• APPENDIXK
    SOUND TRANSMISSION 

    (The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.)

    SECTIONAK101
    GENERAL

    AK101.1 General.

    Wall and floor-ceiling assemblies separating dwelling units, including those separating adjacent townhouse units, shall provide air-borne sound insulation for walls, and both air-borne and impact sound insulation for floor-ceiling assemblies.

    SECTIONAK102
    AIR-BORNE SOUND 

    AK102.1 General.

    Air-borne sound insulation for wall and floor-ceiling assemblies shall meet a sound transmission class (STC) rating of 45 when tested in accordance with ASTM E 90. Penetrations or openings in construction assemblies for piping; electrical devices; recessed cabinets; bathtubs; soffits; or heating, ventilating or exhaust ducts shall be sealed, lined, insulated or otherwise treated to maintain the required ratings. Dwelling unit entrance doors, which share a common space, shall be tight fitting to the frame and sill.

    AK102.1.1 Masonry.

    The sound transmission class of concrete masonry and clay masonry assemblies shall be calculated in accordance with TMS 0302 or determined through testing in accordance with ASTM E 90.

    SECTIONAK103
    STRUCTURAL-BORNE SOUND 

    AK103.1 General.

    Floor/ceiling assemblies between dwelling units, or between a dwelling unit and a public or service area within a structure, shall have an impact insulation class (IIC) rating of not less than 45 when tested in accordance with ASTM E 492.

    SECTIONAK104
    REFERENCED STANDARDS

    ASTM

    The Masonry Society

    TMS 0302—12

    Standard for Determining the Sound Transmission Class Rating for Masonry Walls

    AK102.1.1