• CHAPTER17
    COMBUSTION AIR

    User note: Code change proposals to this chapter will be considered by the IRC – Plumbing and Mechanical Code
    Development Committee during the 2015 (Group A) Code Development Cycle. See explanation on page iv.

    SECTIONM1701
    GENERAL

    M1701.1 Scope.

    Solid fuel-burning appliances shall be provided with combustion air in accordance with the appliance manufacturer’s installation instructions. Oil-fired appliances shall be provided with combustion air in accordance with NFPA 31. The methods of providing combustion air in this chapter do not apply to fireplaces, fireplace stoves and direct-vent appliances. The requirements for combustion and dilution air for gas-fired appliances shall be in accordance with Chapter 24.

    M1701.2 Opening location.

    In flood hazard areas as established in Table R301.2(1), combustion air openings shall be located at or above the elevation required in Section R322.2.1 or R322.3.2.