, at the lowest point of the drip loop of the building electric entrance, and above areas or sidewalks accessed by pedestrians only. Such clearance shall be measured from final grade or other accessible surfaces.

    2. Twelve feet (3658 mm)—over residential property and driveways.

    3. Eighteen feet (5486 mm)—over public streets, alleys, roads or parking areas subject to truck traffic.

    E3604.3 Point of attachment.
    The point of attachment of the service-drop conductors to a building or other structure shall provide the minimum clearances as specified in Sections E3604.1 through E3604.2.2. In no case shall the point of attachment be less than 10 feet (3048 mm) above finished grade.

    E3604.4 Means of attachment.
    Multiconductor cables used for overhead service conductors shall be attached to buildings or other structures by fittings approved for the purpose.

    E3604.5 Service masts as supports.
    Where a service mast is used for the support of service-drop conductors, it shall be of adequate strength or be supported by braces or guys to withstand the strain imposed by the service drop. Where raceway-type service masts are used, all equipment shall be approved. Only power service drop conductors shall be permitted to be attached to a service mast.

    E3604.6 Supports over buildings.
    Service conductors passing over a roof shall be securely supported. Where practicable, such supports shall be independent of the building.

    SECTION E3605
    SERVICE-ENTRANCE CONDUCTORS

    E3605.1 Insulation of service-entrance conductors.
    Service-entrance conductors entering or on the exterior of buildings or other structures shall be insulated in accordance with Section E3406.5.

    Exceptions:

    1. A copper grounded conductor shall not be required to be insulated where it is:

    1.1. In a raceway or part of a service cable assembly,

    1.2. Directly buried in soil of suitable condition, or

    1.3. Part of a cable assembly listed for direct burial without regard to soil conditions.

    2. An aluminum or copper-clad aluminum grounded conductor shall not be required to be insulated where part of a cable or where identified for direct burial or utilization in underground raceways.

    E3605.2 Wiring methods for services.
    Service-entrance wiring methods shall be installed in accordance with the applicable requirements in Chapter 38.

    E3605.3 Spliced conductors.
    Service-entrance conductors shall be permitted to be spliced or tapped. Splices shall be made in enclosures or, if directly buried, with listed underground splice kits. Conductor splices shall be made in accordance with Chapters 34, 37, 38 and 39.

    E3605.4 Protection of underground service entrance conductors.
    Underground service-entrance conductors shall be protected against physical damage in accordance with Chapter 38.

    E3605.5 Protection of all other service cables.
    Above-ground service-entrance cables, where subject to physical damage, shall be protected by one or more of the following: rigid metal conduit, intermediate metal conduit, Schedule 80 PVC conduit, electrical metallic tubing or other approved means.

    E3605.6 Locations exposed to direct sunlight.
    Insulated conductors and cables used where exposed to direct rays of the sun shall comply with one of the following:

    1. The conductors and cables shall be listed, or listed and marked, as being sunlight resistant.

    2. The conductors and cables are covered with insulating material, such as tape or sleeving, that is listed, or listed and marked, as being sunlight resistant.

    E3605.7 Mounting supports.
    Service-entrance cables shall be supported by straps or other approved means within 12 inches (305 mm) of every service head, gooseneck or connection to a raceway or enclosure and at intervals not exceeding 30 inches (762 mm).

    E3605.8 Raceways to drain.
    Where exposed to the weather, raceways enclosing service-entrance conductors shall be suitable for use in wet locations and arranged to drain. Where embedded in masonry, raceways shall be arranged to drain.

    E3605.9 Overhead service locations.
    Connections at service heads shall be in accordance with Sections E3605.9.1 through E3605.9.7.

    E3605.9.1 Rain-tight service head.
    Service raceways shall be equipped with a service head at the point of connection to service-drop or overhead conductors. The service head shall be listed for use in wet locations.

    E3605.9.2 Service cable, service head or gooseneck.
    Service-entrance cable shall be equipped with a service head or shall be formed into a gooseneck in an approved manner. The service head shall be listed for use in wet locations.

    E3605.9.3 Service-head location.
    Service heads, and goosenecks in service-entrance cables, shall be located above the point of attachment of the service-drop or overhead service conductors to the building or other structure.

    Exception: Where it is impracticable to locate the service head or gooseneck above the point of attachment, the service head or gooseneck location shall be not more than 24 inches (610 mm) from the point of attachment.

    E3605.9.4 Separately bushed openings.
    Service heads shall have conductors of different potential brought out through separately bushed openings.

    E3605.9.5 Drip loops.
    Drip loops shall be formed on individual conductors. To prevent the entrance of moisture, service-entrance conductors shall be connected to the service-drop or overhead conductors either below the level of the service head or below the level of the termination of the service-entrance cable sheath.

    E3605.9.6 Conductor arrangement.
    Service-entrance and overhead service conductors shall be arranged so that water will not enter service raceways or equipment.

    E3605.9.7 Secured.
    Service-entrance cables shall be held securely in place.

    SECTION E3606
    SERVICE EQUIPMENT—GENERAL

    E3606.1 Service equipment enclosures.
    Energized parts of service equipment shall be enclosed.

    E3606.2 Working space.
    In no case shall the working space in the vicinity of service equipment be less than that specified in Chapter 34.

    E3606.3 Available short-circuit current.
    Service equipment shall be suitable for the maximum fault current available at its supply terminals, but not less than 10,000 amperes.

    E3606.4 Marking.
    Service equipment shall be marked to identify it as being suitable for use as service equipment. Service equipment shall be listed. Individual meter socket enclosures shall not be considered as service equipment.

    SECTION E3607
    SYSTEM GROUNDING

    E3607.1 System service ground.
    The premises wiring system shall be grounded at the service with a grounding electrode conductor connected to a grounding electrode system as required by this code. Grounding electrode conductors shall be sized in accordance with Table E3603.1.

    E3607.2 Location of grounding electrode conductor connection.
    The grounding electrode conductor shall be connected to the grounded service conductor at any accessible point from the load end of the service drop or service lateral to and including the terminal or bus to which the grounded service conductor is connected at the service disconnecting means. A grounding connection shall not be made to any grounded circuit conductor on the load side of the service disconnecting means, except as provided in Section E3607.3.2.

    E3607.3 Buildings or structures supplied by feeder(s) or branch circuit(s).
    Buildings or structures supplied by feeder(s) or branch circuit(s) shall have a grounding electrode or grounding electrode system installed in accordance with Section E3608. The grounding electrode conductor(s) shall be connected in a manner specified in Section E3607.3.1 or, for existing premises wiring systems only, Section E3607.3.2. Where there is no existing grounding electrode, the grounding electrode(s) required in Section E3608 shall be installed.

    Exception: A grounding electrode shall not be required where only one branch circuit, including a multiwire branch circuit, supplies the building or structure and the branch circuit includes an equipment grounding conductor for grounding the noncurrent-carrying parts of all equipment. For the purposes of this section, a multiwire branch circuit shall be considered as a single branch circuit.

    E3607.3.1 Equipment grounding conductor.
    An equipment grounding conductor as described in Section E3908 shall be run with the supply conductors and connected to the building or structure disconnecting means and to the grounding electrode(s). The equipment grounding conductor shall be used for grounding or bonding of equipment, structures or frames required to be grounded or bonded. The equipment grounding conductor shall be sized in accordance with Section E3908.12. Any installed grounded conductor shall not be connected to the equipment grounding conductor or to the grounding electrode(s).

    E3607.3.2 Grounded conductor, existing premises.
    For installations made in compliance with previous editions of this code that permitted such connection and where an equipment grounding conductor is not run with the supply conductors to the building or structure, there are no continuous metallic paths bonded to the grounding system in both buildings or structures involved, and ground-fault protection of equipment has not been installed on the supply side of the feeder(s), the grounded conductor run with the supply to the buildings or structure shall be connected to the building or structure disconnecting means and to the grounding electrode(s) and shall be used for grounding or bonding of equipment, structures, or frames required to be grounded or bonded. Where used for grounding in accordance with this provision, the grounded conductor shall be not smaller than the larger of:

    1. That required by Section E3704.3.

    2. That required by Section E3908.12.

    E3607.4 Grounding electrode conductor.
    A grounding electrode conductor shall be used to connect the equipment grounding conductors, the service equipment enclosures, and the grounded service conductor to the grounding electrode(s). This conductor shall be sized in accordance with Table E3603.1.

    E3607.5 Main bonding jumper.
    An unspliced main bonding jumper shall be used to connect the equipment grounding conductor(s) and the service-disconnect enclosure to the grounded conductor of the system within the enclosure for each service disconnect.

    E3607.6 Common grounding electrode.
    Where an ac system is connected to a grounding electrode in or at a building or structure, the same electrode shall be used to ground conductor enclosures and equipment in or on that building or structure. Where separate services, feeders or branch circuits supply a building and are required to be connected to a grounding electrode(s), the same grounding electrode(s) shall be used. Two or more grounding electrodes that are effectively bonded together shall be considered as a single grounding electrode system.

    SECTION E3608
    GROUNDING ELECTRODE SYSTEM

    E3608.1 Grounding electrode system.
    All electrodes specified in Sections E3608.1.1, E3608.1.2, E3608.1.3, E3608.1.4 E3608.1.5 and E3608.1.6 that are present at each building or structure served shall be bonded together to form the grounding electrode system. Where none of these electrodes are present, one or more of the electrodes specified in Sections E3608.1.3, E3608.1.4, E3608.1.5 and E3608.1.6 shall be installed and used.

    Exception: Concrete-encased electrodes of existing buildings or structures shall not be required to be part of the grounding electrode system where the steel reinforcing bars or rods are not accessible for use without disturbing the concrete.

    E3608.1.1 Metal underground water pipe.
    A metal underground water pipe that is in direct contact with the earth for 10 feet (3048 mm) or more, including any well casing effectively bonded to the pipe and that is electrically continuous, or made electrically continuous by bonding around insulating joints or insulating pipe to the points of connection of the grounding electrode conductor and the bonding conductors, shall be considered as a grounding electrode (see Section E3608.1). Interior metal water piping located more than 5 feet (1524 mm) from the entrance to the building shall not be used as part of the grounding electrode system or as a conductor to interconnect electrodes that are part of the grounding electrode system.

    E3608.1.1.1 Interior metal water piping.
    Interior metal water piping located more than 5 feet (1524 mm) from the entrance to the building shall not be used as a conductor to interconnect electrodes that are part of the grounding electrode system.

    E3608.1.1.2 Installation.
    Continuity of the grounding path or the bonding connection to interior piping shall not rely on water meters, filtering devices and similar equipment. A metal underground water pipe shall be supplemented by an additional electrode of a type specified in Sections E3608.1.2 through E3608.1.6. The supplemental electrode shall be bonded to the grounding electrode conductor, the grounded service-entrance conductor, a nonflexible grounded service raceway, any grounded service enclosure or to the equipment grounding conductor provided in accordance with Section E3607.3.1. Where the supplemental electrode is a rod, pipe or plate electrode in accordance with Section E3608.1.4 or E3608.1.5, it shall comply with Section E3608.4.

    Where the supplemental electrode is a rod, pipe or plate electrode in accordance with Section E3608.1.4 or E3608.1.5, that portion of the bonding jumper that is the sole connection to the supplemental grounding electrode shall not be required to be larger than 6 AWG copper or 4 AWG aluminum wire.

    E3608.1.2 Concrete-encased electrode.
    A concrete-encased electrode consisting of at least 20 feet (6096 mm) of either of the following shall be considered as a grounding electrode:

    1. One or more bare or zinc galvanized or other electrically conductive coated steel reinforcing bars or rods not less than 1/2 inch (13 mm) in diameter, installed in one continuous 20-foot (6096 mm) length, or if in multiple pieces connected together by the usual steel tie wires, exothermic welding, welding, or other effective means to create a 20-foot (6096 mm) or greater length.

    2. A bare copper conductor not smaller than 4 AWG.

    Metallic components shall be encased by at least 2 inches (51 mm) of concrete and shall be located horizontally within that portion of a concrete foundation or footing that is in direct contact with the earth or within vertical foundations or structural components or members that are in direct contact with the earth.

    Where multiple concrete-encased electrodes are present at a building or structure, only one shall be required to be bonded into the grounding electrode system.

    E3608.1.3 Ground rings.
    A ground ring encircling the building or structure, in direct contact with the earth at a depth below the earth’s surface of not less than 30 inches (762 mm), consisting of at least 20 feet (6096 mm) of bare copper conductor not smaller than 2 AWG shall be considered as a grounding electrode.

    E3608.1.4 Rod and pipe electrodes.
    Rod and pipe electrodes not less than 8 feet (2438 mm) in length and consisting of the following materials shall be considered as a grounding electrode:

    1. Grounding electrodes of pipe or conduit shall not be smaller than trade size 3/4 (metric designator 21) and, where of iron or steel, shall have the outer surface galvanized or otherwise metal-coated for corrosion protection.

    2. Rod-type grounding electrodes of stainless steel and copper or zinc-coated steel shall be at least 5/8 inch (15.9 mm) in diameter unless listed.

    E3608.1.4.1 Installation.
    The rod and pipe electrodes shall be installed such that at least 8 feet (2438 mm) of length is in contact with the soil. They shall be driven to a depth of not less than 8 feet (2438 mm) except that, where rock bottom is encountered, electrodes shall be driven at an oblique angle not to exceed 45 degrees (0.79 rad) from the vertical or shall be buried in a trench that is at least 30 inches (762 mm) deep. The upper end of the electrodes shall be flush with or below ground level except where the aboveground end and the grounding electrode conductor attachment are protected against physical damage.

    E3608.1.5 Plate electrodes.
    A plate electrode that exposes not less than 2 square feet (0.186 m2) of surface to exterior soil shall be considered as a grounding electrode. Electrodes of bare or conductively coated iron or steel plates shall be at least 1/4 inch (6.4 mm) in thickness. Solid, uncoated electrodes of nonferrous metal shall be at least 0.06 inch (1.5 mm) in thickness. Plate electrodes shall be installed not less than 30 inches (762 mm) below the surface of the earth.

    E3608.1.6 Other electrodes.
    In addition to the grounding electrodes specified in Sections E3608.1.1 through E3608.1.5, other listed grounding electrodes shall be permitted.

    E3608.2 Bonding jumper.
    The bonding jumper(s) used to connect the grounding electrodes together to form the grounding electrode system shall be installed in accordance with Sections E3610.2, and E3610.3, shall be sized in accordance with Section E3603.4, and shall be connected in the manner specified in Section E3611.1.

    E3608.3 Rod, pipe and plate electrode requirements.
    Where practicable, rod, pipe and plate electrodes shall be embedded below permanent moisture level. Such electrodes shall be free from nonconductive coatings such as paint or enamel. Where more than one such electrode is used, each electrode of one grounding system shall be not less than 6 feet (1829 mm) from any other electrode of another grounding system. Two or more grounding electrodes that are effectively bonded together shall be considered as a single grounding electrode system. That portion of a bonding jumper that is the sole connection to a rod, pipe or plate electrode shall not be required to be larger than 6 AWG copper or 4 AWG aluminum wire.

    E3608.4 Supplemental electrode required.
    A single rod, pipe, or plate electrode shall be supplemented by an additional electrode of a type specified in Sections E3608.1.2 through E3608.1.6. The supplemental electrode shall be bonded to one of the following:

    1. A rod, pipe, or plate electrode.

    2. A grounding electrode conductor.

    3. A grounded service-entrance conductor.

    4. A nonflexible grounded service raceway.

    5. A grounded service enclosure.

    Where multiple rod, pipe, or plate electrodes are installed to meet the requirements of this section, they shall not be less than 6 feet (1829 mm) apart.

    Exception: Where a single rod, pipe, or plate grounding electrode has a resistance to earth of 25 ohms or less, the supplemental electrode shall not be required.

    E3608.5 Aluminum electrodes.
    Aluminum electrodes shall not be permitted.

    E3608.6 Metal underground gas piping system.
    A metal underground gas piping system shall not be used as a grounding electrode.

    SECTION E3609
    BONDING

    E3609.1 General.
    Bonding shall be provided where necessary to ensure electrical continuity and the capacity to conduct safely any fault current likely to be imposed.

    E3609.2 Bonding of equipment for services.
    The noncurrent-carrying metal parts of the following equipment shall be effectively bonded together:

    1. Raceways or service cable armor or sheath that enclose, contain, or support service conductors.

    2. Service enclosures containing service conductors, including meter fittings, and boxes, interposed in the service raceway or armor.

    E3609.3 Bonding for other systems.
    An intersystem bonding termination for connecting intersystem bonding conductors required for other systems shall be provided external to enclosures at the service equipment or metering equipment enclosure and at the disconnecting means for any additional buildings or structures. The intersystem bonding termination shall comply with all of the following:

    1. It shall be accessible for connection and inspection.

    2. It shall consist of a set of terminals with the capacity for connection of not less than three intersystem bonding conductors.

    3. It shall not interfere with opening of the enclosure for a service, building or structure disconnecting means, or metering equipment.

    4. Where located at the service equipment, it shall be securely mounted and electrically connected to an enclosure for the service equipment, to the meter enclosure, or to an exposed nonflexible metallic service raceway, or shall be mounted at one of these enclosures and connected to the enclosure or to the grounding electrode conductor with a 6 AWG or larger copper conductor.

    5. Where located at the disconnecting means for a building or structure, it shall be securely mounted and electrically connected to the metallic enclosure for the building or structure disconnecting means, or shall be mounted at the disconnecting means and connected to the metallic enclosure or to the grounding electrode conductor with a 6 AWG or larger copper conductor.

    6. It shall be listed as grounding and bonding equipment.

    E3609.4 Method of bonding at the service.
    Bonding jumpers meeting the requirements of this chapter shall be used around impaired connections, such as reducing washers or oversized, concentric, or eccentric knockouts. Standard locknuts or bushings shall not be the only means for the bonding required by this section but shall be permitted to be installed to make mechanical connections of raceways. Electrical continuity at service equipment, service raceways and service conductor enclosures shall be ensured by one or more of the methods specified in Sections E3609.4.1 through E3609.4.4.

    E3609.4.1 Grounded service conductor.
    Equipment shall be bonded to the grounded service conductor in a manner provided in this code.

    E3609.4.2 Threaded connections.
    Equipment shall be bonded by connections using threaded couplings or threaded hubs on enclosures. Such connections shall be made wrench tight.

    E3609.4.3 Threadless couplings and connectors.
    Equipment shall be bonded by threadless couplings and connectors for metal raceways and metal-clad cables. Such couplings and connectors shall be made wrench tight. Standard locknuts or bushings shall not be used for the bonding required by this section.

    E3609.4.4 Other devices.
    Equipment shall be bonded by other listed devices, such as bonding-type locknuts, bushings and bushings with bonding jumpers.

    E3609.5 Sizing supply-side bonding jumper and main bonding jumper.
    The bonding jumper shall not be smaller than the sizes shown in Table E3603.1 for grounding electrode conductors. Where the service-entrance conductors are paralleled in two or more raceways or cables, and an individual supply-side bonding jumper is used for bonding these raceways or cables, the supply-side bonding jumper for each raceway or cable shall be selected from Table E3603.1 based on the size of the ungrounded supply conductors in each raceway or cable. A single supply-side bonding jumper installed for bonding two or more raceways or cables shall be sized in accordance with Table E3603.1 based on the largest set of parallel ungrounded supply conductors.

    E3609.6 Metal water piping bonding.
    The metal water piping system shall be bonded to the service equipment enclosure, the grounded conductor at the service, the grounding electrode conductor where of sufficient size, or to the one or more grounding electrodes used. The bonding jumper shall be sized in accordance with Table E3603.1. The points of attachment of the bonding jumper(s) shall be accessible.

    E3609.7 Bonding other metal piping.
    Where installed in or attached to a building or structure, metal piping systems, including gas piping, capable of becoming energized shall be bonded to the service equipment enclosure, the grounded conductor at the service, the grounding electrode conductor where of sufficient size, or to the one or more grounding electrodes used. The bonding conductor(s) or jumper(s) shall be sized in accordance with Table E3908.12 using the rating of the circuit capable of energizing the piping. The equipment grounding conductor for the circuit that is capable of energizing the piping shall be permitted to serve as the bonding means. The points of attachment of the bonding jumper(s) shall be accessible.

    SECTION E3610
    GROUNDING ELECTRODE CONDUCTORS

    E3610.1 Continuous.
    The grounding electrode conductor shall be installed in one continuous length without splices or joints and shall run to any convenient grounding electrode available in the grounding electrode system where the other electrode(s), if any, are connected by bonding jumpers in accordance with Section E3608.2, or to one or more grounding electrode(s) individually. The grounding electrode conductor shall be sized for the largest grounding electrode conductor required among all of the electrodes connected to it.

    Exception: Splicing of the grounding electrode conductor by irreversible compression-type connectors listed as grounding and bonding equipment or by the exothermic welding process shall not be prohibited.

    E3610.2 Securing and protection against physical damage.
    Where exposed, a grounding electrode conductor or its enclosure shall be securely fastened to the surface on which it is carried. Grounding electrode conductors shall be permitted to be installed on or through framing members. A 4 AWG or larger conductor shall be protected where exposed to physical damage. A 6 AWG grounding conductor that is free from exposure to physical damage shall be permitted to be run along the surface of the building construction without metal covering or protection where it is and securely fastened to the construction; otherwise, it shall be in rigid metal conduit, intermediate metal conduit, rigid polyvinyl chloride (PVC), nonmetallic conduit, reinforced thermosetting resin (RTRC) nonmetallic conduit, electrical metallic tubing or cable armor. Grounding electrode conductors smaller than 6 AWG shall be in rigid metal conduit, intermediate metal conduit, rigid polyvinyl chloride (PVC) nonmetallic conduit, reinforced thermoseting resin (RTRC) nonmetallic conduit, electrical metallic tubing or cable armor.

    Bare aluminum or copper-clad aluminum grounding electrode conductors shall not be used where in direct contact with masonry or the earth or where subject to corrosive conditions. Where used outside, aluminum or copper-clad aluminum grounding electrode conductors shall not be installed within 18 inches (457 mm) of the earth.

    E3610.3 Enclosures for grounding electrode conductors.
    Ferrous metal enclosures for grounding electrode conductors shall be electrically continuous from the point of attachment to cabinets or equipment to the grounding electrode, and shall be securely fastened to the ground clamp or fitting. Nonferrous metal enclosures shall not be required to be electrically continuous. Ferrous metal enclosures that are not physically continuous from cabinet or equipment to the grounding electrode shall be made electrically continuous by bonding each end to the grounding electrode conductor. Bonding methods in compliance with Section E3609.4 for installations at service equipment locations and with E3609.4.2 (B)(2) through E3609.4.4 for other than service equipment locations shall apply at each end and to all intervening ferrous raceways, boxes, and enclosures between the cabinets or equipment and the grounding electrode. The bonding jumper for a grounding electrode conductor raceway shall be the same size or larger than the required enclosed grounding electrode conductor.

    Where a raceway is used as protection for a grounding conductor, the installation shall comply with the requirements of Chapter 38.

    E3610.4 Prohibited use.
    An equipment grounding conductor shall not be used as a grounding electrode conductor.

    SECTION E3611
    GROUNDING ELECTRODE CONDUCTOR
    CONNECTION TO THE GROUNDING ELECTRODES

    E3611.1 Methods of grounding conductor connection to electrodes.
    The grounding or bonding conductor shall be connected to the grounding electrode by exothermic welding, listed lugs, listed pressure connectors, listed clamps or other listed means. Connections depending on solder shall not be used. Ground clamps shall be listed for the materials of the grounding electrode and the grounding electrode conductor and, where used on pipe, rod or other buried electrodes, shall also be listed for direct soil burial or concrete encasement. Not more than one conductor shall be connected to the grounding electrode by a single clamp or fitting unless the clamp or fitting is listed for multiple conductors. One of the methods indicated in the following items shall be used:

    1. A pipe fitting, pipe plug or other approved device screwed into a pipe or pipe fitting.

    2. A listed bolted clamp of cast bronze or brass, or plain or malleable iron.

    3. For indoor communications purposes only, a listed sheet metal strap-type ground clamp having a rigid metal base that seats on the electrode and having a strap of such material and dimensions that it is not likely to stretch during or after installation.

    4. Other equally substantial approved means.

    E3611.2 Accessibility.
    All mechanical elements used to terminate a grounding electrode conductor or bonding jumper to the grounding electrodes that are not buried or concrete encased shall be accessible.

    E3611.3 Effective grounding path.
    The connection of the grounding electrode conductor or bonding jumper shall be made in a manner that will ensure a permanent and effective grounding path. Where necessary to ensure effective grounding for a metal piping system used as a grounding electrode, effective bonding shall be provided around insulated joints and sections and around any equipment that is likely to be disconnected for repairs or replacement. Bonding jumpers shall be of sufficient length to permit removal of such equipment while retaining the integrity of the grounding path.

    E3611.4 Interior metal water piping.
    Where grounding electrode conductors and bonding jumpers are connected to interior metal water piping as a means to extend the grounding electrode conductor connection to an electrode(s), such piping shall be located not more than 5 feet (1524 mm) from the point of entry into the building.

    Where interior metal water piping is used as a conductor to interconnect electrodes that are part of the grounding electrode system, such piping shall be located not more than 5 feet (1524 mm) from the point of entry into the building.

    E3611.5 Protection of ground clamps and fittings.
    Ground clamps or other fittings shall be approved for applications without protection or shall be protected from physical damage by installing them where they are not likely to be damaged or by enclosing them in metal, wood or equivalent protective coverings.

    E3611.6 Clean surfaces.
    Nonconductive coatings (such as paint, enamel and lacquer) on equipment to be grounded shall be removed from threads and other contact surfaces to ensure good electrical continuity or shall be connected by fittings that make such removal unnecessary.