• CHAPTER29
    WATER SUPPLY AND DISTRIBUTION 

    User note: Code change proposals to this chapter will be considered by the IRC – Plumbing and Mechanical Code
    Development Committee during the 2015 (Group A) Code Development Cycle. See explanation on page iv.

    SECTIONP2901
    GENERAL 

    P2901.1 Potable water required.

    Potable water shall be supplied to plumbing fixtures and plumbing appliances except where treated rainwater, treated gray water or municipal reclaimed water is supplied to water closets, urinals and trap primers. The requirements of this section shall not be construed to require signage for water closets and urinals.

    P2901.2 Identification of nonpotable water systems.

    Where nonpotable water systems are installed, the piping conveying the nonpotable water shall be identified either by color marking, metal tags or tape in accordance with Sections P2901.2.1 through P2901.2.2.3.

    P2901.2.1 Signage required.

    Nonpotable water outlets such as hose connections, open-ended pipes and faucets shall be identified with signage that reads as follows: “Nonpotable water is utilized for [application name]. CAUTION: NONPOTABLE WATER. DO NOT DRINK.” The words shall be legibly and indelibly printed on a tag or sign constructed of corrosion-resistant water-proof material or shall be indelibly printed on the fixture. The letters of the words shall be not less than 0.5 inches (12.7 mm) in height and in colors in contrast to the background on which they are applied. In addition to the required wordage, the pictograph shown in Figure P2901.2.1 shall appear on the required signage.

    FIGURE P2901.2.1 PICTOGRAPH—DO NOT DRINK

    FIGURE P2901.2.1

    PICTOGRAPH—DO NOT DRINK

    P2901.2.2 Distribution pipe labeling and marking.

    Nonpotable distribution piping shall be purple in color and shall be embossed or integrally stamped or marked with the words: “CAUTION: NONPOTABLE WATER— DO NOT DRINK” or the piping shall be installed with a purple identification tape or wrap. Pipe identification shall include the contents of the piping system and an arrow indicating the direction of flow. Hazardous piping systems shall contain information addressing the nature of the hazard. Pipe identification shall be repeated at intervals not exceeding 25 feet (7620 mm) and at each point where the piping passes through a wall, floor or roof. Lettering shall be readily observable within the room or space where the piping is located.

    P2901.2.2.1Color.

    The color of the pipe identification shall be discernable and consistent throughout the building. The color purple shall be used to identify reclaimed, rain and gray water distribution systems.

    P2901.2.2.2Lettering size.

    The size of the background color field and lettering shall comply with Table P2901.2.2.2.

    TABLE P2901.2.2.2

    SIZE OF PIPE IDENTIFICATION

    PIPE DIAMETER (inches)LENGTH OF BACKGROUND COLOR FIELD (inches)SIZE OF LETTERS (inches)
    3/4 to 11/480.5
    11/2 to 280.75
    21/2 to 6121.25
    8 to 1022.5
    over 10323.5

    For SI: 1 inch = 25.4 mm.

    P2901.2.2.3Identification Tape.

    Where used, identification tape shall be not less than 3 inches (76 mm) wide and have white or black lettering on a purple field stating “CAUTION: NONPOTABLE WATER—DO NOT DRINK.” Identification tape shall be installed on top of nonpotable rainwater distribution pipes and fastened not greater than every 10 feet (3048 mm) to each pipe length, and run continuously the entire length of the pipe.

    SECTIONP2902
    PROTECTION OF POTABLE WATER SUPPLY 

    P2902.1 General.

    A potable water supply system shall be designed and installed as to prevent contamination from nonpotable liquids, solids or gases being introduced into the potable water supply. Connections shall not be made to a potable water supply in a manner that could contaminate the water supply or provide a cross-connection between the supply and a source of contamination except where approved backflow prevention assemblies, backflow prevention devices or other means or methods are installed to protect the potable water supply. Cross-connections between an individual water supply and a potable public water supply shall be prohibited.

    P2902.2 Plumbing fixtures.

    The supply lines and fittings for every plumbing fixture shall be installed so as to prevent backflow. Plumbing fixture fittings shall provide backflow protection in accordance with ASME A112.18.1/CSA B125.1.

    P2902.3 Backflow protection.

    A means of protection against backflow shall be provided in accordance with Sections P2902.3.1 through P2902.3.6. Backflow prevention applications shall conform to Table P2902.3, except as specifically stated in Sections P2902.4 through P2902.5.5.

    TABLE P2902.3

    APPLICATION FOR BACKFLOW PREVENTERS

    DEVICEDEGREE OF HAZARDaAPPLICATIONbAPPLICABLE STANDARDS
    Backflow Prevention Assemblies
    Double check backflow prevention assembly and double check fire protection backflow prevention assemblyLow hazardBackpressure or backsiphonage Sizes 3/8″ – 16″ASSE 1015, AWWA C510,CSA B64.5, CSA B64.5.1
    Double check detector fire protection backflow prevention assembliesLow hazardBackpressure or backsiphonage Sizes 2″ – 16″ASSE 1048
    Pressure vacuum breaker assemblyHigh or low hazardBacksiphonage only Sizes 1/2″ – 2″ASSE 1020, CSA B64.1.2
    Reduced pressure principle backflow prevention assembly and reduced pressure principle fire protection backflow prevention assemblyHigh or low hazardBackpressure or backsiphonage Sizes 3/8″ – 16″ASSE 1013, AWWA C511,CSA B64.4, CSA B64.4.1
    Reduced pressure detector fire protection backflow prevention assembliesHigh or low hazardBacksiphonage or backpressure (Fire sprinkler systems)ASSE 1047
    Spill-resistant vacuum breakerHigh or low hazardBacksiphonage only Sizes 1/4″ – 2″ASSE 1056, CSA B64.1.3
    Backflow Preventer Plumbing Devices
    Antisiphon-type fill valves for gravity water closet flush tanksHigh hazardBacksiphonage onlyASSE 1002, CSA B125.3
    Backflow preventer with intermediate atmospheric ventsLow hazardBackpressure or backsiphonage Sizes 1/4″ – 3/8ASSE 1012, CSA B64.3
    Dual-check-valve-type backflow preventersLow hazardBackpressure or backsiphonage Sizes 1/4″ – 1″ASSE 1024, CSA B64.6
    Hose-connection backflow preventerHigh or low hazardLow head backpressure, rated working pressure backpressure or backsiphonage Sizes 1/2″ – 1″ASSE 1052, CSA B64.2.1.1
    Hose-connection vacuum breakerHigh or low hazardLow head backpressure or backsiphonage Sizes 1/2″, 3/4″, 1″ASSE 1011, CSA B64.2,B64.2.1
    Laboratory faucet backflow preventerHigh or low hazardLow head backpressure and backsiphonageASSE 1035, CSA B64.7
    Pipe-applied atmospheric-type vacuum breakerHigh or low hazardBacksiphonage only Sizes 1/4 – 4″ASSE 1001, CSA B64.1.1
    Vacuum breaker wall hydrants, frost-resistant, automatic-draining typeHigh or low hazardLow head backpressure or backsi-phonage Sizes 3/4″ – 1″ASSE 1019, CSA B64.2.2
    Other Means Or Methods
    Air gapHigh or low hazardBacksiphonage onlyASME A112.1.2
    Air gap fittings for use with plumbing fixtures, appliances and appurtenancesHigh or low hazardBacksiphonage or backpressureASME A112.1.3

    For SI: 1 inch = 25.4 mm.

    1. a.Low hazard—See Pollution (Section R202). High hazard—See Contamination (Section R202).

    2. b.See Backpressure (Section R202). See Backpressure, Low Head (Section R202). See Backsiphonage (Section R202).

    P2902.3.1 Air gaps.

    Air gaps shall comply with ASME A112.1.2 and air gap fittings shall comply with ASME A112.1.3. An air gap shall be measured vertically from the lowest end of a water outlet to the flood level rim of the fixture or receptor into which the water outlets discharges to the floor. The required air gap shall be not less than twice the diameter of the effective opening of the outlet and not less than the values specified in Table P2902.3.1.

    TABLE P2902.3.1

    MINIMUM AIR GAPS

    FIXTUREMINIMUM AIR GAP
    Away from a walla (inches)Close to a wall (inches)
    Effective openings greater than 1 inchTwo times the diameter of the effective openingThree times the diameter of the effective opening
    Lavatories and other fixtures with effective opening not greater than 1/2 inch in diameter11.5
    Over-rim bath fillers and other fixtures with effective openings not greater than 1 inch in diameter23
    Sink, laundry trays, gooseneck back faucets and other fixtures with effective openings not greater than 3/4 inch in diameter1.52.5

    For SI: 1 inch = 25.4 mm.

    1. a.Applicable where walls or obstructions are spaced from the nearest inside edge of the spout opening a distance greater than three times the diameter of the effective opening for a single wall, or a distance greater than four times the diameter of the effective opening for two intersecting walls.

    P2902.3.2 Atmospheric-type vacuum breakers.

    Atmospheric-type vacuum breakers shall conform to ASSE 1001 or CSA B64.1.1. Hose-connection vacuum breakers shall conform to ASSE 1011, ASSE 1019, ASSE 1035, ASSE 1052, CSA B64.2, CSA B64.2.1, CSA B64.2.1.1, CSA B64.2.2 or CSA B64.7. Both types of vacuum breakers shall be installed with the outlet continuously open to the atmosphere. The critical level of the atmospheric vacuum breaker shall be set at not less than 6 inches (152 mm) above the highest elevation of downstream piping and the flood level rim of the fixture or device.

    P2902.3.3 Backflow preventer with intermediate atmospheric vent.

    Backflow preventers with intermediate atmospheric vents shall conform to ASSE 1012 or CSA B64.3. These devices shall be permitted to be installed where subject to continuous pressure conditions. These devices shall be prohibited as a means of protection where any hazardous chemical additives are introduced downstream of the device. The relief opening shall discharge by air gap and shall be prevented from being submerged.

    P2902.3.4 Pressure vacuum breaker assemblies.

    Pressure vacuum breaker assemblies shall conform to ASSE 1020 or CSA B64.1.2. Spill-resistant vacuum breaker assemblies shall comply with ASSE 1056. These assemblies are designed for installation under continuous pressure conditions where the critical level is installed at the required height. The critical level of a pressure vacuum breaker and a spill-resistant vacuum breaker assembly shall be set at not less than 12 inches (304 mm) above the highest elevation of downstream piping and the flood level rim of the fixture or device. Pressure vacuum breaker assemblies shall not be installed in locations where spillage could cause damage to the structure.

    P2902.3.5 Reduced pressure principle backflow prevention assemblies.

    Reduced pressure principle backflow prevention assemblies and reduced pressure principle fire protection backflow prevention assemblies shall conform to ASSE 1013, AWWA C511, CSA B64.4 or CSA B64.4.1. Reduced pressure detector fire protection backflow prevention assemblies shall conform to ASSE 1047. These devices shall be permitted to be installed where subject to continuous pressure conditions. The relief opening shall discharge by air gap and shall be prevented from being submerged.

    P2902.3.6 Double check backflow prevention assemblies.

    Double check backflow prevention assemblies shall conform to ASSE 1015, CSA B64.5, CSA B64.5.1 or AWWA C510. Double check detector fire protection backflow prevention assemblies shall conform to ASSE 1048. These assemblies shall be capable of operating under continuous pressure conditions.

    P2902.3.7 Dual check backflow preventer.

    Dual check backflow preventers shall conform with ASSE 1024 or CSA B64.6.

    P2902.4 Protection of potable water outlets.

    Potable water openings and outlets shall be protected by an air gap, a reduced pressure principle backflow prevention assembly, an atmospheric vent, an atmospheric-type vacuum breaker, a pressure-type vacuum breaker assembly or a hose connection backflow preventer.

    P2902.4.1 Fill valves.

    Flush tanks shall be equipped with an antisiphon fill valve conforming to ASSE 1002 or CSA B125.3. The critical level of the fill valve shall be located not less than 1 inch (25 mm) above the top of the flush tank overflow pipe.

    P2902.4.2 Deck-mounted and integral vacuum breakers.

    Approved deck-mounted or equipment-mounted vacuum breakers and faucets with integral atmospheric vacuum breakers or spill–resistant vacuum breaker assemblies shall be installed in accordance with the manufacturer’s instructions and the requirements for labeling. The critical level of the breakers and assemblies shall be located at not less than 1 inch (25 mm) above the flood level rim.

    P2902.4.3 Hose connection.

    Sillcocks, hose bibbs, wall hydrants and other openings with a hose connection shall be protected by an atmospheric-type or pressure-type vacuum breaker, a pressure vacuum breaker assembly or a permanently attached hose connection vacuum breaker.

    Exceptions:

    1. 1.This section shall not apply to water heater and boiler drain valves that are provided with hose connection threads and that are intended only for tank or vessel draining.

    2. 2.This section shall not apply to water supply valves intended for connection of clothes washing machines where backflow prevention is otherwise provided or is integral with the machine.

    P2902.5 Protection of potable water connections.

    Connections to the potable water shall conform to Sections P2902.5.1 through P2902.5.5.

    P2902.5.1 Connections to boilers.

    Where chemicals will not be introduced into a boiler, the potable water supply to the boiler shall be protected from the boiler by a backflow preventer with an intermediate atmospheric vent complying with ASSE 1012 or CSA B64.3. Where chemicals will be introduced into a boiler, the potable water supply to the boiler shall be protected from the boiler by an air gap or a reduced pressure principle backflow prevention assembly complying with ASSE 1013, CSA B64.4 or AWWA C511.

    P2902.5.2 Heat exchangers.

    Heat exchangers using an essentially toxic transfer fluid shall be separated from the potable water by double-wall construction. An air gap open to the atmosphere shall be provided between the two walls. Single-wall construction heat exchangers shall be used only where an essentially nontoxic transfer fluid is utilized.

    P2902.5.3 Lawn irrigation systems.

    The potable water supply to lawn irrigation systems shall be protected against backflow by an atmospheric vacuum breaker, a pressure vacuum breaker assembly or a reduced pressure principle backflow prevention assembly. Valves shall not be installed downstream from an atmospheric vacuum breaker. Where chemicals are introduced into the system, the potable water supply shall be protected against backflow by a reduced pressure principle backflow prevention assembly.

    P2902.5.4 Connections to automatic fire sprinkler systems.

    The potable water supply to automatic fire sprinkler systems shall be protected against backflow by a double check backflow prevention assembly, a double check fire protection backflow prevention assembly, a reduced pressure principle backflow prevention assembly or a reduced pressure principle fire protection backflow prevention assembly.

    Exception: Where systems are installed as a portion of the water distribution system in accordance with the requirements of this code and are not provided with a fire department connection, backflow protection for the water supply system shall not be required.

    P2902.5.4.1Additives or nonpotable source.

    Where systems contain chemical additives or antifreeze, or where systems are connected to a nonpotable secondary water supply, the potable water supply shall be protected against backflow by a reduced pressure principle backflow prevention assembly or a reduced pressure principle fire protection backflow prevention assembly. Where chemical additives or antifreeze is added to only a portion of an automatic fire sprinkler or standpipe system, the reduced pressure principle fire protection backflow preventer shall be permitted to be located so as to isolate that portion of the system.

    P2902.5.5 Solar thermal systems.

    Where a solar thermal system heats potable water to supply a potable hot water distribution or any other type of heating system, the solar thermal system shall be in accordance with Section P2902.5.5.1, P2902.5.5.2 or P2902.5.5.3 as applicable.

    P2902.5.5.1Indirect systems.

    Water supplies of any type shall not be connected to the solar heating loop of an indirect solar thermal hot water heating system. This requirement shall not prohibit the presence of inlets or outlets on the solar heating loop for the purposes of servicing the fluid in the solar heating loop.

    P2902.5.5.2Direct systems for potable water distribution systems.

    Where a solar thermal system directly heats potable water for a potable water distribution system, the pipe, fittings, valves and other components that are in contact with the potable water in the system shall comply with the requirements of Chapter 29.

    P2902.5.5.3Direct systems for other than potable water distribution systems.

    Where a solar thermal system directly heats water for a system other than a potable water distribution system, a potable water supply connected to such system shall be protected by a backflow preventer with an intermediate atmospheric vent complying with ASSE 1012. Where a solar thermal system directly heats chemically treated water for a system other than a potable water distribution system, a potable water supply connected to such system shall be protected by a reduced pressure principle backflow prevention assembly complying with ASSE 1013.

    P2902.6 Location of backflow preventers.

    Access shall be provided to backflow preventers as specified by the manufacturer’s installation instructions.

    P2902.6.1 Outdoor enclosures for backflow prevention devices.

    Outdoor enclosures for backflow prevention devices shall comply with ASSE 1060.

    P2902.6.2 Protection of backflow preventers.

    Backflow preventers shall not be located in areas subject to freezing except where they can be removed by means of unions, or are protected by heat, insulation or both.

    P2902.6.3 Relief port piping.

    The termination of the piping from the relief port or air gap fitting of the backflow preventer shall discharge to an approved indirect waste receptor or to the outdoors where it will not cause damage or create a nuisance.

    SECTIONP2903
    WATER SUPPLY SYSTEM 

    P2903.1 Water supply system design criteria.

    The water service and water distribution systems shall be designed and pipe sizes shall be selected such that under conditions of peak demand, the capacities at the point of outlet discharge shall not be less than shown in Table P2903.1.

    TABLE P2903.1

    REQUIRED CAPACITIES AT POINT OF OUTLET DISCHARGE

    FIXTURE SUPPLY OUTLET SERVINGFLOW RATE (gpm)FLOW PRESSURE (psi)
    Bathtub, balanced-pressure, thermostatic or combination balanced-pressure/thermostatic mixing valve420
    Bidet, thermostatic mixing valve220
    Dishwasher2.758
    Laundry tray48
    Lavatory0.88
    Shower, balanced-pressure, thermostatic or combination balanced-pressure/thermostatic mixing valve2.5a20
    Sillcock, hose bibb58
    Sink1.758
    Water closet, flushometer tank1.620
    Water closet, tank, close coupled320
    Water closet, tank, one-piece620

    For SI: 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 3.785 L/m.

    1. a.Where the shower mixing valve manufacturer indicates a lower flow rating for the mixing valve, the lower value shall be applied.

    P2903.2 Maximum flow and water consumption.

    The maximum water consumption flow rates and quantities for plumbing fixtures and fixture fittings shall be in accordance with Table P2903.2.

    TABLE P2903.2

    MAXIMUM FLOW RATES AND CONSUMPTION FOR PLUMBING FIXTURES AND FIXTURE FITTINGSb

    PLUMBING FIXTURE OR FIXTURE FITTINGMAXIMUM FLOW RATE OR QUANTITY
    Lavatory faucet2.2 gpm at 60 psi
    Shower heada2.5 gpm at 80 psi
    Sink faucet2.2 gpm at 60 psi
    Water closet1.6 gallons per flushing cycle

    For SI: 1 gallon per minute = 3.785 L/m, 1 pound per square inch = 6.895 kPa.

    1. a.A handheld shower spray shall be considered a shower head.

    2. b.Consumption tolerances shall be determined from referenced standards.

    P2903.3Minimum pressure.

    Where the water pressure supplied by the public water main or an individual water supply system is insufficient to provide for the minimum pressures and quantities for the plumbing fixtures in the building, the pressure shall be increased by means of an elevated water tank, a hydropnuematic pressure booster system or a water pressure booster pump.

    P2903.3.1 Maximum pressure.

    The static water pressure shall be not greater than 80 psi (551 kPa). Where the main pressure exceeds 80 psi (551 kPa), an approved pressure-reducing valve conforming to ASSE 1003 or CSA B356 shall be installed on the domestic water branch main or riser at the connection to the water service pipe.

    P2903.4 Thermal expansion control.

    A means for controlling increased pressure caused by thermal expansion shall be installed where required in accordance with Sections P2903.4.1 and P2903.4.2.

    P2903.4.1 Pressure-reducing valve.

    For water service system sizes up to and including 2 inches (51 mm), a device for controlling pressure shall be installed where, because of thermal expansion, the pressure on the downstream side of a pressure-reducing valve exceeds the pressure-reducing valve setting.

    P2903.4.2 Backflow prevention device or check valve.

    Where a backflow prevention device, check valve or other device is installed on a water supply system using storage water heating equipment such that thermal expansion causes an increase in pressure, a device for controlling pressure shall be installed.

    P2903.5 Water hammer.

    The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. Water-hammer arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform to ASSE 1010.

    P2903.6 Determining water supply fixture units.

    Supply loads in the building water distribution system shall be determined by total load on the pipe being sized, in terms of water supply fixture units (w.s.f.u.), as shown in Table P2903.6, and gallon per minute (gpm) flow rates [see Table P2903.6(1)]. For fixtures not listed, choose a w.s.f.u. value of a fixture with similar flow characteristics.

    TABLE P2903.6

    WATER-SUPPLY FIXTURE-UNIT VALUES FOR VARIOUS PLUMBING FIXTURES AND FIXTURE GROUPS

    TYPE OF FIXTURES OR GROUP OF FIXTURESWATER-SUPPLY FIXTURE-UNIT VALUE (w.s.f.u.)
    HotColdCombined
    Bathtub (with/without overhead shower head)1.01.01.4
    Clothes washer1.01.01.4
    Dishwasher1.41.4
    Full-bath group with bathtub (with/without shower head) or shower stall1.52.73.6
    Half-bath group (water closet and lavatory)0.52.52.6
    Hose bibb (sillcock)a2.52.5
    Kitchen group (dishwasher and sink with or without food-waste disposer)1.91.02.5
    Kitchen sink1.01.01.4
    Laundry group (clothes washer standpipe and laundry tub)1.81.82.5
    Laundry tub1.01.01.4
    Lavatory0.50.50.7
    Shower stall1.01.01.4
    Water closet (tank type)2.22.2

    For SI: 1 gallon per minute = 3.785 L/m.

    1. a.The fixture unit value 2.5 assumes a flow demand of 2.5 gpm, such as for an individual lawn sprinkler device. If a hose bibb or sill cock will be required to furnish a greater flow, the equivalent fixture-unit value may be obtained from this table or Table P2903.6(1).

    TABLE P2903.6(1)

    CONVERSIONS FROM WATER SUPPLY FIXTURE UNIT TO GALLON PER MINUTE FLOW RATES

    SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH TANKSSUPPLY SYSTEMS PREDOMINANTLY FOR FLUSHOMETER VALVES
    LoadDemandLoadDemand
    (Water supply fixture units)(Gallons per minute)(Cubic feet per minute)(Water supply fixture units)(Gallons per minute)(Cubic feet per minute)
    13.00.04104
    25.00.0684
    36.50.86892
    48.01.06944
    59.41.256592515.02.0052
    610.71.430376617.42.326032
    711.81.577424719.82.646364
    812.81.711104822.22.967696
    913.71.831416924.63.288528
    1014.61.9517281027.03.60936
    1115.42.0586721127.83.716304
    1216.02.138881228.63.823248
    1316.52.205721329.43.930192
    1417.02.272561430.24.037136
    1517.52.33941531.04.14408
    1618.02.906241631.84.241024
    1718.42.4597121732.64.357968
    1818.82.5131841833.44.464912
    1919.22.5666561934.24.571856
    2019.62.6201282035.04.6788
    2521.52.874122538.05.07984
    3023.33.1147443042.05.61356
    3524.93.3286323544.05.88192
    4026.33.5157844046.06.14928
    4527.73.7029364548.06.41664
    5029.13.8900885050.06.684

    For SI: 1 gallon per minute = 3.785 L/m, 1 cubic foot per minute = 0.4719 L/s.

    P2903.7 Size of water-service mains, branch mains and risers.

    The size of the water service pipe shall be not less than

    3/4 inch (19 mm) diameter. The size of water service mains, branch mains and risers shall be determined from the water supply demand [gpm (L/m)], available water pressure [psi (kPa)] and friction loss caused by the water meter and developed length of pipe [feet (m)], including equivalent length of fittings. The size of each water distribution system shall be determined according to design methods conforming to acceptable engineering practice, such as those methods in Appendix P and shall be approved by the code official.

    P2903.8Gridded and parallel water distribution systems.

    Hot water and cold water manifolds installed with parallel-connected individual distribution lines and cold water manifolds installed with gridded distribution lines to each fixture or fixture fitting shall be designed in accordance with Sections P2903.8.1 through P2903.8.5. Gridded systems for hot water distribution systems shall be prohibited.

    P2903.8.1 Sizing of manifolds.

    Manifolds shall be sized in accordance with Table P2903.8.1. Total gallons per minute is the demand for all outlets.

    TABLE P2903.8.1

    MANIFOLD SIZING

    PLASTICMETALLIC
    Nominal Size ID (inches)Maximuma gpmNominal Size ID (inches)Maximuma gpm
    3/4173/411
    129120
    11/44611/431
    11/26611/244

    For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m, 1 foot per second = 0.3048 m/s.

    Note: See Table P2903.6(1) for w.s.f.u and Table 2903.6(1) for gallon-per-minute (gpm) flow rates.

    1. a.Based on velocity limitation: plastic-12 fps; metal-8 fps.

    P2903.8.2 Minimum size.

    Where the developed length of the distribution line is 60 feet (18 288 mm) or less, and the available pressure at the meter is not less than 40 pounds per square inch (276 kPa), the size of individual distribution lines shall be not less than 3/8 inch (10 mm) diameter. Certain fixtures such as one-piece water closets and whirlpool bathtubs shall require a larger size where specified by the manufacturer. If a water heater is fed from the end of a cold water manifold, the manifold shall be one size larger than the water heater feed.

    P2903.8.3 Support and protection.

    Plastic piping bundles shall be secured in accordance with the manufacturer’s instructions and supported in accordance with Section P2605. Bundles that have a change in direction equal to or greater than 45 degrees (0.79 rad) shall be protected from chafing at the point of contact with framing members by sleeving or wrapping.

    P2903.8.4 Valving.

    Fixture valves, when installed, shall be located either at the fixture or at the manifold. Valves installed at the manifold shall be labeled indicating the fixture served.

    P2903.8.5 Hose bibb bleed.

    A readily accessible air bleed shall be installed in hose bibb supplies at the manifold or at the hose bibb exit point.

    P2903.9 Valves.

    Valves shall be installed in accordance with Sections P2903.9.1 through P2903.9.5.

    P2903.9.1 Service valve.

    Each dwelling unit shall be provided with an accessible main shutoff valve near the entrance of the water service. The valve shall be of a full-open type having nominal restriction to flow, with provision for drainage such as a bleed orifice or installation of a separate drain valve. Additionally, the water service shall be valved at the curb or lot line in accordance with local requirements.

    P2903.9.2 Water heater valve.

    A readily accessible full-open valve shall be installed in the cold-water supply pipe to each water heater at or near the water heater.

    P2903.9.3 Fixture valves and access.

    Shutoff valves shall be required on each fixture supply pipe to each plumbing appliance and to each plumbing fixture other than bathtubs and showers. Valves serving individual plumbing fixtures, plumbing appliances, risers and branches shall be accessible.

    P2903.9.4 Valve requirements.

    Valves shall be compatible with the type of piping material installed in the system. Valves shall conform to one of the standards listed in

    Table P2903.9.4 or shall be approved. Valves intended to supply drinking water shall meet the requirements of NSF 61.

    TABLE P2903.9.4

    VALVES

    MATERIALSTANDARD
    Chlorinated polyvinyl chloride (CPVC) plasticASME A112.4.14, ASME A112.18.1/CSA B125.1,ASTM F 1970, CSA B125.3
    Copper or copper alloyASME A112.4.14, ASME A112.18.1/CSA B125.1,ASME B16.34, CSA B125.3, MSS SP-67, MSS SP-80, MSS SP-110
    Gray and ductile ironASTM A126, AWWA C500, AWWA C504, AWWA C507,MSS SP-42, MSS SP-67, MSS SP-70, MSS SP-71, MSS SP-72,MSS SP-78
    Cross-linked polyethylene (PEX) plasticASME A112.4.14, ASME A112.18.1/CSA B125.1, CSA B125.3,NSF 359
    Polypropylene (PP) plasticASME A112.4.14, ASTM F 2389
    Polyvinyl chloride (PVC) plasticASME A112.4.14, ASTM F 1970

    P2903.9.5 Valves and outlets prohibited below grade.

    Potable water outlets and combination stop-and-waste valves shall not be installed underground or below grade. Freezeproof yard hydrants that drain the riser into the ground are considered to be stop-and-waste valves.

    Exception: Installation of freezeproof yard hydrants that drain the riser into the ground shall be permitted if the potable water supply to such hydrants is protected upstream of the hydrants in accordance with Section P2902 and the hydrants are permanently identified as nonpotable outlets by approved signage that reads as follows: “Caution, Nonpotable Water. Do Not Drink.”

    P2903.10 Hose bibb.

    Hose bibbs subject to freezing, including the “frostproof” type, shall be equipped with an accessible stop-and-waste-type valve inside the building so that they can be controlled and drained during cold periods.

    Exception: Frostproof hose bibbs installed such that the stem extends through the building insulation into an open heated or semiconditioned space need not be separately valved (see Figure P2903.10).

    FIGURE P2903.10 TYPICAL FROSTPROOF HOSE BIBB INSTALLATION NOT REQUIRING SEPARATE VALUE

    FIGURE P2903.10

    TYPICAL FROSTPROOF HOSE BIBB INSTALLATION NOT REQUIRING SEPARATE VALUE

    P2903.11 Drain water heat recovery units.

    Drain water heat recovery units shall be in accordance with Section N1103.5.4.

    SECTIONP2904
    DWELLING UNIT FIRE SPRINKLER SYSTEMS 

    P2904.1 General.

    The design and installation of residential fire sprinkler systems shall be in accordance with NFPA 13D or Section P2904, which shall be considered equivalent to NFPA 13D. Partial residential sprinkler systems shall be permitted to be installed only in buildings not required to be equipped with a residential sprinkler system. Section P2904 shall apply to stand-alone and multipurpose wet-pipe sprinkler systems that do not include the use of antifreeze. A multipurpose fire sprinkler system shall provide domestic water to both fire sprinklers and plumbing fixtures. A stand-alone sprinkler system shall be separate and independent from the water distribution system. A backflow preventer shall not be required to separate a stand-alone sprinkler system from the water distribution system.

    P2904.1.1 Required sprinkler locations.

    Sprinklers shall be installed to protect all areas of a dwelling unit.

    Exceptions:

    1. 1.Attics, crawl spaces and normally unoccupied concealed spaces that do not contain fuel-fired appliances do not require sprinklers. In attics, crawl spaces and normally unoccupied concealed spaces that contain fuel-fired equipment, a sprinkler shall be installed above the equipment; however, sprinklers shall not be required in the remainder of the space.

    2. 2.Clothes closets, linen closets and pantries not exceeding 24 square feet (2.2 m2) in area, with the smallest dimension not greater than 3 feet (915 mm) and having wall and ceiling surfaces of gypsum board.

    3. 3.Bathrooms not more than 55 square feet (5.1 m2) in area.

    4. 4.Garages; carports; exterior porches; unheated entry areas, such as mud rooms, that are adjacent to an exterior door; and similar areas.

    P2904.2 Sprinklers.

    Sprinklers shall be new listed residential sprinklers and shall be installed in accordance with the sprinkler manufacturer’s instructions.

    P2904.2.1 Temperature rating and separation from heat sources.

    Except as provided for in Section P2904.2.2, sprinklers shall have a temperature rating of not less than 135°F (57°C) and not more than 170°F (77°C). Sprinklers shall be separated from heat sources as required by the sprinkler manufacturer’s installation instructions.

    P2904.2.2 Intermediate temperature sprinklers.

    Sprinklers shall have an intermediate temperature rating not less than 175°F (79°C) and not more than 225°F (107°C) where installed in the following locations:

    1. 1.Directly under skylights, where the sprinkler is exposed to direct sunlight.

    2. 2.In attics.

    3. 3.In concealed spaces located directly beneath a roof.

    4. 4.Within the distance to a heat source as specified in Table P2904.2.2.

    TABLE P2904.2.2

    LOCATIONS WHERE INTERMEDIATE TEMPERATURE SPRINKLERS ARE REQUIRED

    HEAT SOURCERANGE OF DISTANCE FROM HEAT SOURCE WITHIN WHICH INTERMEDIATE TEMPERATURE SPRINKLERS ARE REQUIREDa, b (inches)
    Fireplace, side of open or recessed fireplace12 to 36
    Fireplace, front of recessed fireplace36 to 60
    Coal and wood burning stove12 to 42
    Kitchen range top9 to 18
    Oven9 to 18
    Vent connector or chimney connector9 to 18
    Heating duct, not insulated9 to 18
    Hot water pipe, not insulated6 to 12
    Side of ceiling or wall warm air register12 to 24
    Front of wall mounted warm air register18 to 36
    Water heater, furnace or boiler3 to 6
    Luminaire up to 250 watts3 to 6
    Luminaire 250 watts up to 499 watts6 to 12

    For SI: 1 inch = 25.4 mm.

    1. a.Sprinklers shall not be located at distances less than the minimum table distance unless the sprinkler listing allows a lesser distance.

    2. b.Distances shall be measured in a straight line from the nearest edge of the heat source to the nearest edge of the sprinkler.

    P2904.2.3 Freezing areas.

    Piping shall be protected from freezing as required by Section P2603.6. Where sprinklers are required in areas that are subject to freezing, dry-side-wall or dry-pendent sprinklers extending from a nonfreezing area into a freezing area shall be installed.

    P2904.2.4 Sprinkler coverage.

    Sprinkler coverage requirements and sprinkler obstruction requirements shall be in accordance with Sections P2904.2.4.1 and P2904.2.4.2.

    P2904.2.4.1Coverage area limit.

    The area of coverage of a single sprinkler shall not exceed 400 square feet (37 m2) and shall be based on the sprinkler listing and the sprinkler manufacturer’s installation instructions.

    P2904.2.4.2Obstructions to coverage.

    Sprinkler discharge shall not be blocked by obstructions unless additional sprinklers are installed to protect the obstructed area. Additional sprinklers shall not be required where the sprinkler separation from obstructions complies with either the minimum distance indicated in Figure P2904.2.4.2 or the minimum distances specified in the sprinkler manufacturer’s instructions where the manufacturer’s instructions permit a lesser distance.

    FIGURE P2904.2.4.2 MINIMUM ALLOWABLE DISTANCE BETWEEN SPRINKLER AND OBSTRUCTION

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

    FIGURE P2904.2.4.2

    MINIMUM ALLOWABLE DISTANCE BETWEEN SPRINKLER AND OBSTRUCTION

    P2904.2.4.2.1Additional requirements for pendent sprinklers.

    Pendent sprinklers within 3 feet (915 mm) of the center of a ceiling fan, surface-mounted ceiling luminaire or similar object shall be considered to be obstructed, and additional sprinklers shall be installed.

    P2904.2.4.2.2Additional requirements for side-wall sprinklers.

    Sidewall sprinklers within 5 feet (1524 mm) of the center of a ceiling fan, surface-mounted ceiling luminaire or similar object shall be considered to be obstructed, and additional sprinklers shall be installed.

    P2904.2.5 Sprinkler installation on systems assembled with solvent cement.

    The solvent cementing of threaded adapter fittings shall be completed and threaded adapters for sprinklers shall be verified as being clear of excess cement prior to the installation of sprinklers on systems assembled with solvent cement.

    P2904.2.6 Sprinkler modifications prohibited.

    Painting, caulking or modifying of sprinklers shall be prohibited. Sprinklers that have been painted, caulked, modified or damaged shall be replaced with new sprinklers.

    P2904.3 Sprinkler piping system.

    Sprinkler piping shall be supported in accordance with requirements for cold water distribution piping. Sprinkler piping shall comply with the requirements for cold water distribution piping. For multipurpose piping systems, the sprinkler piping shall connect to and be a part of the cold water distribution piping system.

    Exception: For plastic piping, it shall be permissible to follow the manufacturer’s installation instructions.

    P2904.3.1 Nonmetallic pipe and tubing.

    Nonmetallic pipe and tubing, such as CPVC, PEX, and PE-RT shall be listed for use in residential fire sprinkler systems.

    P2904.3.1.1Nonmetallic pipe protection.

    Nonmetallic pipe and tubing systems shall be protected from exposure to the living space by a layer of not less than 3/8-inch-thick (9.5 mm) gypsum wallboard, 1/2-inch-thick (13 mm) plywood, or other material having a 15-minute fire rating.

    Exceptions:

    1. 1.Pipe protection shall not be required in areas that do not require protection with sprinklers as specified in Section P2904.1.1.

    2. 2.Pipe protection shall not be required where exposed piping is permitted by the pipe listing.

    P2904.3.2 Shutoff valves prohibited.

    With the exception of shutoff valves for the entire water distribution system, valves shall not be installed in any location where the valve would isolate piping serving one or more sprinklers.

    P2904.3.3 Single dwelling limit.

    Piping beyond the service valve located at the beginning of the water distribution system shall not serve more than one dwelling.

    P2904.3.4 Drain.

    A means to drain the sprinkler system shall be provided on the system side of the water distribution shutoff valve.

    P2904.4 Determining system design flow.

    The flow for sizing the sprinkler piping system shall be based on the flow rating of each sprinkler in accordance with Section P2904.4.1 and the calculation in accordance with Section P2904.4.2.

    P2904.4.1 Determining required flow rate for each sprinkler.

    The minimum required flow for each sprinkler shall be determined using the sprinkler manufacturer’s published data for the specific sprinkler model based on all of the following:

    1. 1.The area of coverage.

    2. 2.The ceiling configuration.

    3. 3.The temperature rating.

    4. 4.Any additional conditions specified by the sprinkler manufacturer.

    P2904.4.2 System design flow rate.

    The design flow rate for the system shall be based on the following:

    1. 1.The design flow rate for a room having only one sprinkler shall be the flow rate required for that sprinkler, as determined by Section P2904.4.1.

    2. 2.The design flow rate for a room having two or more sprinklers a shall be determined by identifying the sprinkler in that room with the highest required flow rate, based on Section P2904.4.1, and multiplying that flow rate by 2.

    3. 3.Where the sprinkler manufacturer specifies different criteria for ceiling configurations that are not smooth, flat and horizontal, the required flow rate for that room shall comply with the sprinkler manufacturer’s instructions.

    4. 4.The design flow rate for the sprinkler system shall be the flow required by the room with the largest flow rate, based on Items 1, 2 and 3.

    5. 5.For the purpose of this section, it shall be permissible to reduce the design flow rate for a room by subdividing the space into two or more rooms, where each room is evaluated separately with respect to the required design flow rate. Each room shall be bounded by walls and a ceiling. Openings in walls shall have a lintel not less than 8 inches (203 mm) in depth and each lintel shall form a solid barrier between the ceiling and the top of the opening.

    P2904.5 Water supply.

    The water supply shall provide not less than the required design flow rate for sprinklers in accordance with Section P2904.4.2 at a pressure not less than that used to comply with Section P2904.6.

    P2904.5.1 Water supply from individual sources.

    Where a dwelling unit water supply is from a tank system, a private well system or a combination of these, the available water supply shall be based on the minimum pressure control setting for the pump.

    P2904.5.2 Required capacity.

    The water supply shall have the capacity to provide the required design flow rate for sprinklers for a period of time as follows:

    1. 1.Seven minutes for dwelling units one story in height and less than 2,000 square feet (186 m2) in area.

    2. 2.Ten minutes for dwelling units two or more stories in height or equal to or greater than 2,000 square feet (186 m2) in area.

    Where a well system, a water supply tank system or a combination thereof is used, any combination of well capacity and tank storage shall be permitted to meet the capacity requirement.

    P2904.6 Pipe sizing.

    The piping to sprinklers shall be sized for the flow required by Section P2904.4.2. The flow required to supply the plumbing fixtures shall not be required to be added to the sprinkler design flow.

    P2904.6.1 Method of sizing pipe.

    Piping supplying sprinklers shall be sized using the prescriptive method in Section P2904.6.2 or by hydraulic calculation in accordance with NFPA 13D. The minimum pipe size from the water supply source to any sprinkler shall be 3/4 inch (19 mm) nominal. Threaded adapter fittings at the point where sprinklers are attached to the piping shall be not less than 1/2 inch (13 mm) nominal.

    P2904.6.2 Prescriptive pipe sizing method.

    Pipe shall be sized by determining the available pressure to offset friction loss in piping and identifying a piping material, diameter and length using the equation in Section P2904.6.2.1 and the procedure in Section P2904.6.2.2.

    TABLE P2904.6.2(1)

    WATER SERVICE PRESSURE LOSS (PLsvc)a, b

    FLOW RATEc (gpm)3/4-INCH WATER SERVICE PRESSURE LOSS (psi)1-INCH WATER SERVICE PRESSURE LOSS (psi)11/4 -INCH WATER SERVICE PRESSURE LOSS (psi)
    Length of water service pipe (feet)Length of water service pipe (feet)Length of water service pipe (feet)
    40 or less41 to 7576 to 100101 to 15040 or less41 to 7576 to 100101 to 15040 or less41 to 7576 to 100101 to 150
    85.18.711.817.41.52.53.45.10.61.01.31.9
    107.713.117.826.32.33.85.27.70.81.42.02.9
    1210.818.424.9NP3.25.47.310.71.22.02.74.0
    1414.424.5NPNP4.27.19.614.31.62.73.65.4
    1618.4NPNPNP5.49.112.418.32.03.44.76.9
    1822.9NPNPNP6.711.415.422.72.54.35.88.6
    2027.8NPNPNP8.113.818.727.63.15.27.010.4
    22NPNPNPNP9.716.522.3NP3.76.28.412.4
    24NPNPNPNP11.419.326.2NP4.37.39.914.6
    26NPNPNPNP13.222.4NPNP5.08.511.416.9
    28NPNPNPNP15.125.7NPNP5.79.713.119.4
    30NPNPNPNP17.2NPNPNP6.511.014.922.0
    32NPNPNPNP19.4NPNPNP7.312.416.824.8
    34NPNPNPNP21.7NPNPNP8.213.918.8NP
    36NPNPNPNP24.1NPNPNP9.115.420.9NP

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 0.063 L/s, 1 pound per square inch = 6.895 kPa.

    NP = Not permitted. Pressure loss exceeds reasonable limits.

    1. a.Values are applicable for underground piping materials listed in Table P2905.4 and are based on an SDR of 11 and a Hazen Williams C Factor of 150.

    2. b.Values include the following length allowances for fittings: 25% length increase for actual lengths up to 100 feet and 15% length increase for actual lengths over 100 feet.

    3. c.Flow rate from Section P2904.4.2. Add 5 gpm to the flow rate required by Section P2904.4.2 where the water-service pipe supplies more than one dwelling.

    TABLE P2904.6.2(2)

    MINIMUM WATER METER PRESSURE LOSS (PLm)a

    FLOW RATE(gallons per minute, gpm)b5/8-INCH METER PRESSURE LOSS (pounds per square inch, psi)3/4-INCH METER PRESSURE LESS(pounds per square inch, psi)1-INCH METER PRESSURE LOSS (pounds per square inch, psi)
    8211
    10311
    12411
    14521
    16731
    18941
    201142
    22NP52
    24NP52
    26NP62
    28NP62
    30NP72
    32NP73
    34NP83
    36NP83

    For SI: 1 inch = 25.4 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.063 L/s.

    NP—Not permitted unless the actual water meter pressure loss is known.

    1. a.Table P2904.6.2(2) establishes conservative values for water meter pressure loss or installations where the water meter loss is unknown. Where the actual water meter pressure loss is known, Pm shall be the actual loss.

    2. b.Flow rate from Section P2904.4.2. Add 5 gpm to the flow rate required by Section P2904.4.2 where the water-service pipe supplies more than one dwelling.

    TABLE P2904.6.2(3)

    ELEVATION LOSS (PLe)

    ELEVATION (feet)PRESSURE LOSS (psi)
    52.2
    104.4
    156.5
    208.7
    2510.9
    3013
    3515.2
    4017.4

    For SI: 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa.

    TABLE P2904.6.2(4)

    ALLOWABLE PIPE LENGTH FOR 3/4-INCH TYPE M COPPER WATER TUBING

    SPRINKLER FLOW RATEa (gpm)WATER DISTRIBUTION SIZE (inch)AVAILABLE PRESSURE—Pt (psi)
    15202530354045505560
    Allowable length of pipe from service valve to farthest sprinkler (feet)
    83/4217289361434506578650723795867
    93/4174232291349407465523581639697
    103/4143191239287335383430478526574
    113/4120160200241281321361401441481
    123/4102137171205239273307341375410
    133/488118147177206235265294324353
    143/477103128154180205231257282308
    153/46890113136158181203226248271
    163/46080100120140160180200220241
    173/4547290108125143161179197215
    183/448648197113129145161177193
    193/444587388102117131146160175
    203/44053668093106119133146159
    213/4364861738597109121133145
    223/4334456677889100111122133
    233/431415161728292102113123
    243/42838475766768595104114
    253/4263544536170798897105
    263/424334149576573829098
    273/423303846536169768491
    283/421283643505764717885
    293/420273340475360677380
    303/419253138445056636975
    313/418242935414753596571
    323/417222833394450566167
    333/416212632374247535863
    343/4NP202530354045505560
    353/4NP192428333842475257
    363/4NP182227313640454954
    373/4NP172126303438434751
    383/4NP162024283236404549
    393/4NP151923273135394246
    403/4NPNP1822262933374044

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s.

    NP—Not permitted.

    1. a.Flow rate from Section P2904.4.2.

    TABLE P2904.6.2(5)

    ALLOWABLE PIPE LENGTH FOR 1-INCH TYPE M COPPER WATER TUBING

    SPRINKLER FLOW RATEa (gpm)WATER DISTRIBUTION SIZE (inch)AVAILABLE PRESSURE—Pt (psi)
    15202530354045505560
    Allowable length of pipe from service valve to farthest sprinkler (feet)
    81806107513431612188121492418268729553224
    9164886410801296151217281945216123772593
    1015337118891067124514221600177819562134
    111447586745894104311921341149116401789
    12138150863476188810151142126913961523
    131328438547657766875985109412041313
    14128638247757266876385995410491145
    1512523364205045886727568409241008
    161224298373447522596671745820894
    171200266333400466533600666733799
    181180240300360420479539599659719
    191163217271325380434488542597651
    201148197247296345395444493543592
    211135180225270315360406451496541
    221124165207248289331372413455496
    231114152190228267305343381419457
    241106141176211246282317352387422
    25198131163196228261294326359392
    26191121152182212243273304334364
    27185113142170198226255283311340
    28179106132159185212238265291318
    2917499124149174198223248273298
    3017093116140163186210233256280
    3116688110132153175197219241263
    3216283103124145165186207227248
    331597898117137156176195215234
    341557492111129148166185203222
    351537088105123140158175193210
    361506683100116133150166183199
    37147637995111126142158174190
    38145607590105120135150165181
    39143577286100115129143158172
    4014155688296109123137150164

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s.

    1. a.Flow rate from Section P2904.4.2.

    TABLE P2904.6.2(6)

    ALLOWABLE PIPE LENGTH FOR 3/4-INCH CPVC PIPE

    SPRINKLER FLOW RATEa (gpm)WATER DISTRIBUTION SIZE (inch)AVAILABLE PRESSURE—Pt (psi)
    15202530354045505560
    Allowable length of pipe from service valve to farthest sprinkler (feet)
    83/43484655816978139291045116112781394
    93/428037446756065474784193410271121
    103/4231307384461538615692769845922
    113/4193258322387451515580644709773
    123/4165219274329384439494549603658
    133/4142189237284331378426473520568
    143/4124165206247289330371412454495
    153/4109145182218254290327363399436
    163/497129161193226258290322354387
    173/486115144173202230259288317346
    183/478104130155181207233259285311
    193/47094117141164188211234258281
    203/46485107128149171192213235256
    213/4587897117136156175195214234
    223/4547189107125143161179197214
    233/449668299115132148165181198
    243/446617691107122137152167183
    253/44256718599113127141155169
    263/43952667992105118131144157
    273/4374961738698110122135147
    283/4344657698092103114126137
    293/432435464758696107118129
    303/430405060708191101111121
    313/42838475766768595104114
    323/4273645546371808998107
    333/4253442515968768493101
    343/424324048566472808896
    353/423303845536168768391
    363/422293643505765727986
    373/420273441485561687582
    383/420263339465259657278
    393/419253137435056626874
    403/418243035414753596571

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s.

    1. a.Flow rate from Section P2904.4.2.

    TABLE P2904.6.2(7)

    ALLOWABLE PIPE LENGTH FOR 1-INCH CPVC PIPE

    SPRINKLER FLOW RATEa (gpm)WATER DISTRIBUTION SIZE (inch)AVAILABLE PRESSURE—Pt (psi)
    15202530354045505560
    Allowable length of pipe from service valve to farthest sprinkler (feet)
    811049139817482098244727973146349638454195
    91843112514061687196822492530281130933374
    10169492511571388161918512082231425452776
    1115827769701164135815521746194021332327
    121495660826991115613211486165118161981
    13142757071285499711391281142415661709
    1413724976217458699931117124113661490
    151328437546656765874983109312021311
    16129138848558267977687397010671164
    1712603474335206076937808679541040
    181234312390468546624702780858936
    191212282353423494565635706776847
    201193257321385449513578642706770
    211176235293352410469528586645704
    221161215269323377430484538592646
    231149198248297347396446496545595
    241137183229275321366412458504550
    251127170212255297340382425467510
    261118158197237276316355395434474
    271111147184221258295332368405442
    281103138172207241275310344379413
    29197129161194226258290323355387
    30191121152182212242273303333364
    31186114143171200228257285314342
    32181108134161188215242269296323
    33176102127152178203229254280305
    3417296120144168192216240265289
    3516891114137160182205228251273
    3616587108130151173195216238260
    3716282103123144165185206226247
    381597898117137157176196215235
    391567593112131149168187205224
    401537189107125142160178196214

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s.

    1. a.Flow rate from Section P2904.4.2.

    TABLE P2904.6.2(8)

    ALLOWABLE PIPE LENGTH FOR 3/4-INCH PEX AND PE-RT TUBING

    SPRINKLER FLOW RATEa (gpm)WATER DISTRIBUTION SIZE (inch)AVAILABLE PRESSURE—Pt (psi)
    15202530354045505560
    Allowable length of pipe from service valve to farthest sprinkler (feet)
    83/493123154185216247278309339370
    93/47499124149174199223248273298
    103/46182102123143163184204225245
    113/4516886103120137154171188205
    123/444587387102117131146160175
    133/43850637588101113126138151
    143/433445566778899110121132
    153/42939485868778796106116
    163/4263443516068778694103
    173/423313846546169778492
    183/421283441485562697683
    193/419253137445056626975
    203/417232834404551576268
    213/416212631364147525762
    223/4NP192428333843475257
    233/4NP172226313539444852
    243/4NP162024283236404449
    253/4NPNP1922263034374145
    263/4NPNP1721242831353842
    273/4NPNP1620232629333639
    283/4NPNP1518212427303336
    293/4NPNPNP17202326283134
    303/4NPNPNP16192124272932
    313/4NPNPNP15182023252830
    323/4NPNPNPNP171921242628
    333/4NPNPNPNP161820222527
    343/4NPNPNPNPNP1719212325
    353/4NPNPNPNPNP1618202224
    363/4NPNPNPNPNP1517192123
    373/4NPNPNPNPNPNP16182022
    383/4NPNPNPNPNPNP16171921
    393/4NPNPNPNPNPNPNP161820
    403/4NPNPNPNPNPNPNP161719

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s.

    NP—Not permitted.

    1. a.Flow rate from Section P2904.4.2.

    TABLE P2904.6.2(9)

    ALLOWABLE PIPE LENGTH FOR 1-INCH PEX AND PE-RT TUBING

    SPRINKLER FLOW RATEa (gpm)WATER DISTRIBUTION SIZE (inch)AVAILABLE PRESSURE—Pt (psi)
    15202530354045505560
    Allowable length of pipe from service valve to farthest sprinkler (feet)
    81314418523628732837941104611511255
    912523364215055896737578419251009
    101208277346415485554623692761831
    111174232290348406464522580638696
    121148198247296346395445494543593
    131128170213256298341383426469511
    141111149186223260297334371409446
    15198131163196229262294327360392
    16187116145174203232261290319348
    17178104130156182208233259285311
    1817093117140163187210233257280
    1916384106127148169190211232253
    201587796115134154173192211230
    211537088105123140158175193211
    22148648097113129145161177193
    23144597489104119133148163178
    2414155698296110123137151164
    2513851647689102114127140152
    261354759718395106118130142
    27133445566778899110121132
    28131415262728293103113124
    2912939485868778797106116
    3012736455463738291100109
    311263443516068778594102
    32124324048566472808997
    33123303846536168768491
    34122293643505865727986
    35120273441485561687582
    36119263239455258657178
    37118253137434955626874
    38118232935414753596470
    39117222833394550566167
    40116212732374348535964

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s.

    1. a.Flow rate from Section P2904.4.2.

    P2904.6.2.1Available pressure equation.

    The pressure available to offset friction loss in the interior piping system (Pt) shall be determined in accordance with the Equation 29-1.

    https://cdn-codes.iccsafe.org/bundles/document/new_document_images/553/Eq0008.jpg(Equation 29-1)

    where:

    Pt=Pressure used in applying Tables P2904.6.2(4) through P2904.6.2(9).
    Psup=Pressure available from the water supply source.
    PLsvc=Pressure loss in the water-service pipe.
    PLm=Pressure loss in the water meter.
    PLd=Pressure loss from devices other than the water meter.
    PLe=Pressure loss associated with changes in elevation.
    Psp=Maximum pressure required by a sprinkler.

    P2904.6.2.2Calculation procedure.

    Determination of the required size for water distribution piping shall be in accordance with the following procedure:

    Step 1—DeterminePsup

    Obtain the static supply pressure that will be available from the water main from the water purveyor, or for an individual source, the available supply pressure shall be in accordance with Section P2904.5.1.

    Step 2—DeterminePLsvc

    Use Table P2904.6.2(1) to determine the pressure loss in the water service pipe based on the selected size of the water service.

    Step 3—DeterminePLm

    Use Table P2904.6.2(2) to determine the pressure loss from the water meter, based on the selected water meter size.

    Step 4—DeterminePLd

    Determine the pressure loss from devices other than the water meter installed in the piping system supplying sprinklers, such as pressure-reducing valves, backflow preventers, water softeners or water filters. Device pressure losses shall be based on the device manufacturer’s specifications. The flow rate used to determine pressure loss shall be the rate from Section P2904.4.2, except that 5 gpm (0.3 L/s) shall be added where the device is installed in a water-service pipe that supplies more than one dwelling. As an alternative to deducting pressure loss for a device, an automatic bypass valve shall be installed to divert flow around the device when a sprinkler activates.

    Step 5—DeterminePLe

    Use Table P2904.6.2(3) to determine the pressure loss associated with changes in elevation. The elevation used in applying the table shall be the difference between the elevation where the water source pressure was measured and the elevation of the highest sprinkler.

    Step 6—DeterminePsp

    Determine the maximum pressure required by any individual sprinkler based on the flow rate from Section P2904.4.1. The required pressure is provided in the sprinkler manufacturer’s published data for the specific sprinkler model based on the selected flow rate.

    Step 7—CalculatePt

    Using Equation 29-1, calculate the pressure available to offset friction loss in water-distribution piping between the service valve and the sprinklers.

    Step 8—Determine the maximum allowable pipe length

    Use Tables P2904.6.2(4) through P2904.6.2(9) to select a material and size for water distribution piping. The piping material and size shall be acceptable if the developed length of pipe between the service valve and the most remote sprinkler does not exceed the maximum allowable length specified by the applicable table. Interpolation of Pt between the tabular values shall be permitted.

    The maximum allowable length of piping in Tables P2904.6.2(4) through P2904.6.2(9) incorporates an adjustment for pipe fittings. Additional consideration of friction losses associated with pipe fittings shall not be required.

    P2904.7 Instructions and signs.

    An owner’s manual for the fire sprinkler system shall be provided to the owner. A sign or valve tag shall be installed at the main shutoff valve to the water distribution system stating the following: “Warning, the water system for this home supplies fire sprinklers that require certain flows and pressures to fight a fire. Devices that restrict the flow or decrease the pressure or automatically shut off the water to the fire sprinkler system, such as water softeners, filtration systems and automatic shutoff valves, shall not be added to this system without a review of the fire sprinkler system by a fire protection specialist. Do not remove this sign.”

    P2904.8 Inspections.

    The water distribution system shall be inspected in accordance with Sections P2904.8.1 and P2904.8.2.

    P2904.8.1 Preconcealment inspection.

    The following items shall be verified prior to the concealment of any sprinkler system piping:

    1. 1.Sprinklers are installed in all areas as required by Section P2904.1.1.

    2. 2.Where sprinkler water spray patterns are obstructed by construction features, luminaires or ceiling fans, additional sprinklers are installed as required by Section P2904.2.4.2.

    3. 3.Sprinklers are the correct temperature rating and are installed at or beyond the required separation distances from heat sources as required by Sections P2904.2.1 and P2904.2.2.

    4. 4.The pipe size equals or exceeds the size used in applying Tables P2904.6.2(4) through P2904.6.2(9) or, if the piping system was hydraulically calculated in accordance with Section P2904.6.1, the size used in the hydraulic calculation.

    5. 5.The pipe length does not exceed the length permitted by Tables P2904.6.2(4) through P2904.6.2(9) or, if the piping system was hydraulically calculated in accordance with Section P2904.6.1, pipe lengths and fittings do not exceed those used in the hydraulic calculation.

    6. 6.Nonmetallic piping that conveys water to sprinklers is listed for use with fire sprinklers.

    7. 7.Piping is supported in accordance with the pipe manufacturer’s and sprinkler manufacturer’s installation instructions.

    8. 8.The piping system is tested in accordance with Section P2503.7.

    P2904.8.2 Final inspection.

    The following items shall be verified upon completion of the system:

    1. 1.Sprinkler are not painted, damaged or otherwise hindered from operation.

    2. 2.Where a pump is required to provide water to the system, the pump starts automatically upon system water demand.

    3. 3.Pressure-reducing valves, water softeners, water filters or other impairments to water flow that were not part of the original design have not been installed.

    4. 4.The sign or valve tag required by Section P2904.7 is installed and the owner’s manual for the system is present.

    SECTIONP2905
    HEATED WATER DISTRIBUTION SYSTEMS 

    P2905.1 Heated water circulation systems and heat trace systems.

    Circulation systems and heat trace systems that are installed to bring heated water in close proximity to one or more fixtures shall meet the requirements of Section N1103.5.1.

    P2905.2 Demand recirculation systems.

    Demand recirculation water systems shall be in accordance with Section N1103.5.2.

    SECTIONP2906
    MATERIALS, JOINTS AND CONNECTIONS 

    P2906.1 Soil and groundwater.

    The installation of water service pipe, water distribution pipe, fittings, valves, appurtenances and gaskets shall be prohibited in soil and groundwater that is contaminated with solvents, fuels, organic compounds or other detrimental materials that cause permeation, corrosion, degradation or structural failure of the water service or water distribution piping material.

    P2906.1.1 Investigation required.

    Where detrimental conditions are suspected by or brought to the attention of the building official, a chemical analysis of the soil and groundwater conditions shall be required to ascertain the acceptability of the water service material for the specific installation.

    P2906.1.2 Detrimental condition.

    Where a detrimental condition exists, approved alternate materials or alternate routing shall be required.

    P2906.2 Lead content.

    The lead content in pipe and fittings used in the water supply system shall be not greater than 8 percent.

    P2906.2.1 Lead content of drinking water pipe and fittings.

    Pipe, pipe fittings, joints, valves, faucets and fixture fittings utilized to supply water for drinking or cooking purposes shall comply with NSF 372 and shall have a weighted average lead content of 0.25 percent lead or less.

    P2906.3 Polyethylene plastic piping installation.

    Polyethylene pipe shall be cut square using a cutter designed for plastic pipe. Except where joined by heat fusion, pipe ends shall be chamfered to remove sharp edges. Pipe that has been kinked shall not be installed. For bends, the installed radius of pipe curvature shall be greater than 30 pipe diameters or the coil radius where bending with the coil. Coiled pipe shall not be bent beyond straight. Bends within 10 pipe diameters of any fitting or valve shall be prohibited. Joints between polyethylene plastic pipe and fittings shall comply with Section P2906.3.1 or P2906.3.2.

    P2906.3.1 Heat-fusion joints.

    Joint surfaces shall be clean and free from moisture. Joint surfaces shall be heated to melting temperature and joined. The joint shall be undisturbed until cool. Joints shall be made in accordance with ASTM D 2657.

    P2906.3.2 Mechanical joints.

    Mechanical joints shall be installed in accordance with the manufacturer’s instructions.

    P2906.4 Water service pipe.

    Water service pipe shall conform to NSF 61 and shall conform to one of the standards indicated in Table P2906.4. Water service pipe or tubing, installed underground and outside of the structure, shall have a working pressure rating of not less than 160 pounds per square inch at 73°F (1103 kPa at 23°C). Where the water pressure exceeds 160 pounds per square inch (1103 kPa), piping material shall have a rated working pressure equal to or greater than the highest available pressure. Water service piping materials not third-party certified for water distribution shall terminate at or before the full open valve located at the entrance to the structure. Ductile iron water service piping shall be cement mortar lined in accordance with AWWA C104/A21.4.

    TABLE P2906.4

    WATER SERVICE PIPE

    MATERIALSTANDARD
    Acrylonitrile butadiene styrene (ABS) plastic pipeASTM D 1527; ASTM D 2282
    Chlorinated polyvinyl chloride (CPVC) plastic pipeASTM D 2846; ASTM F 441; ASTM F 442; CSA B137.6
    Chlorinated polyvinyl chloride/aluminum/chlorinated poly vinyl chloride (CPVC/AL/CPVC) plastic pipeASTM F 2855
    Copper or copper-alloy pipeASTM B 42; ASTM B 43; ASTM B 302
    Copper or copper-alloy tubing (Type K, WK, L, WL, M or WM)ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 447
    Cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pipeASTM F 1281; ASTM F 2262; CSA B137.10
    Cross-linked polyethylene/aluminum/high-density polyethylene (PEX-AL-HDPE) pipeASTM F 1986
    Cross-linked polyethylene (PEX) plastic tubingASTM F 876; ASTM F 877; CSA B137.5
    Ductile iron water pipeAWWA C115/A21.15; AWWA C151/A21.51
    Galvanized steel pipeASTM A 53
    Polyethylene/aluminum/polyethylene (PE-AL-PE) pipeASTM F 1282; CSA B137.9
    Polyethylene (PE) plastic pipeASTM D 2104; ASTM D 2239; AWWA C901; CSA B137.1
    Polyethylene (PE) plastic tubingASTM D 2737; AWWA C901; CSA B137.1
    Polyethylene of raised temperature (PE-RT) plastic tubingASTM F 2769
    Polypropylene (PP) plastic tubingASTM F 2389; CSA B137.11
    Polyvinyl chloride (PVC) plastic pipeASTM D 1785; ASTM D 2241; ASTM D 2672; CSA B137.3
    Stainless steel (Type 304/304L) pipeASTM A 312; ASTM A 778
    Stainless steel (Type 316/316L) pipeASTM A 312; ASTM A 778

    P2906.4.1 Separation of water service and building sewer.

    Trenching, pipe installation and backfilling shall be in accordance with Section P2604. Where water service piping is located in the same trench with the building sewer, such sewer shall be constructed of materials listed in Table P3002.1(2). Where the building sewer piping is not constructed of materials indicated in Table P3002.1(2), the water service pipe and the building sewer shall be horizontally separated by not less than 5 feet (1524 mm) of undisturbed or compacted earth. The required separation distance shall not apply where a water service pipe crosses a sewer pipe, provided the water service is sleeved to a point not less than 5 feet (1524 mm) horizontally from the sewer pipe centerline on both sides of such crossing. The sleeve shall be of pipe materials indicated in Table P2906.4, P3002.1(2) or P3002.2. The required separation distance shall not apply where the bottom of the water service pipe that is located within 5 feet (1524 mm) of the sewer is not less than 12 inches (305 mm) above the highest point of the top of the building sewer.

    P2906.5 Water-distribution pipe.

    Water-distribution piping within dwelling units shall conform to NSF 61 and shall conform to one of the standards indicated in Table P2906.5. Hot-water-distribution pipe and tubing shall have a pressure rating of not less than 100 psi at 180°F (689 kPa at 82°C).

    TABLE P2906.5

    WATER DISTRIBUTION PIPE

    MATERIALSTANDARD
    Chlorinated polyvinyl chloride (CPVC) plastic pipe and tubingASTM D 2846; ASTM F 441; ASTM F 442;CSA B137.6
    Chlorinated polyvinyl chloride/aluminum/chlorinated polyvinyl chloride (CPVC/AL/CPVC) plastic pipeASTM F 2855
    Copper or copper-alloy pipeASTM B 42; ASTM B 43; ASTM B 302
    Copper or copper-alloy tubing (Type K, WK, L, WL, M or WM)ASTM B 75; ASTM B 88; ASTM B 251;ASTM B 447
    Cross-linked polyethylene (PEX) plastic tubingASTM F 876; ASTM F 877; CSA B137.5
    Cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pipeASTM F 1281; ASTM F 2262; CSA B137.10
    Cross-linked polyethylene/aluminum/high-density polyethylene (PEX-AL-HDPE) pipeASTM F 1986
    Galvanized steel pipeASTM A 53
    Polyethylene/aluminum/polyethylene (PE-AL-PE) composite pipeASTM F 1282
    Polyethylene of raised temperature (PE-RT) plastic tubingASTM F 2769
    Polypropylene (PP) plastic pipe or tubingASTM F 2389; CSA B137.11
    Stainless steel (Type 304/304L) pipeASTM A 312; ASTM A 778

    P2906.6 Fittings.

    Pipe fittings shall be approved for installation with the piping material installed and shall comply with the applicable standards indicated in Table P2906.6. Pipe fittings used in water supply systems shall comply with NSF 61.

    TABLE P2906.6

    PIPE FITTINGS

    MATERIALSTANDARD
    Acrylonitrile butadiene styrene (ABS) plasticASTM D 2468
    Cast-ironASME B16.4
    Chlorinated polyvinyl chloride (CPVC) plasticASSE 1061; ASTM D 2846; ASTM F 437; ASTM F 438;ASTM F 439; CSA B137.6
    Copper or copper alloyASSE 1061; ASME B16.15; ASME B16.18; ASME B16.22;ASME B16.26; ASME B16.51
    Cross-linked polyethylene/aluminum/high-density polyethylene (PEX-AL-HDPE)ASTM F 1986
    Fittings for cross-linked polyethylene (PEX) plastic tubingASSE 1061; ASTM F 877; ASTM F 1807; ASTM F 1960;ASTM F 2080; ASTM F 2098; ASTM F 2159; ASTM F 2434;ASTM F 2735; CSA B137.5
    Gray iron and ductile ironAWWA C110/A21.10; AWWA C153/A21.53
    Malleable ironASME B16.3
    Insert fittings for Polyethylene/aluminum/polyethylene (PE-AL-PE) and cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX)ASTM F 1974; ASTM F 1281; ASTM F 1282; CSA B137.9;CSA B137.10
    Polyethylene (PE) plasticASTM D 2609; CSA B137.1
    Fittings for polyethylene of raised temperature (PE-RT) plastic tubingASTM F 1807; ASTM F2098; ASTM F 2159; ASTM F 2735; ASTM F 2769
    Polypropylene (PP) plastic pipe or tubingASTM F 2389; CSA B137.11
    Polyvinyl chloride (PVC) plasticASTM D 2464; ASTM D 2466; ASTM D 2467; CSA B137.2;CSA B137.3
    Stainless steel (Type 304/304L) pipeASTM A 312; ASTM A 778
    Stainless steel (Type 316/316L) pipeASTM A 312; ASTM A 778
    SteelASME B16.9; ASME B16.11; ASME B16.28

    P2906.7 Flexible water connectors.

    Flexible water connectors, exposed to continuous pressure, shall conform to ASME A112.18.6/CSA B125.6. Access shall be provided to flexible water connectors.

    P2906.8 Joint and connection tightness.

    Joints and connections in the plumbing system shall be gas tight and water tight for the intended use or required test pressure.

    P2906.9 Plastic pipe joints.

    Joints in plastic piping shall be made with approved fittings by solvent cementing, heat fusion, corrosion-resistant metal clamps with insert fittings or compression connections. Flared joints for polyethylene pipe shall be permitted in accordance with Section P2906.3.

    P2906.9.1 Solvent cementing.

    Solvent-cemented joints shall comply with Sections P2906.9.1.1 through P2906.9.1.4.

    P2906.9.1.1ABS plastic pipe.

    Solvent cement for ABS plastic pipe conforming to ASTM D 2235 shall be applied to all joint surfaces.

    P2906.9.1.2CPVC plastic pipe.

    Joint surfaces shall be clean and free from moisture. Joints shall be made in accordance with the pipe, fitting or solvent cement manufacturer’s installation instructions. Where such instructions require a primer to be used, an approved primer shall be applied, and a solvent cement, orange in color and conforming to ASTM F 493, shall be applied to joint surfaces. Where such instructions allow for a one-step solvent cement, yellow or red in color and conforming to ASTM F 493, to be used, the joint surfaces shall not require application of a primer before the solvent cement is applied. The joint shall be made while the cement is wet, and in accordance with ASTM D 2846 or ASTM F 493. Solvent cement joints shall be permitted above or below ground.

    P2906.9.1.3CPVC/AL/CPVC pipe.

    Joint surfaces shall be clean and free from moisture, and an approved primer shall be applied. Solvent cement, orange in color and conforming to ASTM F 493, shall be applied to all joint surfaces. The joint shall be made while the cement is wet, and in accordance with ASTM D 2846 or ASTM F 493. Solvent-cement joints shall be installed above or below ground.

    Exception: A primer shall not be required where all of the following conditions apply:

    1. 1.The solvent cement used is third-party certified as conforming to ASTM F 493.

    2. 2.The solvent cement used is yellow in color.

    3. 3.The solvent cement is used only for joining 1/2-inch (12.7 mm) through 1-inch (25 mm) diameter CPVC/AL/CPVC pipe and CPVC fittings.

    4. 4.The CPVC fittings are manufactured in accordance with ASTM D 2846.

    P2906.9.1.4PVC plastic pipe.

    A purple primer that conforms to ASTM F 656 shall be applied to PVC solvent-cemented joints. Solvent cement for PVC plastic pipe conforming to ASTM D 2564 shall be applied to all joint surfaces.

    P2906.9.1.5Cross-linked polyethylene plastic (PEX).

    Joints between cross-linked polyethylene plastic tubing or fittings shall comply with Section P2906.9.1.5.1 or Section P2906.9.1.5.2.

    P2906.9.1.5.1Flared joints.

    Flared pipe ends shall be made by a tool designed for that operation.

    P2906.9.1.5.2Mechanical joints.

    Mechanical joints shall be installed in accordance with the manufacturer’s instructions. Fittings for cross-linked polyethylene (PEX) plastic tubing shall comply with the applicable standards indicated in Table P2906.6 and shall be installed in accordance with the manufacturer’s instructions. PEX tubing shall be factory marked with the applicable standards for the fittings that the PEX manufacturer specifies for use with the tubing.

    P2906.10 Polypropylene (PP) plastic.

    Joints between polypropylene plastic pipe and fittings shall comply with Section P2906.10.1 or P2906.10.2.

    P2906.10.1 Heat-fusion joints.

    Heat fusion joints for polypropylene pipe and tubing joints shall be installed with socket-type heat-fused polypropylene fittings, butt-fusion polypropylene fittings or electrofusion polypropylene fittings. Joint surfaces shall be clean and free from moisture. The joint shall be undisturbed until cool. Joints shall be made in accordance with ASTM F 2389.

    P2906.10.2 Mechanical and compression sleeve joints.

    Mechanical and compression sleeve joints shall be installed in accordance with the manufacturer’s instructions.

    P2906.11 Cross-linked polyethylene/aluminum/cross-linked polyethylene.

    Joints between polyethylene/aluminum/polyethylene (PE-AL-PE) and cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pipe and fittings shall comply with Section P2906.11.1.

    P2906.11.1 Mechanical joints.

    Mechanical joints shall be installed in accordance with the manufacturer’s instructions. Fittings for PE-AL-PE and PEX-AL-PEX as described in ASTM F 1974, ASTM F 1281, ASTM F 1282, CSA B137.9 and CSA B137.10 shall be installed in accordance with the manufacturer’s instructions.

    P2906.12 Stainless steel.

    Joints between stainless steel pipe and fittings shall comply with Section P2906.12.1 or P2906.12.2.

    P2906.12.1 Mechanical joints.

    Mechanical joints shall be installed in accordance with the manufacturer’s instructions.

    P2906.12.2 Welded joints.

    Joint surfaces shall be cleaned. The joint shall be welded autogenously or with an approved filler metal in accordance with ASTM A 312.

    P2906.13 Threaded pipe joints.

    Threaded joints shall conform to American National Taper Pipe Thread specifications. Pipe ends shall be deburred and chips removed. Pipe joint compound shall be used only on male threads.

    P2906.14 Soldered and brazed joints.

    Soldered joints in copper and copper alloy tubing shall be made with fittings approved for water piping and shall conform to ASTM B 828. Surfaces to be soldered shall be cleaned bright. Fluxes for soldering shall be in accordance with ASTM B 813. Brazing fluxes shall be in accordance with AWS A5.31M/A5.31. Solders and fluxes used in potable water-supply systems shall have a lead content of not greater than 0.2 percent.

    P2906.15 Flared joints.

    Flared joints in water tubing shall be made with approved fittings. The tubing shall be reamed and then expanded with a flaring tool.

    P2906.16 Above-ground joints.

    Joints within the building between copper pipe or CPVC tubing, in any combination with compatible outside diameters, shall be permitted to be made with the use of approved push-in mechanical fittings of a pressure-lock design.

    P2906.17 Joints between different materials.

    Joints between different piping materials shall be made in accordance with Section P2906.17.1, P2906.17.2 or P2906.17.3, or with a mechanical joint of the compression or mechanical sealing type having an elastomeric seal conforming to ASTM D 1869 or ASTM F 477. Joints shall be installed in accordance with the manufacturer’s instructions.

    P2906.17.1 Copper or copper-alloy tubing to galvanized steel pipe.

    Joints between copper or copper-alloy tubing and galvanized steel pipe shall be made with a copper alloy fitting or dielectric fitting. The copper tubing shall be joined to the fitting in an approved manner, and the fitting shall be screwed to the threaded pipe.

    P2906.17.2 Plastic pipe or tubing to other piping material.

    Joints between different types of plastic pipe or between plastic pipe and other piping material shall be made with an approved adapter fitting.

    P2906.17.3 Stainless steel.

    Joints between stainless steel and different piping materials shall be made with a mechanical joint of the compression or mechanical-sealing type or a dielectric fitting.

    P2906.18 Press-connect joints.

    Press-connect joints shall conform to one of the standards indicated in Table P2906.6. Press-type mechanical joints in copper tubing shall be made in accordance with the manufacturer’s instructions. Cut tube ends shall be reamed to the full inside diameter of the tube end. Joint surfaces shall be cleaned. The tube shall be fully inserted into the press connect fitting. Press-connect joints shall be pressed with a tool certified by the manufacturer.

    P2906.19 Polyethylene of raised temperature plastic.

    Joints between polyethylene of raised temperature plastic tubing and fittings shall be in accordance with Section P2906.19.1.

    P2906.19.1 Mechanical joints.

    Mechanical joints shall be installed in accordance with the manufacturer’s instructions. Fittings for polyethylene of raised temperature plastic tubing shall comply with the applicable standards listed in Table P2906.6 and shall be installed in accordance with the manufacturer’s instructions. Polyethylene of raised temperature plastic tubing shall be factory marked with the applicable standards for the fittings that the manufacturer of the tubing specifies for use with the tubing.

    SECTIONP2907
    CHANGES IN DIRECTION

    P2907.1 Bends.

    Changes in direction in copper tubing shall be permitted to be made with bends having a radius of not less than four diameters of the tube, provided that such bends are made by use of forming equipment that does not deform or create loss in cross-sectional area of the tube.

    SECTIONP2908
    SUPPORT

    P2908.1 General.

    Pipe and tubing support shall conform to Section P2605.

    SECTIONP2909
    DRINKING WATER TREATMENT UNITS

    P2909.1 Design.

    Drinking water treatment units shall meet the requirements of NSF42, NSF 44, NSF 53, NSF 60 or CSA B483.1.

    P2909.2 Reverse osmosis drinking water treatment units.

    Point-of-use reverse osmosis drinking water treatment units, designed for residential use, shall meet the requirements of NSF 58 or CSA B483.1. Waste or discharge from reverse osmosis drinking water treatment units shall enter the drainage system through an air gap or an air gap device that meets the requirements of NSF 58.

    P2909.3 Connection tubing.

    The tubing to and from drinking water treatment units shall be of a size and material as recommended by the manufacturer. The tubing shall comply with NSF 14, NSF 42, NSF 44, NSF 53, NSF 58 or NSF 61.

    SECTIONP2910
    NONPOTABLE WATER SYSTEMS

    P2910.1 Scope.

    The provisions of this section shall govern the materials, design, construction and installation of systems for the collection, storage, treatment and distribution of nonpotable water. The use and application of nonpotable water shall comply with laws, rules and ordinances applicable in the jurisdiction.

    P2910.2 Water quality.

    Nonpotable water for each end use application shall meet the minimum water quality requirements as established for the intended application by the laws, rules and ordinances applicable in the jurisdiction. Where nonpotable water from different sources is combined in a system, the system shall comply with the most stringent requirements of this code applicable to such sources.

    P2910.2.1 Residual disinfectants.

    Where chlorine is used for disinfection, the nonpotable water shall contain not more than 4 ppm (4 mg/L) of chloramines or free chlorine. Where ozone is used for disinfection, the nonpotable water shall not contain gas bubbles having elevated levels of ozone at the point of use.

    Exception: Reclaimed water sources shall not be required to comply with the requirements of this section.

    P2910.2.2 Filtration required.

    Nonpotable water utilized for water closet and urinal flushing applications shall be filtered by a 100 micron or finer filter.

    Exception: Reclaimed water sources shall not be required to comply with the requirements of this section.

    P2910.3 Signage required.

    Nonpotable water outlets such as hose connections, open-ended pipes and faucets shall be identified at the point of use for each outlet with signage that reads as follows: “Nonpotable water is utilized for [application name]. CAUTION: NONPOTABLE WATER. DO NOT DRINK.” The words shall be legibly and indelibly printed on a tag or sign constructed of corrosion-resistant, waterproof material or shall be indelibly printed on the fixture. The letters of the words shall be not less than 0.5 inches (12.7 mm) in height and in colors contrasting the background on which they are applied. In addition to the required wordage, the pictograph shown in Figure P2910.3 shall appear on the signage required by this section.

    FIGURE P2910.3 PICTOGRAPH—DO NOT DRINK

    FIGURE P2910.3

    PICTOGRAPH—DO NOT DRINK

    P2910.4 Permits.

    Permits shall be required for the construction, installation, alteration and repair of nonpotable water systems. Construction documents, engineering calculations, diagrams and other such data pertaining to the nonpotable water system shall be submitted with each permit application.

    P2910.5 Potable water connections.

    Where a potable system is connected to a nonpotable water system, the potable water supply shall be protected against backflow in accordance with Section P2902.

    P2910.6 Approved components and materials.

    Piping, plumbing components and materials used in collection and conveyance systems shall be manufactured of material approved for the intended application and compatible with any disinfection and treatment systems used.

    P2910.7 Insect and vermin control.

    The system shall be protected to prevent the entrance of insects and vermin into storage tanks and piping systems. Screen materials shall be compatible with contacting system components and shall not accelerate the corrosion of system components.

    P2910.8 Freeze protection.

    Where sustained freezing temperatures occur, provisions shall be made to keep storage tanks and the related piping from freezing.

    P2909.9 Nonpotable water storage tanks.

    Nonpotable water storage tanks shall comply with Sections P2910.9.1 through P2910.9.11.

    P2910.9.1 Sizing.

    The holding capacity of the storage tank shall be sized in accordance with the anticipated demand.

    P2910.9.2 Location.

    Storage tanks shall be installed above or below grade. Above-grade storage tanks shall be protected from direct sunlight and shall be constructed using opaque, UV-resistant materials such as, but not limited to, heavily tinted plastic, lined metal, concrete and wood; or painted to prevent algae growth; or shall have specially constructed sun barriers including, but not limited to, installation in garages, crawlspaces or sheds. Storage tanks and their manholes shall not be located directly under any soil piping, waste piping or any source of contamination.

    P2910.9.3 Materials.

    Where collected on site, water shall be collected in an approved tank constructed of durable, nonabsorbent and corrosion-resistant materials. The storage tank shall be constructed of materials compatible with any disinfection systems used to treat water upstream of the tank and with any systems used to maintain water quality within the tank. Wooden storage tanks that are not equipped with a makeup water source shall be provided with a flexible liner.

    P2910.9.4 Foundation and supports.

    Storage tanks shall be supported on a firm base capable of withstanding the weight of the storage tank when filled to capacity. Storage tanks shall be supported in accordance with this code.

    P2910.9.4.1Ballast.

    Where the soil can become saturated, an underground storage tank shall be ballasted or otherwise secured to prevent the tank from floating out of the ground when empty. The combined weight of the tank and hold-down ballast shall meet or exceed the buoyancy force of the tank. Where the installation requires a foundation, the foundation shall be flat and shall be designed to support the storage tank weight when full, consistent with the bearing capability of adjacent soil.

    P2910.9.4.2Structural support.

    Where installed below grade, storage tank installations shall be designed to withstand earth and surface structural loads without damage and with minimal deformation when empty or filled with water.

    P2910.9.5 Makeup water.

    Where an uninterrupted nonpotable water supply is required for the intended application, potable or reclaimed water shall be provided as a source of makeup water for the storage tank. The makeup water supply shall be protected against backflow by means of an air gap not less than 4 inches (102 mm) above the overflow or an approved backflow device in accordance with Section P2902. A full-open valve located on the makeup water supply line to the storage tank shall be provided. Inlets to the storage tank shall be controlled by fill valves or other automatic supply valves installed to prevent the tank from overflowing and to prevent the water level from dropping below a predetermined point. Where makeup water is provided, the water level shall be prohibited from dropping below the source water inlet or the intake of any attached pump.

    P2910.9.5.1Inlet control valve alarm.

    Makeup water systems shall be fitted with a warning mechanism that alerts the user to a failure of the inlet control valve to close correctly. The alarm shall activate before the water within the storage tank begins to discharge into the overflow system.

    P2910.9.6 Overflow.

    The storage tank shall be equipped with an overflow pipe having a diameter not less than that shown in Table P2910.9.6. The overflow outlet shall discharge at a point not less than 6 inches (152 mm) above the roof or roof drain; floor or floor drain; or over an open water-supplied fixture. The overflow outlet shall be covered with a corrosion-resistant screen of not less than 16 by 20 mesh per inch (630 by 787 mesh per m) and by 1/4-inch (6.4 mm) hardware cloth or shall terminate in a horizontal angle seat check valve. Drainage from overflow pipes shall be directed to prevent freezing on roof walks. The overflow drain shall not be equipped with a shutoff valve. Not less than one cleanout shall be provided on each overflow pipe in accordance with Section P3005.2.

    TABLE P2910.9.6

    SIZE OF DRAIN PIPES FOR WATER TANKS

    TANK CAPACITY (gallons)DRAIN PIPE (inches)
    Up to 7501
    751 to 150011/2
    1501 to 30002
    3001 to 500021/2
    5001 to 75003
    Over 75004

    For SI: 1 gallon = 3.875 liters, 1 inch = 25.4 mm.

    P2910.9.7 Access.

    Not less than one access opening shall be provided to allow inspection and cleaning of the tank interior. Access openings shall have an approved locking device or other approved method of securing access. Below-grade storage tanks, located outside of the building, shall be provided with a manhole either not less than 24 inches (610 mm) square or with an inside diameter not less than 24 inches (610 mm). Manholes shall extend not less than 4 inches (102 mm) above ground or shall be designed to prevent water infiltration. Finished grade shall be sloped away from the manhole to divert surface water. Manhole covers shall be secured to prevent unauthorized access. Service ports in manhole covers shall be not less than 8 inches (203 mm) in diameter and shall be not less than 4 inches (102 mm) above the finished grade level. The service port shall be secured to prevent unauthorized access.

    Exception: Storage tanks under 800 gallons (3028 L) in volume installed below grade shall not be required to be equipped with a manhole, but shall have a service port not less than 8 inches (203 mm) in diameter.

    P2910.9.8 Venting.

    Storage tanks shall be provided with a vent sized in accordance with Chapter 31 and based on the aggregate diameter of all tank influent pipes. The reservoir vent shall not be connected to sanitary drainage system vents. Vents shall be protected from contamination by means of an approved cap or a U-bend installed with the opening directed downward. Vent outlets shall extend not less than 4 inches (102 mm) above grade, or as necessary to prevent surface water from entering the storage tank. Vent openings shall be protected against the entrance of vermin and insects in accordance with the requirements of Section P2902.7.

    P2910.9.9 Drain.

    A drain shall be located at the lowest point of the storage tank. The tank drain pipe shall discharge as required for overflow pipes and shall not be smaller in size than specified in Table P2910.9.6. Not less than one cleanout shall be provided on each drain pipe in accordance with Section P3005.2.

    P2910.10 Marking and signage.

    Each nonpotable water storage tank shall be labeled with its rated capacity. The contents of storage tanks shall be identified with the words “CAUTION: NONPOTABLE WATER—DO NOT DRINK.” Where an opening is provided that could allow the entry of personnel, the opening shall be marked with the words, “DANGER—CONFINED SPACE.” Markings shall be indelibly printed on the tank, or on a tag or sign constructed of corrosion-resistant waterproof material that is mounted on the tank. The letters of the words shall be not less than 0.5 inches (12.7 mm) in height and shall be of a color in contrast with the background on which they are applied.

    P2910.11 Storage tank tests.

    Storage tanks shall be tested in accordance with the following:

    1. 1.Storage tanks shall be filled with water to the overflow line prior to and during inspection. Seams and joints shall be left exposed and the tank shall remain water tight without leakage for a period of 24 hours.

    2. 2.After 24 hours, supplemental water shall be introduced for a period of 15 minutes to verify proper drainage of the overflow system and leaks do not exist.

    3. 3.Following a successful test of the overflow, the water level in the tank shall be reduced to a level that is 2 inches (51 mm) below the makeup water trigger point by using the tank drain. The tank drain shall be observed for proper operation. The makeup water system shall be observed for proper operation, and successful automatic shutoff of the system at the refill threshold shall be verified. Water shall not be drained from the overflow at any time during the refill test.

    P2910.12 System abandonment.

    If the owner of an on-site nonpotable water reuse system or rainwater collection and conveyance system elects to cease use of or fails to properly maintain such system, the system shall be abandoned and shall comply with the following:

    1. 1.System piping connecting to a utility-provided water system shall be removed or disabled.

    2. 2.The distribution piping system shall be replaced with an approved potable water supply piping system. Where an existing potable water pipe system is already in place, the fixtures shall be connected to the existing system.

    3. 3.The storage tank shall be secured from accidental access by sealing or locking tank inlets and access points, or filled with sand or equivalent.

    P2910.13 Separation requirements for nonpotable water piping.

    Nonpotable water collection and distribution piping and reclaimed water piping shall be separated from the building sewer and potable water piping underground by 5 feet (1524 mm) of undisturbed or compacted earth. Nonpotable water collection and distribution piping shall not be located in, under or above cesspools, septic tanks, septic tank drainage fields or seepage pits. Buried nonpotable water piping shall comply with the requirements of Section P2604.

    Exceptions:

    1. 1.The required separation distance shall not apply where the bottom of the nonpotable water pipe within 5 feet (1524 mm) of the sewer is not less than 12 inches (305 mm) above the top of the highest point of the sewer and the pipe materials conforms to Table P3002.2.

    2. 2.The required separation distance shall not apply where the bottom of the potable water service pipe within 5 feet (1524 mm) of the nonpotable water pipe is not less than 12 inches (305 mm) above the top of the highest point of the nonpotable water pipe and the pipe materials comply with the requirements of Table P2906.5.

    3. 3.The required separation distance shall not apply where a nonpotable water pipe is located in the same trench with a building sewer that is constructed of materials that comply with the requirements of Table P3002.2.

    4. 4.The required separation distance shall not apply where a nonpotable water pipe crosses a sewer pipe provided that the nonpotable water pipe is sleeved to not less than 5 feet (1524 mm) horizontally from the sewer pipe centerline on both sides of such crossing, with pipe materials that comply with Table P3002.2.

    5. 5.The required separation distance shall not apply where a potable water service pipe crosses a nonpotable water pipe, provided that the potable water service pipe is sleeved for a distance of not less than 5 feet (1524 mm) horizontally from the centerline of the nonpotable pipe on both sides of such crossing, with pipe materials that comply with Table P3002.2.

    6. 6.The required separation distance shall not apply to irrigation piping located outside of a building and downstream of the backflow preventer where nonpotable water is used for outdoor applications.

    P2910.14 Outdoor outlet access.

    Sillcocks, hose bibs, wall hydrants, yard hydrants and other outdoor outlets supplied by nonpotable water shall be located in a locked vault or shall be operable only by means of a removable key.

    SECTIONP2911
    ON-SITE NONPOTABLE WATER REUSE SYSTEMS

    P2911.1 General.

    The provisions of this section shall govern the construction, installation, alteration and repair of on-site nonpotable water reuse systems for the collection, storage, treatment and distribution of on-site sources of nonpotable water as permitted by the jurisdiction.

    P2911.2 Sources.

    On-site nonpotable water reuse systems shall collect waste discharge only from the following sources: bathtubs, showers, lavatories, clothes washers and laundry trays. Water from other approved nonpotable sources including swimming pool backwash operations, air conditioner condensate, rainwater, foundation drain water, fluid cooler discharge water and fire pump test water shall be permitted to be collected for reuse by on-site nonpotable water reuse systems, as approved by the building official and as appropriate for the intended application.

    P2911.2.1 Prohibited sources.

    Reverse osmosis system reject water, water softener backwash water, kitchen sink wastewater, dishwasher wastewater and wastewater containing urine or fecal matter shall not be collected for reuse within an on- site nonpotable water reuse system.

    P2911.3 Traps.

    Traps serving fixtures and devices discharging waste water to on-site nonpotable water reuse systems shall comply with the Section P3201.2.

    P2911.4 Collection pipe.

    On-site nonpotable water reuse systems shall utilize drainage piping approved for use within plumbing drainage systems to collect and convey untreated water for reuse. Vent piping approved for use within plumbing venting systems shall be utilized for vents within the gray-water system. Collection and vent piping materials shall comply with Section P3002.

    P2911.4.1 Installation.

    Collection piping conveying untreated water for reuse shall be installed in accordance with Section P3005.

    P2911.4.2 Joints.

    Collection piping conveying untreated water for reuse shall utilize joints approved for use with the distribution piping and appropriate for the intended applications as specified in Section P3002.

    P2911.4.3 Size.

    Collection piping conveying untreated water for reuse shall be sized in accordance with drainage sizing requirements specified in Section P3005.4.

    P2911.4.4 Marking.

    Additional marking of collection piping conveying untreated water for reuse shall not be required beyond that required for sanitary drainage, waste and vent piping by the Chapter 30.

    P2911.5 Filtration.

    Untreated water collected for reuse shall be filtered as required for the intended end use. Filters shall be accessible for inspection and maintenance. Filters shall utilize a pressure gauge or other approved method to provide indication when a filter requires servicing or replacement. Filters shall be installed with shutoff valves immediately upstream and downstream to allow for isolation during maintenance.

    P2911.6 Disinfection.

    Nonpotable water collected on site for reuse shall be disinfected, treated or both to provide the quality of water needed for the intended end-use application. Where the intended end-use application does not have requirements for the quality of water, disinfection and treatment of water collected on site for reuse shall not be required. Nonpotable water collected on site containing untreated gray water shall be retained in collection reservoirs for not more than 24 hours.

    P2911.6.1 Gray water used for fixture flushing.

    Gray water used for flushing water closets and urinals shall be disinfected and treated by an on-site water reuse treatment system complying with NSF 350.

    P2911.7 Storage tanks.

    Storage tanks utilized in on-site nonpotable water reuse systems shall comply with Section P2910.9 and Sections P2911.7.1 through P2911.7.3.

    P2911.7.1 Location.

    Storage tanks shall be located with a minimum horizontal distance between various elements as indicated in Table P2911.7.1.

    TABLE P2911.7.1

    LOCATION OF NONPOTABLE WATER REUSE STORAGE TANKS

    ELEMENTMINIMUM HORIZONTAL DISTANCE FROM STORAGE TANK (feet)
    Critical root zone (CRZ) of protected trees2
    Lot line adjoining private lots5
    Seepage pits5
    Septic tanks5
    Water wells50
    Streams and lakes50
    Water service5
    Public water main10

    For SI: 1 foot = 304.8 mm

    P2911.7.2 Inlets.

    Storage tank inlets shall be designed to introduce water into the tank with minimum turbulence, and shall be located and designed to avoid agitating the contents of the storage tank.

    P2911.7.3 Outlets.

    Outlets shall be located not less than 4 inches (102 mm) above the bottom of the storage tank, and shall not skim water from the surface.

    P2911.8 Valves.

    Valves shall be supplied on on-site nonpotable water reuse systems in accordance with Sections P2911.8.1 and P2911.8.2.

    P2911.8.1 Bypass valve.

    One three-way diverter valve certified to NSF 50 or other approved device shall be installed on collection piping upstream of each storage tank, or drainfield, as applicable, to divert untreated on-site reuse sources to the sanitary sewer to allow servicing and inspection of the system. Bypass valves shall be installed downstream of fixture traps and vent connections. Bypass valves shall be labeled to indicate the direction of flow, connection and storage tank or drainfield connection. Bypass valves shall be installed in accessible locations. Two shutoff valves shall not be installed to serve as a bypass valve.

    P2911.8.2 Backwater valve.

    Backwater valves shall be installed on each overflow and tank drain pipe. Backwater valves shall be in accordance with Section P3008.

    P2911.9 Pumping and control system.

    Mechanical equipment including pumps, valves and filters shall be accessible and removable in order to perform repair, maintenance and cleaning. The minimum flow rate and flow pressure delivered by the pumping system shall be appropriate for the application and in accordance with Section P2903.

    P2911.10 Water-pressure-reducing valve or regulator.

    Where the water pressure supplied by the pumping system exceeds 80 psi (552 kPa) static, a pressure-reducing valve shall be installed to reduce the pressure in the nonpotable water distribution system piping to 80 psi (552 kPa) static or less. Pressure-reducing valves shall be specified and installed in accordance with Section P2903.3.1.

    P2911.11 Distribution pipe.

    Distribution piping utilized in on-site nonpotable water reuse systems shall comply with Sections P2911.11.1 through P2911.11.3.

    Exception: Irrigation piping located outside of the building and downstream of a backflow preventer.

    P2910.11.1 Materials, joints and connections.

    Distribution piping shall conform to the standards and requirements specified in Section P2906 for nonpotable water.

    P2911.11.2 Design.

    On-site nonpotable water reuse distribution piping systems shall be designed and sized in accordance with Section P2903 for the intended application.

    P2911.11.3 Marking.

    On-site nonpotable water distribution piping labeling and marking shall comply with Section P2901.2

    P2911.12 Tests and inspections.

    Tests and inspections shall be performed in accordance with Sections P2911.12.1 through P2911.12.6.

    P2911.12.1 Collection pipe and vent test.

    Drain, waste and vent piping used for on-site water reuse systems shall be tested in accordance with Section P2503.

    P2911.12.2 Storage tank test.

    Storage tanks shall be tested in accordance with Section P2910.11.

    P2911.12.3 Water supply system test.

    The testing of makeup water supply piping and distribution piping shall be conducted in accordance with Section P2503.7.

    P2911.12.4 Inspection and testing of backflow prevention assemblies.

    The testing of backflow preventers and backwater valves shall be conducted in accordance with Section P2503.8.

    P2911.12.5 Inspection of vermin and insect protection.

    Inlets and vents to the system shall be inspected to verify that each is protected to prevent the entrance of insects and vermin into the storage tank and piping systems in accordance with Section P2910.7.

    P2911.12.6 Water quality test.

    The quality of the water for the intended application shall be verified at the point of use in accordance with the requirements of the jurisdiction.

    P2911.13 Operation and maintenance manuals.

    Operation and maintenance materials shall be supplied with nonpotable on-site water reuse systems in accordance with Sections P2910.13.1 through P2910.13.4.

    P2911.13.1 Manual.

    A detailed operations and maintenance manual shall be supplied in hard-copy form for each system.

    P2911.13.2 Schematics.

    The manual shall include a detailed system schematic, the location of system components and a list of system components that includes the manufacturers and model numbers of the components.

    P2911.13.3 Maintenance procedures.

    The manual shall provide a schedule and procedures for system components requiring periodic maintenance. Consumable parts including filters shall be noted along with part numbers.

    P2911.13.4 Operations procedures.

    The manual shall include system startup and shutdown procedures. The manual shall include detailed operating procedures for the system.

    SECTIONP2912
    NONPOTABLE RAINWATER COLLECTION AND DISTRIBUTION SYSTEMS

    P2912.1 General.

    The provisions of this section shall govern the construction, installation, alteration, and repair of rainwater collection and conveyance systems for the collection, storage, treatment and distribution of rainwater for nonpotable applications, as permitted by the jurisdiction.

    P2912.2 Collection surface.

    Rainwater shall be collected only from above-ground impervious roofing surfaces constructed from approved materials. Collection of water from vehicular parking or pedestrian walkway surfaces shall be prohibited except where the water is used exclusively for landscape irrigation. Overflow and bleed-off pipes from roof-mounted appliances including, but not limited to, evaporative coolers, water heaters and solar water heaters shall not discharge onto rainwater collection surfaces.

    P2912.3 Debris excluders.

    Downspouts and leaders shall be connected to a roof washer and shall be equipped with a debris excluder or equivalent device to prevent the contamination of collected rainwater with leaves, sticks, pine needles and similar material. Debris excluders and equivalent devices shall be self-cleaning.

    P2912.4 Roof washer.

    An amount of rainwater shall be diverted at the beginning of each rain event, and not allowed to enter the storage tank, to wash accumulated debris from the collection surface. The amount of rainfall to be diverted shall be field adjustable as necessary to minimize storage tank water contamination. The roof washer shall not rely on manually operated valves or devices, and shall operate automatically. Diverted rainwater shall not be drained to the roof surface, and shall be discharged in a manner consistent with the storm water runoff requirements of the jurisdiction. Roof washers shall be accessible for maintenance and service.

    P2912.5 Roof gutters and downspouts.

    Gutters and downspouts shall be constructed of materials that are compatible with the collection surface and the rainwater quality for the desired end use. Joints shall be watertight.

    P2912.5.1 Slope.

    Roof gutters, leaders and rainwater collection piping shall slope continuously toward collection inlets and shall be free of leaks. Gutters and downspouts shall have a slope of not less than 1/8 inch per foot (10.4 mm/m) along their entire length. Gutters and downspouts shall be installed so that water does not pool at any point.

    P2912.5.2 Cleanouts.

    Cleanouts shall be provided in the water conveyance system to allow access to filters, flushes, pipes and downspouts.

    P2912.6 Drainage.

    Water drained from the roof washer or debris excluder shall not be drained to the sanitary sewer. Such water shall be diverted from the storage tank and shall discharge to a location that will not cause erosion or damage to property. Roof washers and debris excluders shall be provided with an automatic means of self-draining between rain events and shall not drain onto roof surfaces.

    P2912.7 Collection pipe.

    Rainwater collection and conveyance systems shall utilize drainage piping approved for use within plumbing drainage systems to collect and convey captured rainwater. Vent piping approved for use within plumbing venting systems shall be utilized for vents within the rainwater system. Collection and vent piping materials shall comply with Section P3002.

    P2912.7.1 Installation.

    Collection piping conveying captured rainwater shall be installed in accordance with Section P3005.3.

    P2912.7.2 Joints.

    Collection piping conveying captured rainwater shall utilize joints approved for use with the distribution piping and appropriate for the intended applications as specified in Section P3003.

    P2912.7.3 Size.

    Collection piping conveying captured rainwater shall be sized in accordance with drainage-sizing requirements specified in Section P3005.4.

    P2912.7.4 Marking.

    Additional marking of collection piping conveying captured rainwater for reuse shall not be required beyond that required for sanitary drainage, waste, and vent piping by Chapter 30.

    P2912.8 Filtration.

    Collected rainwater shall be filtered as required for the intended end use. Filters shall be accessible for inspection and maintenance. Filters shall utilize a pressure gauge or other approved method to provide indication when a filter requires servicing or replacement. Filters shall be installed with shutoff valves installed immediately upstream and downstream to allow for isolation during maintenance.

    P2912.9 Disinfection.

    Where the intended application for rainwater requires disinfection or other treatment or both, it shall be disinfected as needed to ensure that the required water quality is delivered at the point of use.

    P2912.10 Storage tanks.

    Storage tanks utilized in nonpotable rainwater collection and conveyance systems shall comply with Section P2910.9 and Sections P2912.10.1 through P2912.10.3.

    P2912.10.1 Location.

    Storage tanks shall be located with a minimum horizontal distance between various elements as indicated in Table P2912.10.1.

    TABLE P2912.10.1

    LOCATION OF RAINWATER STORAGE TANKS

    ELEMENTMINIMUM HORIZONTAL DISTANCE FROM STORAGE TANK (feet)
    Critical root zone (CRZ) of protected trees2
    Lot line adjoining private lots5
    Seepage pits5
    Septic tanks5

    For SI: 1 foot = 304.8 mm

    P2912.10.2 Inlets.

    Storage tank inlets shall be designed to introduce collected rainwater into the tank with minimum turbulence, and shall be located and designed to avoid agitating the contents of the storage tank.

    P2912.10.3 Outlets.

    Outlets shall be located not less than 4 inches (102 mm) above the bottom of the storage tank and shall not skim water from the surface.

    P2912.11 Valves.

    Valves shall be supplied on rainwater collection and conveyance systems in accordance with Sections P2912.11.1 and P2912.11.2.

    P2912.11.1 Influent diversion.

    A means shall be provided to divert storage tank influent to allow for maintenance and repair of the storage tank system.

    P2912.11.2 Backwater valve.

    Backwater valves shall be installed on each overflow and tank drain pipe. Backwater valves shall be in accordance with Section P3008.

    P2912.12 Pumping and control system.

    Mechanical equipment including pumps, valves and filters shall be easily accessible and removable in order to perform repair, maintenance and cleaning. The minimum flow rate and flow pressure delivered by the pumping system shall appropriate for the application and in accordance with Section P2903.

    P2912.13 Water-pressure-reducing valve or regulator.

    Where the water pressure supplied by the pumping system exceeds 80 psi (552 kPa) static, a pressure-reducing valve shall be installed to reduce the pressure in the rainwater distribution system piping to 80 psi (552 kPa) static or less. Pressure-reducing valves shall be specified and installed in accordance with Section P2903.3.1.

    P2912.14 Distribution pipe.

    Distribution piping utilized in rainwater collection and conveyance systems shall comply with Sections P2912.14.1 through P2912.14.3.

    Exception: Irrigation piping located outside of the building and downstream of a backflow preventer.

    P2912.14.1 Materials, joints and connections.

    Distribution piping shall conform to the standards and requirements specified in Section P2906 for nonpotable water.

    P2912.14.2 Design.

    Distribution piping systems shall be designed and sized in accordance with the Section P2903 for the intended application.

    P2912.14.3 Labeling and marking.

    Nonpotable rainwater distribution piping labeling and marking shall comply with Section P2901.2.

    P2912.15 Tests and inspections.

    Tests and inspections shall be performed in accordance with Sections P2912.15.1 through P2912.15.8.

    P2912.15.1 Roof gutter inspection and test.

    Roof gutters shall be inspected to verify that the installation and slope is in accordance with Section P2912.5.1. Gutters shall be tested by pouring not less than one gallon of water (3.8 L) into the end of the gutter opposite the collection point. The gutter being tested shall not leak and shall not retain standing water.

    P2912.15.2 Roofwasher test.

    Roofwashers shall be tested by introducing water into the gutters. Proper diversion of the first quantity of water in accordance with the requirements of Section P2912.4 shall be verified.

    P2912.15.3 Collection pipe and vent test.

    Drain, waste and vent piping used for rainwater collection and conveyance systems shall be tested in accordance with Section P2503.

    P2912.15.4 Storage tank test.

    Storage tanks shall be tested in accordance with the Section P2910.11.

    P2912.15.5 Water supply system test.

    The testing of makeup water supply piping and distribution piping shall be conducted in accordance with Section P2503.7.

    P2912.15.6 Inspection and testing of backflow prevention assemblies.

    The testing of backflow preventers and backwater valves shall be conducted in accordance with Section P2503.8.

    P2912.15.7 Inspection of vermin and insect protection.

    Inlets and vents to the system shall be inspected to verify that each is protected to prevent the entrance of insects and vermin into the storage tank and piping systems in accordance with Section P2910.7.

    P2912.15.8 Water quality test.

    The quality of the water for the intended application shall be verified at the point of use in accordance with the requirements of the jurisdiction.

    P2912.16 Operation and maintenance manuals.

    Operation and maintenance manuals shall be supplied with rainwater collection and conveyance systems in accordance with Sections P2912.16.1 through P2912.16.4.

    P2912.16.1 Manual.

    A detailed operations and maintenance manual shall be supplied in hard-copy form for each system.

    P2912.16.2 Schematics.

    The manual shall include a detailed system schematic, the location of system components and a list of system components that includes the manufacturers and model numbers of the components.

    P2912.16.3 Maintenance procedures.

    The manual shall provide a maintenance schedule and procedures for system components requiring periodic maintenance. Consumable parts, including filters, shall be noted along with part numbers.

    P2912.16.4 Operations procedures.

    The manual shall include system startup and shutdown procedures, and detailed operating procedures.

    SECTIONP2913
    RECLAIMED WATER SYSTEMS

    P2913.1 General.

    The provisions of this section shall govern the construction, installation, alteration and repair of systems supplying nonpotable reclaimed water.

    P2913.2 Water-pressure-reducing valve or regulator.

    Where the reclaimed water pressure supplied to the building exceeds 80 psi (552 kPa) static, a pressure-reducing valve shall be installed to reduce the pressure in the reclaimed water distribution system piping to 80 psi (552 kPa) static or less. Pressure-reducing valves shall be specified and installed in accordance with Section P2903.3.1

    P2913.3 Reclaimed water systems.

    The design of the reclaimed water systems shall conform to accepted engineering practice.

    P2913.3.1 Distribution pipe.

    Distribution piping shall comply with Sections P2913.3.1.1 through P2913.3.1.3.

    Exception: Irrigation piping located outside of the building and downstream of a backflow preventer.

    P2913.3.1.1Materials, joints and connections.

    Distribution piping conveying reclaimed water shall conform to standards and requirements specified in Section P2905 for nonpotable water.

    P2913.3.1.2Design.

    Distribution piping systems shall be designed and sized in accordance with Section P2903 for the intended application.

    P2913.3.1.3Labeling and marking.

    Nonpotable rainwater distribution piping labeling and marking shall comply with Section P2901.2.

    P2913.4 Tests and inspections.

    Tests and inspections shall be performed in accordance with Sections P2913.4.1 and P2913.4.2.

    P2913.4.1 Water supply system test.

    The testing of makeup water supply piping and reclaimed water distribution piping shall be conducted in accordance with Section P2503.7.

    P2913.4.2 Inspection and testing of backflow prevention assemblies.

    The testing of backflow preventers shall be conducted in accordance with Section P2503.8.