Chapter 16: Duct Systems

BASIC READ ONLY
  • Open Link
  • Open Link In New Tab
  • Copy Link

Chapter 16:
Duct Systems

General Comments

This chapter addresses duct systems by instituting requirements for the protection of the occupants of the building and the building itself. This chapter regulates the materials and methods of construction. Duct construction affects the performance of the entire air distribution system.

Section M1601 contains the material requirements that are generally applied to all duct construction and installation. Section M1602 contains regulations for return air.

Purpose

Chapter 16 contains requirements for the installation of supply, return and exhaust air systems. The chapter contains no information on the design of these systems from the standpoint of air movement, but it is concerned with the structural integrity of the systems and the overall impact of the systems on the fire-safety performance of the building. Design considerations such as duct sizing, maximum efficiency, cost effectiveness, occupant comfort and convenience are the responsibility of the designer.

SECTION M1601
DUCT CONSTRUCTION

M1601.1 Duct design.

Duct systems serving heating, cooling and ventilation equipment shall be installed in accordance with the provisions of this section and ACCA Manual D, the appliance manufacturer’s installation instructions or other approved methods.

❖ Material and construction requirements for duct systems can be divided into two major categories: those for above-ground ducts and those for underground ducts. The demands placed on each of these types of duct systems are different; therefore, they are treated separately in the code and in the following commentary.

Adequately sized supply air and return air ductwork is essential for efficient and proper circulation of conditioned air. Ducts must be large enough to allow sufficient airflow through appliances to satisfy refrigerant coil airflow demands and to avoid excessive temperature rise. As a practical matter, restriction of the supply duct system is an infrequently encountered problem. However, inadequately sized return systems are often found in the field, particularly on heat pump installations. The code does not provide specific requirements for sizing duct systems, but relies on ACCA Manual D, the appliance manufacturer or other sizing criteria approved by the code official.

M1601.1.1 Above-ground duct systems.

Above-ground duct systems shall conform to the following:

  1. 1. Equipment connected to duct systems shall be designed to limit discharge air temperature to not greater than 250°F (121°C).

  2. 2. Factory-made ducts shall be listed and labeled in accordance with UL 181 and installed in accordance with the manufacturer’s instructions.

  3. 3. Fibrous glass duct construction shall conform to the SMACNA Fibrous Glass Duct Construction Standards or NAIMA Fibrous Glass Duct Construction Standards.

  4. 4. Field-fabricated and shop-fabricated metal and flexible duct constructions shall conform to the SMACNA HVAC Duct Construction StandardsMetal and Flexible except as allowed by Table M1601.1.1. Galvanized steel shall conform to ASTM A653.

  5. 5. The use of gypsum products to construct return air ducts or plenums is permitted, provided that the air temperature does not exceed 125°F (52°C) and exposed surfaces are not subject to condensation.

  6. 6. Duct systems shall be constructed of materials having a flame spread index of not greater than 200.

  7. 7. Stud wall cavities and the spaces between solid floor joists to be used as air plenums shall comply with the following conditions:

    1. 7.1. These cavities or spaces shall not be used as a plenum for supply air.

    2. 7.2. These cavities or spaces shall not be part of a required fire-resistance-rated assembly.

    3. 7.3. Stud wall cavities shall not convey air from more than one floor level.

    4. 7.4. Stud wall cavities and joist-space plenums shall be isolated from adjacent concealed spaces by tight-fitting fireblocking in accordance with Section R302.11. Fireblocking materials used for isolation shall comply with Section R302.11.1.

    5. 7.5. Stud wall cavities in the outside walls of building envelope assemblies shall not be utilized as air plenums.

    6. 7.6. Building cavities used as plenums shall be sealed.

  8. 8. Volume dampers, equipment and other means of supply, return and exhaust air adjustment used in system balancing shall be provided with access.

❖ Metal ducts are usually constructed of galvanized sheet steel. Duct size is based on required airflow, system pressure, flow velocity and pressure losses caused by friction. Duct material thickness is determined by duct size, static pressure of the system, distance between supports and whether the duct is reinforced. Metal ducts must be constructed with the minimum thicknesses specified in Table M1601.1.1, which bases the minimum required duct thickness on the geometry of the duct, the material used and the major dimension of the duct (the diameter for round ducts and the widest side for rectangular ducts).

Metallic ducts must be constructed to comply with the requirements contained in SMACNA HVAC Duct Construction Standards—Metal and Flexible. This standard contains information on duct reinforcement, joints, fittings, hangers and supports and other pertinent design information needed to achieve a stable, efficient and durable installation of ductwork. While this standard contains the minimum required thickness of duct materials, ducts that are installed within a single dwelling are allowed to be constructed with the minimum thicknesses specified in Table M1601.1.1.

Factory-made ducts must be tested and classified in accordance with the provisions of UL 181. Only Class 0 and Class 1 are recognized by UL 181. Class 0 indicates flame spread and smoke-developed indices of zero; Class 1 indicates a flame spread index not greater than 25 and a smoke-developed index not greater than 50, when tested to ASTM E84. The exception to the 25 flame spread index for nonmetallic ducts is Item 6 of this section, which is intended to allow the installation of plastic ducts above ground where such ducts have a flame spread index of 200 or less. However, it should be noted that there is an ICC committee formal interpretation that opines that plastic ducts are allowed to be installed above ground only if they meet the Class I flame spread index requirement of 25 and smoke development index of 50. Plastic rigid ducts are typically made of PVC that cannot meet a smoke development index of 50.

UL 181 requires that a nonmetallic duct be tested to determine its fire-performance characteristics, corrosion resistance, mold-growth resistance, humidity resistance, leakage resistance, temperature resistance, erosion resistance and structural performance. Air ducts that conform to the requirements of UL 181 are identified by the manufacturer’s or vendor’s name, rated velocity, negative and positive pressure classification and duct material class.

Fibrous ducts are constructed of a composite material of rigid (high-density) fiberglass board and a factory-applied facing, typically reinforced aluminum. The surface of the fibrous duct that is exposed to the airflow is sealed with a fiber-bonding adhesive that prevents erosion of the fiberglass material. The factory-applied exterior duct-board facing contributes to the strength and rigidity of the composite material, acts as a heat reflector, serves as a vapor barrier and is an integral component of the joining method used to construct fibrous ducts. The material is available in board form for shop or field fabrication into rectangular sections or into 10-sided duct form, which approximates a circular cross section. Factory-built round fibrous glass ducts are also available.

Fibrous ducts take advantage of the inherent insulating qualities of the glass fiber material. The air friction factors for fibrous ducts are higher than those for sheet metal because of the relatively rough surface finish of the former.

Construction of fibrous glass ducts must conform to the requirements of the SMACNA Fibrous Glass Duct Construction Standards or NAIMA Fibrous Glass Duct Construction Standards, which provide details for the design and fabrication of air distribution systems using fibrous glass ducts. The SMACNA and NAIMA standards referenced in this section and the previous section are enforceable extensions of the code.

The maximum discharge temperature permitted by industry standards for warm-air heating systems is 250°F (121°C). This section prohibits nonmetallic ducts from being used in applications in which the air temperature would exceed this maximum because the material has not been tested to withstand higher temperatures, and high temperatures will cause accelerated aging of the duct material.

Gypsum board is a composite material commonly used for the construction of air plenums and shafts. Gypsum board can reduce construction costs because it is a common component of building construction assemblies. By serving a dual purpose, gypsum board eliminates the need for independent duct construction. The use of gypsum board to form ducts and plenums is specifically regulated to prevent deterioration of the gypsum board material. Air temperatures that exceed 125°F (52°C) will, over time, dry both the paper facing and the gypsum of the gypsum board, leading to deterioration of the panel.

Gypsum board can also deteriorate when exposed to moisture, which will happen if the surface temperature of the gypsum board is lower than the airstream dew-point temperature, causing water to condense on the surface of the gypsum board. For these reasons, gypsum board cannot be used for air distribution systems using evaporative cooling equipment. It is further restricted to return-air system applications only, a maximum airstream temperature of 125°F (52° C) and an airstream dew-point temperature continuously below the temperature of the gypsum board surface. Evaporative cooling equipment, such as a “swamp cooler,” uses water as a refrigerant. The resulting addition of moisture to the airstream could cause deterioration of the gypsum board.

Stud spaces and joist spaces have commonly been used as plenums in residential construction (see Section N1103.3.5). These spaces are limited to return air plenums because the negative pressures within the return air plenum with respect to surrounding spaces will decrease the likelihood of spreading smoke to other spaces via the plenum. Also, the temperature and moisture content of heated, cooled and conditioned supply air could cause a fire hazard or deterioration of the construction materials exposed in the spaces.

Note that Section N1103.3.5 prohibits the use of all framing cavities as ducts or plenums.

The space must not be a part of a fire-resistancerated assembly because the ASTM E119 test does not consider the impact of air movement within the assembly on the fire-resistance rating. This restriction is a concession to the convenience and cost-saving potential of this method of moving air. The use of stud spaces inherently means the interconnection of different floor levels by the concealed space. Because of the hazard of such an interconnection, the use of this type of plenum is limited to return air from one floor level only for each independent stud cavity. All cavities not used for air movement must be isolated from the plenum by fireblocking constructed and installed in accordance with the code. The use of stud wall cavities as a plenum in outside walls is prohibited due to the difficulty in sealing the space to prevent outdoor air from infiltrating the cavity, which would increase the heating and cooling loads on the system. Note that Section N1103.3.5 prohibits the use of all framing cavities as ducts or plenums.

Commentary Figure M1601.1.1(1) shows an example of an acceptable stud and joist space installation. The bottom plate of the wall is cut away for the plenum to function, and fireblocking is installed in the joist and stud space to limit communication of the plenum with other spaces. The stud cavity shown is being used to return air from one floor level only, conducting it to the space below, where the air-handling equipment is located. Whether viewed as a shaft or as a duct, a stud-cavity plenum penetrates floor assemblies and is, therefore, subject to the floor penetration protection requirements of Section R302.4.1. Commentary Figure M1601.1.1(2) shows an example of an unacceptable stud and joist space installation. Because air is returned from more than one floor level through the same stud cavity, this section prohibits this type of installation because it creates a direct connection from one floor level to another by means of a concealed cavity. Such direct connections would act as a chase or chimney, allowing fire and smoke to spread quickly upward through the building. Thus, stud-cavity return-air plenums are subject to the same restrictions and requirements as floor openings and penetrations regulated by Section R302.4. Stud-space and joist-space plenums must be viewed as an exception to the fireblocking provisions of Section R302.11 because one or more fireblocks (wall plates) must be removed or relocated to construct the plenums. The code does not mention the type of materials allowed for “panning” the bottom of open joists to create joist-space plenums. Traditionally, sheet metal has been used; however, composite materials are also used. The building official must determine what materials are acceptable for joist panning.

Where stud cavities and joist cavities are used for return air, the negative pressure within such cavities can draw in outdoor air at any point where the cavities are adjacent to attic spaces, crawl spaces and outside walls. Sealing of the interface with attics, crawl spaces and outside walls will reduce unwanted infiltration and improve system efficiency. Because it would be nearly impossible to seal a stud cavity plenum space after the wall board is attached to both sides of the studs, sealing can be accomplished by applying a continuous bead of glue or caulking on the studs, on top and bottom plates and on any fireblocking so that the wall board will be sealed to the structural members, thereby preventing air from entering the cavity from adjacent cavities, attics and crawl spaces. Wood studs are not perfectly straight or uniform; therefore, there will always be some gaps where the wall board does not completely contact the stud.

Commentary Figure M1601.1.1(1).jpg

Commentary Figure M1601.1.1(1)

ACCEPTABLE STUD AND JOIST-SPACE INSTALLATION

Commentary Figure M1601.1.1(2).jpg

Commentary Figure M1601.1.1(2)

UNACCEPTABLE STUD AND JOIST-SPACE PLENUM INSTALLATION

Table M1601.1.1.

TABLE M1601.1.1

DUCT CONSTRUCTION MINIMUM SHEET METAL THICKNESS FOR SINGLE DWELLING UNITSa

ROUND DUCT DIAMETER (inches) STATIC PRESSURE
1/2-inch water gauge 1-inch water gauge
Thickness (inches) Thickness (inches)
Galvanized Aluminum Galvanized Aluminum
< 12 0.013 0.018 0.013 0.018
12 to 14 0.013 0.018 0.016 0.023
15 to 17 0.016 0.023 0.019 0.027
18 0.016 0.023 0.024 0.034
19 to 20 0.019 0.027 0.024 0.034
RECTANGULAR DUCT DIMENSION (inches) STATIC PRESSURE
1/2-inch water gauge 1-inch water gauge
Thickness (inches) Thickness (inches)
Galvanized Aluminum Galvanized Aluminum
≤ 8 0.013 0.018 0.013 0.018
9 to 10 0.013 0.018 0.016 0.023
11 to 12 0.016 0.023 0.019 0.027
13 to 16 0.019 0.027 0.019 0.027
17 to 18 0.019 0.027 0.024 0.034
19 to 20 0.024 0.034 0.024 0.034

For SI: 1 inch = 25.4 mm, 1 inch water gage = 249 Pa.

  1. a.Ductwork that exceeds 20 inches by dimension or exceeds a pressure of 1 inch water gauge shall be constructed in accordance with SMACNA HVAC Duct Construction Standards—Metal and Flexible.

❖ The minimum thicknesses indicated are the low end of the tolerance range for the nominal thicknesses of commonly available sheet materials according to the SMACNA HVAC Duct Construction Standards. The minimum thickness allows the code official to verify that the proper nominal thickness of material is being used. The dimension indicated for rectangular sizes is the largest dimension. The indicated thicknesses for aluminum sheet are for aluminum alloy 3003-H 14. Note a is included to indicate that for ducts having static pressures greater than 1-inch water gauge, and for ducts with a dimension greater than 20 inches (508 mm), the ducts must be designed in accordance with the material thickness and reinforcing requirements of the SMACNA HVAC Duct Construction Standards. The table allows what is commonly referred to as “30 gage” sheet metal.

M1601.1.2 Underground duct systems.

Underground duct systems shall be constructed of approved concrete, clay, metal or plastic. The maximum design temperature for systems utilizing plastic duct and fittings shall be 150°F (66°C). Metal ducts shall be protected from corrosion in an approved manner or shall be completely encased in concrete not less than 2 inches (51 mm) thick. Nonmetallic ducts shall be installed in accordance with the manufacturer’s instructions. Plastic pipe and fitting materials shall conform to cell classification 12454-B of ASTM D1248 or ASTM D1784 and external loading properties of ASTM D2412. Ducts shall slope to a drainage point that has access. Ducts shall be sealed, secured and tested prior to encasing the ducts in concrete or direct burial. Duct tightness shall be verified as required by Section N1103.3. Metallic ducts having an approved protective coating and nonmetallic ducts shall be installed in accordance with the manufacturer’s instructions.

❖ Ducts installed underground must be able to resist the forces imposed on them by the materials that encase them, the forces created by floodwaters in and around them and corrosion. The ASHRAE Handbook of HVAC Systems and Equipment recommends that all underground ducts and fittings be round to provide optimum structural performance. Unlike round ducts, square or rectangular ducts offer little resistance to deformation or collapse caused by the structural loads associated with burial.

Metal ducts must have either a protective coating to resist corrosion or be completely encased in concrete a minimum of 2 inches (52 mm) thick all around. Concrete-encased ducts may eventually corrode; however, the air passageway will be maintained because of the remaining concrete enclosure. All nonmetallic ducts and metallic ducts with factory-applied protective coatings must be approved, and all such duct installations must be in accordance with the manufacturer’s installation instructions. Application of any field-applied protective coating must be approved. Great care must be taken to protect underground ducts from damage prior to placing the concrete or installing the permanent structure above them. Plastic duct and fitting systems designed for underground applications are available and allow corrosion-resistant and waterproof installations.

Plastic ducts have the advantage of being corrosion resistant. The required external loading properties of ASTM D2412 ensure that the pipe has the ability to resist deformation from the loads associated with direct burial. Plastic ducts rapidly lose strength as their temperature approaches their maximum service temperature. At temperatures above 150°F (65.5°C), PVC pipe is substantially weakened and deformation/collapse is possible.

Underground ducts must be sloped to drain to an accessible point in the event that water enters the duct through duct openings or from the subsoil. Water can cause corrosion, deterioration of duct materials, mold growth and duct blockages; therefore, sloping the duct to drain to a collection point will allow removal of water. The code does not require that ducts be watertight. This section requires that the duct be sealed, secured in place and tested before the concrete is poured or the trench is backfilled. It is obviously too late to seal ducts and reseal leaking ducts after concrete or backfill is placed.

M1601.2 Vibration isolators.

Vibration isolators installed between mechanical equipment and metal ducts shall be fabricated from approved materials and shall not exceed 10 inches (254 mm) in length.

❖ Isolators must be built from materials that will withstand the temperatures and pressures of typical conditioned air passing through the duct. The 10-inch (254 mm) length limitation prevents installation of long lengths of nonrigid duct material, which could adversely affect the integrity of the duct system.

M1601.3 Duct insulation materials.

Duct insulation materials shall conform to the following requirements:

  1. 1. Duct coverings and linings, including adhesives where used, shall have a flame spread index not higher than 25, and a smoke-developed index not over 50 when tested in accordance with ASTM E84 or UL 723, using the specimen preparation and mounting procedures of ASTM E2231.

    Exception: Spray application of polyurethane foam to the exterior of ducts in attics and crawl spaces shall be permitted subject to all of the following:

    1. 1. The flame spread index is not greater than 25 and the smoke-developed index is not greater than 450 at the specified installed thickness.

    2. 2. The foam plastic is protected in accordance with the ignition barrier requirements of Sections R316.5.3 and R316.5.4.

    3. 3. The foam plastic complies with the requirements of Section R316.

  2. 2. Duct coverings and linings shall not flame, glow, smolder or smoke when tested in accordance with ASTM C411 at the temperature to which they are exposed in service. The test temperature shall not fall below 250°F (121°C). Coverings and linings shall be listed and labeled.

  3. 3. External reflective duct insulation shall be legibly printed or identified at intervals not greater than 36 inches (914 mm) with the name of the manufacturer, the product R-value at the specified installed thickness and the flame spread and smoke-developed indices. The installed thickness of the external duct insulation shall include the enclosed airspace(s). The product R-value for external reflective duct insulation shall be determined in accordance with ASTM C1668.

  4. 4. External duct insulation and factory-insulated flexible ducts shall be legibly printed or identified at intervals not longer than 36 inches (914 mm) with the name of the manufacturer, the thermal resistance R-value at the specified installed thickness and the flame spread and smoke-developed indices of the composite materials. Spray polyurethane foam manufacturers shall provide the same product information and properties, at the nominal installed thickness, to the customer in writing at the time of foam application. Nonreflective duct insulation product R-values shall be based on insulation only, excluding air films, vapor retarders or other duct components, and shall be based on tested C-values at 75°F (24°C) mean temperature at the installed thickness, in accordance with recognized industry procedures. The installed thickness of duct insulation used to determine its R-value shall be determined as follows:

    1. 4.1. For duct board, duct liner and factory-made rigid ducts not normally subjected to compression, the nominal insulation thickness shall be used.

    2. 4.2. For ductwrap, the installed thickness shall be assumed to be 75 percent (25-percent compression) of nominal thickness.

    3. 4.3. For factory-made flexible air ducts, The installed thickness shall be determined by dividing the difference between the actual outside diameter and nominal inside diameter by two.

    4. 4.4. For spray polyurethane foam, the aged R-value per inch measured in accordance with recognized industry standards shall be provided to the customer in writing at the time of foam application. In addition, the total R-value for the nominal application thickness shall be provided.

❖ Because duct systems connect most rooms in a building, they can provide a path for fire and smoke to travel throughout that building. Duct coverings and linings are exposed to the surrounding environment and to the airstream in the duct. To reduce the possible spread of fire and smoke, duct coverings and linings must be tested to ASTM E84 or UL 723. These materials are limited to a maximum flame spread index of 25 and a smoke-developed index of 50, which correspond to Class 1 material. In addition, duct coverings and linings must be rated for the air temperatures expected; this avoids degradation of these materials.

An exception to the requirement for meeting the flame spread and smoke-developed indices was added to allow spray polyurethane insulation to be applied on the exterior of ducts in attics and crawl spaces as long as all of the requirements of the exception are met. Although the exception requires this foam plastic to be protected by an ignition barrier, Sections 316.5.3 and 316.5.4 allow for deletion of the ignition barrier if the foam plastic material is specifically approved in accordance with Section 316.6.

To verify that duct coverings and linings will not present a fire hazard, these materials must be tested in accordance with ASTM C411 in the form in which they will be installed at their rated temperatures, but to not less than 250°F (121°C). This minimum temperature for testing represents the maximum temperature that industry standards will permit in the airstream of a warm-air heating appliance. It is important that the duct coverings and linings are tested in their composite form rather than having tests conducted on each component that comprises the product (i.e., the insulation, the facing and the adhesive). Each component could pass the ASTM E84 or UL 723 tests individually, but could fail when combined into the final assembly to be installed in the field. Requiring the product to be listed and labeled ensures that the product installed is the same one that was tested.

ASTM E84 and UL 723 indicate the test methods required for duct coverings and linings, including a requirement for testing of systems representative of the actual field installation. ASTM E2231 was added to the code because it contains the specimen preparation and mounting procedures necessary to ensure that the specimen tested in the laboratory is as close as possible to the actual field installation. This will result in a safer field installation where the actual performance of the material can be more accurately predicted.

To assist inspectors, the code requires that duct insulation have a label with the manufacturer’s name, thermal resistance (R), and the flame/smoke indexes. However, because labeling of the exterior of spray polyurethane insulation is not feasible, the code requires that the same information be given, in writing, to the customer at the time of application.

A third-party agency must provide quality control inspections at the manufacturer’s facility in accordance with the requirements for labeling. Testing performed by an independent agency must determine the insulating R-value, the flame spread index and the smoke-developed index. The 36-inch (914 mm) label intervals are intended to increase the likelihood that every cut piece of insulation and flexible duct will have a label.

Reflective duct insulation is a defined term in Chapter 2. It is typically constructed of aluminum foil or metalized film membranes having closed air cells sandwiched between the membranes. The air cells provide R-value and the foil or metalized film acts as a reflector of radiant energy. Reflective duct insulation is often installed with spacers that create an airspace (not to be confused with air films) between the duct surface and the inside surface of the insulation, thereby increasing the overall R-value of the assembly. Items 4.1 through 4.4 of Item 4 do not apply to reflective duct insulation.

The thermal performance of duct insulation is dependent on its “installed” condition including the compressed condition, as is the case for duct wrap insulations other than reflective duct insulation. This section is intended to provide manufacturers, installers and inspectors with specific guidance for meeting the intent of the code. For example, installed fiberglass duct wrap is assumed to have a thickness of 75 percent of the nominal uninstalled thickness. The R-value reduction for the product will account for the decreased thermal resistance caused by compression of the product.

M1601.4 Installation.

Duct installation shall comply with Sections M1601.4.1 through M1601.4.10.

❖ See Sections M1601.4.1 through M1601.4.10.

M1601.4.1 Joints, seams and connections.

Longitudinal and transverse joints, seams and connections in metallic and nonmetallic ducts shall be constructed as specified in SMACNA HVAC Duct Construction Standards—Metal and Flexible and NAIMA Fibrous Glass Duct Construction Standards. Joints, longitudinal and transverse seams, and connections in ductwork shall be securely fastened and sealed with welds, gaskets, mastics (adhesives), mastic-plus-embedded-fabric systems, liquid sealants or tapes. Tapes and mastics used to seal fibrous glass ductwork shall be listed and labeled in accordance with UL 181A and shall be marked “181A-P” for pressure-sensitive tape, “181 A-M” for mastic or “181 A-H” for heat-sensitive tape.

Tapes and mastics used to seal metallic and flexible air ducts and flexible air connectors shall comply with UL 181B and shall be marked “181 B-FX” for pressure-sensitive tape or “181 BM” for mastic. Duct connections to flanges of air distribution system equipment shall be sealed and mechanically fastened. Mechanical fasteners for use with flexible nonmetallic air ducts shall comply with UL 181B and shall be marked 181B-C. Crimp joints for round metallic ducts shall have a contact lap of not less than 1 inch (25 mm) and shall be mechanically fastened by means of not less than three sheet-metal screws or rivets equally spaced around the joint.

Closure systems used to seal all ductwork shall be installed in accordance with the manufacturers’ instructions.

Exceptions:

  1. 1. Spray polyurethane foam shall be permitted to be applied without additional joint seals.

  2. 2. Where a duct connection is made that is partially without access, three screws or rivets shall be equally spaced on the exposed portion of the joint so as to prevent a hinge effect.

  3. 3. For ducts having a static pressure classification of less than 2 inches of water column (500 Pa), additional closure systems shall not be required for continuously welded joints and seams and locking-type joints and seams. This exception shall not apply to snap-lock and button-lock type joints and seams that are located outside of conditioned spaces.

❖ Duct sealing is commonly overlooked or poorly performed. The U.S. Environmental Protection Agency (EPA) estimates that 20 percent of the energy efficiency of heating and cooling systems can be lost due to duct air leaks located outside of the conditioned space. With the increased focus on lowering energy use in all types of buildings, substantial gains in energy efficiency can be obtained by making sure that ducts are “substantially” airtight. While approved duct materials have low permeability, the joints in these materials as well as the joints in the connections of these materials to fittings/equipment must be carefully sealed to achieve a “substantially” airtight condition.

Field experience has shown that poor workmanship and failure to follow manufacturer’s instructions has resulted in a high incidence of joint failure in attics and crawl spaces. It is not uncommon to find that air is supplied to or air is returned from an attic because of a separated duct joint. This is obviously a tremendous waste of energy.

In general, joints must be sealed using tapes, mastics, liquid sealants, gasketing or other approved closure systems. A “closure system” consists of the materials and an installation method used to make the joint substantially airtight. This section specifically addresses sealing for three types of duct material which can be accomplished as follows:

  • Rigid fibrous glass ductwork must be sealed in accordance with UL 181A. Where pressure-sensitive tape is used, the exterior of the tape must be factory marked with the designation “181 A-P.” Where mastic is used, the container label must indicate “181 A-M.” Where heat-sensitive tape is used, the exterior of the tape must be factory marked with the designation “181 A-H.”

  • Metallic ducts, flexible air ducts and flexible air connectors must be sealed in accordance with UL 181B. Where pressure-sensitive tape is used, the exterior of the tape must be factory marked with the designation “181B F-X.” Where mastic is used, the container label must indicate “181 B-M.”

In addition to sealing, joints must also be mechanically fastened. In other words, sealing by itself is not a substitute for the mechanical fastening of a duct joint. Two examples are taping a flexible air duct to a fitting and “gluing” a round metal duct joint with caulking. Both practices are not acceptable fastening methods. Mechanical fasteners must be used. This section specifically addresses the mechanical fastening of three types of duct material as follows:

  • Rigid fibrous glass ductwork must be mechanically attached to flanges of air distribution equipment or sheet metal fittings. For example, where a rigid fibrous glass duct connects to a sheet metal flange of an air handler, sheet metal screws (with flat washers) can be used to attach the duct board to the metal flange. Where fittings for other ducts must attach to the duct, a “spin in,” “twist lock” or “tabbed” collar provides for the required mechanical fastening of the joint.

  • Flexible air ducts and flexible air connectors must be fastened to collar stubs or duct connector sleeves. Worm gear band clamps and plastic cable ties are most commonly used for fastening. Where cable ties are used, they must comply with UL 181B and be marked “181-C.” The collar stubs should have a convex bead formed on the circumference of the fitting to prevent the flexible duct from being pulled off the connector. Commentary Figure M1601.4.1(1) shows installation guidelines for flexible air ducts and flexible air connectors.

  • Round metal duct with crimp joints must have an overlap of at least 1 inch (25.4 mm). At least three sheet metal screws or rivets must be installed, equally spaced around the duct, for mechanical fastening of the joint. A minimum of 3 fasteners creates a rigid joint that will not allow a hinge movement.

Exception 1 allows spray polyurethane foam insulation to serve as a duct joint sealing method. Spray foam insulation has strong adhesive properties and low porosity such that its application provides an equivalent air-tight condition as compared to other closure systems. Exception 2 allows the spacing of the screws or rivets on round metal ducts to be equally spaced on the portion of duct joint that can be accessed, if the entire perimeter of the joint cannot be accessed. The installation of duct work in close quarters such as in joist spaces and chases, often limits access to the complete circumference of the joint. The installation of three screws or rivets in the portion of joint that can be accessed is a reasonable accommodation for such conditions. For air systems with a static pressure of less than 2 inches water column (0.50 kPa), Exception 3 allows for longitudinal (including spiral-type) welded joints and locking-type joints and seams to not be sealed. A welded or locking-type (e.g., Pittsburgh lock) joint is sufficiently air tight at low pressures such that joint sealing would be of limited value. Snap-lock and button-lock type joints located outside of conditioned spaces (e.g., crawl spaces, attics, outdoors) do not fall under Exception 3 and must be sealed because such joints will leak and the leakage will not be into the conditioned space. Note that some duct manufacturers provide snap-lock joints that contain a factory-applied sealant in the locking groove that serves to seal the joint when assembled. S-slip joints, drive joints and lap joints must always be sealed. See Commentary Figure M1601.4.1(2).

Commentary Figure M1601.4.1(1).jpgCommentary Figure M1601.4.1(1)_1.jpgCommentary Figure M1601.4.1(1)_2.jpgCommentary Figure M1601.4.1(1)_3.jpgCommentary Figure M1601.4.1(1)_4.jpgCommentary Figure M1601.4.1(1)_5.jpgCommentary Figure M1601.4.1(1)_6.jpg

Commentary Figure M1601.4.1(1)

INSTALLATION INSTRUCTIONS FOR FLEXIBLE AIR DUCTS AND AIR CONNECTORS (Courtesy of Air Diffusion Council)

Commentary Figure M1601.4.1(2).jpg

Commentary Figure M1601.4.1(2)

SNAP-LOCK AND BUTTON-LOCK DUCT JOINTS

M1601.4.2 Duct lap.

Crimp joints for round and oval metal ducts shall be lapped not less than 1 inch (25 mm) and the male end of the duct shall extend into the adjoining duct in the direction of airflow.

❖ The crimped end of a round duct is the male end and it points in the direction of flow. The minimum required lap creates joint stability and allows for proper mechanical fastening. Crimped joints can be exceptionally leaky, depending on the length of lap and the depth of the crimp valleys. Section M1601.4.1 requires such joints to be sealed.

M1601.4.3 Plastic duct joints.

Joints between plastic ducts and plastic fittings shall be made in accordance with the manufacturer’s installation instructions.

❖ Plastic ducts are typically installed underground. If plastic ducts are installed, this section requires the installer to follow the duct manufacturer’s instructions for making joints in the duct. Some manufacturers require joints to be solvent cemented while others require the joints to be caulked. Section M1601.4.1 does not address plastic ducts.

M1601.4.4 Support.

Factory-made ducts listed in accordance with UL 181 shall be supported in accordance with the manufacturer’s installation instructions. Field- and shop-fabricated fibrous glass ducts shall be supported in accordance with the SMACNA Fibrous Glass Duct Construction Standards or the NAIMA Fibrous Glass Duct Construction Standards. Field- and shop-fabricated metal and flexible ducts shall be supported in accordance with the SMACNA HVAC Duct Construction Standards—Metal and Flexible.

❖ These material requirements and the 10-foot (3048 mm) maximum spacing requirement prescribe structural support for metal ductwork to limit deflection and maintain alignment. Nonmetallic ducts must be supported in accordance with the manufacturer’s installation instructions because these ducts are produced in various configurations. See Commentary Figure M1601.4.1(1) for information on nonmetallic duct support.

M1601.4.5 Fireblocking.

Duct installations shall be fire-blocked in accordance with Section R302.11.

❖ Section R602.8 refers to Section R302.11 and requires that all openings around ducts at ceiling and floor levels must be fireblocked. Fireblocking retards the spread of fire to other areas in the dwelling.

M1601.4.6 Duct insulation.

Duct insulation shall be installed in accordance with the following requirements:

  1. 1.A vapor retarder having a permeance of not greater than 0.05 perm [2.87 ng/(s × m2 × Pa)] in accordance with ASTM E96, or aluminum foil with a thickness of not less than 2 mils (0.05 mm), shall be installed on the exterior of insulation on cooling supply ducts that pass through unconditioned spaces conducive to condensation except where the insulation is spray polyurethane foam with a water vapor permeance of not greater than 3 perms per inch [1722 ng/(s × m2 × Pa)] at the installed thickness.

  2. 2.Outdoor duct systems shall be protected against the elements.

  3. 3.Duct coverings shall not penetrate a fireblocked wall or floor.

❖ Where a duct is installed outdoors or in an unconditioned area (such as an attic or crawl space), it can be exposed to humidity and temperature differentials that can create condensation on the outside of the duct. A vapor retarder must be installed on the exterior of the duct to protect the duct and/or insulation from damage caused by moisture. Duct insulation and coverings must not penetrate fireblocked assemblies. If the exterior insulation and vapor retarder burn in a fire, a pathway will open for the fire to spread through the penetration in the structure for the duct.

The exterior of cooling supply ducts that are insulated with spray polyurethane foam which has a maximum water vapor permeance of 3 perm per inch does not require a vapor retarder or aluminum foil. Spray polyurethane foam has been successfully used without a vapor barrier in other applications, such as exterior walls. The natural low permeance of the installed material makes a vapor barrier over the spray foam insulation redundant.

M1601.4.7 Factory-made air ducts.

Factory-made air ducts shall not be installed in or on the ground, in tile or metal pipe, or within masonry or concrete.

❖ Factory-made air ducts must be listed and labeled for underground installations. Ducts not listed for inground installations might not have sufficient strength to withstand the loads applied by these types of installations and might not be suitable for high-moisture areas.

M1601.4.8 Duct separation.

Ducts shall be installed with not less than 4 inches (102 mm) separation from earth except where they meet the requirements of Section M1601.1.2.

❖ A physical separation from earth is the best method of protecting metallic and nonmetallic ducts from the effects of corrosion and moisture.

M1601.4.9 Ducts located in garages.

Ducts in garages shall comply with the requirements of Section R302.5.2.

❖ Ducts in garages and ducts penetrating separation walls or ceilings between garages and living spaces must be designed to prevent fire and smoke from easily entering the living spaces (see commentary, Sections R302.5.2 and M1601.6). Section R302.5.2 is intended to protect the penetration of the fire separation between a dwelling and an attached garage, and also to prevent contaminants in the garage from entering the living spaces. The code assumes that the 26-gage steel ductwork and the furnace/air-handler casing will offer a significant impediment to the spread of fire from the garage to the dwelling interior. Placing furnaces, air handlers and ductwork in unconditioned spaces is becoming less common because of energy saving efforts. Concern has been expressed by some that having a furnace/air handler with nonmetallic access doors to the blower or filter compartments creates a weak spot in the steel duct barrier. It is the author’s opinion that Section R302.5.2 is violated where any air-handling equipment in the garage has access doors that are less resistant to fire than 26 gage steel ducts. The code official can approve materials other than steel in accordance with Sections R302.5.2 and R104.11.

M1601.4.10 Flood hazard areas.

In flood hazard areas as established by Table R301.2, duct systems shall be located or installed in accordance with Section R322.1.6.

❖ In buildings and structures located in flood hazard areas, ducts must be installed above the design flood elevation or must be capable of preventing water from entering the ducts and capable of withstanding the forces of buoyancy and moving water (see commentary, Section R322.1.6).

M1601.5 Under-floor plenums.

Under-floor plenums shall be prohibited in new structures. Modification or repairs to underfloor plenums in existing structures shall conform to the requirements of this section.

❖ New structures must not be designed to use crawl spaces as plenums. This practice is quite rare and such arrangements can waste energy and negatively affect indoor air quality. Because some existing structures might still utilize under-floor plenums, this section allows those arrangements to continue to exist even if modifications or repairs are performed to those systems. See Commentary Figure M1601.5 for an example of an under-floor plenum system.

Commentary Figure M1601.5.jpg

For SI: 1 inch = 25.4 mm.

Commentary Figure M1601.5

UNDER-FLOOR PLENUM

M1601.5.1 General.

The space shall be cleaned of loose combustible materials and scrap, and shall be tightly enclosed. The ground surface of the space shall be covered with a moisture barrier having a thickness of not less than 4 mils (0.1 mm). Plumbing waste cleanouts shall not be located within the space.

Exception: Plumbing waste cleanouts shall be permitted to be located in unvented crawl spaces that receive conditioned air in accordance with Section R408.3.

❖ Loose combustible scrap must be removed from an under-floor space used as a plenum. The space must be substantially airtight because the furnace will place the plenum under a slight positive pressure to force conditioned air out of the registers into the rooms above. If there are leaks in the plenum walls, the conditioned air will escape to the outdoors and result in energy loss and the creation of negative pressure in the living space.

Efforts to rod drains through cleanouts located in under-floor plenums could create spills and splashes of sewage in the plenum and cleanout openings might be carelessly left open allowing sewer gases to enter the plenum. Because this would create an insanitary air condition for the building occupants, plumbing cleanouts are prohibited in these spaces. An issue that often comes up is whether fuel gas piping is prohibited in under-floor plenums. Chapter 24 contains the requirements for fuel-gas piping and does not prohibit gas piping in such spaces.

M1601.5.2 Materials.

The under-floor space, including the sidewall insulation, shall be formed by materials having flame spread index values not greater than 200 when tested in accordance with ASTM E84 or UL 723.

❖ The enclosing materials of an under-floor plenum, including the sidewall insulation, are limited to materials having a flame spread index less than or equal to 200 because the plenum space could introduce smoke and fire to the living space.

M1601.5.3 Furnace connections.

A duct shall extend from the furnace supply outlet to not less than 6 inches (152 mm) below the combustible framing. This duct shall comply with the provisions of Section M1601.1. A noncombustible receptacle shall be installed below any floor opening into the plenum in accordance with the following requirements:

  1. 1.The receptacle shall be securely suspended from the floor members and shall be not more than 18 inches (457 mm) below the floor opening.

  2. 2.The area of the receptacle shall extend 3 inches (76 mm) beyond the opening on all sides.

  3. 3.The perimeter of the receptacle shall have a vertical lip not less than 1 inch (25 mm) in height at the open sides.

❖ A noncombustible receptacle, (i.e., a pan) must be installed below each of the supply openings in the floor. This receptacle (pan) must be suspended from the floor members and must be located not greater than 18 inches (457 mm) below the floor opening so that items and debris dropped into floor openings can be easily retrieved by reaching down through the opening. The receptacle (pan) must extend 3 inches (76 mm) beyond the opening on all sides and have a vertical lip at least 1-inch (25 mm) high to keep items from sliding or rolling off the edges of the pan. The requirement for the pan material to be noncombustible anticipates the potential for burning material being dropped into the opening.

M1601.5.4 Access.

Access to an under-floor plenum shall be provided through an opening in the floor with minimum dimensions of 18 inches by 24 inches (457 mm by 610 mm).

❖ An 18-inch by 24-inch (457 mm by 610 mm) or larger opening in the floor is required to provide access to the under-floor plenum to permit maintenance and repairs in the crawl space.

M1601.5.5 Furnace controls.

The furnace shall be equipped with an automatic control that will start the air-circulating fan when the air in the furnace bonnet reaches a temperature not higher than 150°F (66°C). The furnace shall additionally be equipped with an approved automatic control that limits the outlet air temperature to 200°F (93°C).

❖ Because exposed wood joists and flooring often form under-floor plenums, the outlet air temperature from the furnace must be limited to 200°F (93°C).

Furnaces must also be equipped with an automatic control that starts the air circulation fan before the air temperature in the furnace at the heat exchanger exceeds 150°F (66°C). This requirement serves to limit plenum air temperature. Note that replacement furnaces will not likely be available that can meet these control requirements and altering the furnaces would violate the listing of the appliance.

M1601.6 Independent garage HVAC systems.

Furnaces and air-handling systems that supply air to living spaces shall not supply air to or return air from a garage.

❖ This section prohibits a furnace or air-handler from serving both living spaces and garages. If a garage is conditioned, it must be done so by an independent system. For example, if a furnace supplies air to a garage and also to a dwelling interior, the air to the garage will be lost because return air cannot be taken from a garage. The result will be negative pressure in the dwelling with respect to the garage, and the condition will cause contaminants in the garage to migrate into the dwelling (see M1602.2, Item 4).

Garages could contain contaminants that would negatively affect air quality in the living spaces. Pressure differentials and duct leakage could cause contaminants to migrate into the living space. Requiring that the living space system be completely separate ensures that contaminants will not be introduced into the living spaces.

SECTION M1602
RETURN AIR

M1602.1 Outdoor air openings.

Outdoor intake openings shall be located in accordance with Section R303.5.1. Opening protection shall be in accordance with Section R303.6

❖ See Sections R303.5.1 and R303.6.

M1602.2 Return air openings.

Return air openings for heating, ventilation and air-conditioning systems shall comply with all of the following:

  1. 1.Openings shall not be located less than 10 feet (3048 mm) measured in any direction from an open combustion chamber or draft hood of another appliance located in the same room or space.

  2. 2.The amount of return air taken from any room or space shall be not greater than the flow rate of supply air delivered to such room or space.

  3. 3.Return and transfer openings shall be sized in accordance with the appliance or equipment manufacturer’s installation instructions, Manual D or the design of the registered design professional.

  4. 4.Return air shall not be taken from a closet, bathroom, toilet room, kitchen, garage, mechanical room, boiler room, furnace room or unconditioned attic.

    Exceptions:

    1. 1.Taking return air from a kitchen is not prohibited where such return air openings serve the kitchen only, and are located not less than 10 feet (3048 mm) from the cooking appliances.

    2. 2.Dedicated forced-air systems serving only the garage shall not be prohibited from obtaining return air from the garage.

  5. 5.For other than dedicated HVAC systems, return air shall not be taken from indoor swimming pool enclosures and associated deck areas except where the air in such spaces is dehumidified,

  6. 6.Taking return air from an unconditioned crawl space shall not be accomplished through a direct connection to the return side of a forced-air furnace. Transfer openings in the crawl space enclosure shall not be prohibited.

  7. 7.Return air from one dwelling unit shall not be discharged into another dwelling unit.

❖ This text is a revised version of what was formerly located in Section 918 under forced-air furnaces. The return air provisions from Section 918 were collected, reformatted, revised in some cases, clarified as to intent and then relocated to Chapter 6 because these provisions are broadly applicable and not solely associated with forced-air furnaces. Return air is defined and is typically partially or completely recirculated, thus it is important to control the locations from which return air is taken to prevent contamination.

Item 1 expresses the concern for drawing combustion products into the return air intakes.

Item 2 is intended to prevent the creation of negative pressures that would interfere with the function of vents, chimneys and fuel-fired appliances. Such interference can cause appliance malfunction, unsafe operation and spillage of combustion products into the space served by the return air system.

Item 3 defers the sizing of return air openings and transfer openings to the design professional, the appliance manufacturer or the ACCA Manual D for residential duct systems. The aggregate area of all ducts or openings that convey return air back to the furnace must be adequate to allow the required airflow through the furnace. A furnace that is “starved” for return air will produce an abnormal temperature rise across the heat exchanger, which is a fire hazard and likely detrimental to the furnace.

Item 4 addresses potential sources of air contaminants, and the creation of pressure differentials that can draw combustion products and contaminants from garages, chimneys, vents and appliances. Return air openings might interfere with the ability of exhaust systems and hoods to capture the target contaminants or effluent. Taking return air from an unconditioned attic would also cause significant energy waste. Exception 1 to Item 4 recognizes that return air could be necessary for conditioning a kitchen and contamination of the return air is avoided by the required minimum separation from cooking appliances. Exception 2 to Item 4 recognizes that return from a garage cannot be avoided where the return system is part of a dedicated space conditioning system that serves only the garage.

Item 5 addresses indoor swimming pools. The air in swimming pool spaces will have high humidity. This item does not apply where the space is served by a dedicated HVAC system, which is typically the case.

Item 6 addresses the practice of indirectly conditioning a crawl space to the extent that it is considered to be within the thermal envelope of the building. Transfer openings are allowed for this purpose, but locating a ducted return air opening in the crawl space is prohibited because of the potential for contaminants such as moisture, dust, radon, mold, etc., to be present in such space.

Item 7 prohibits a return system from serving more than one dwelling unit. Any arrangement in which dwelling units share all or part of an air distribution system would allow a communication of atmospheres in the units. This communication would spread odors, smoke, contaminants and disease-causing organisms from one dwelling unit to another and therefore must be avoided.