  • CHAPTER15
    CONSTRUCTION SAFEGUARDS

    SECTION1501
    GENERAL

    [BG]1501.1 Scope.

    The provisions of this chapter shall govern safety during construction that is under the jurisdiction of this code and the protection of adjacent public and private properties.

    [BG]1501.2 Storage and placement.

    Construction equipment and materials shall be stored and placed so as not to endanger the public, the workers or adjoining property for the duration of the construction project.

    [BG]1501.3 Alterations, repairs, and additions.

    Required exits, existing structural elements, fire protection devices, and sanitary safeguards shall be maintained at all times during alterations, repairs, or additions to any building or structure.

    Exceptions:

    1. 1.When such required elements or devices are being altered or repaired, adequate substitute provisions shall be made.

    2. 2.When the existing building is not occupied.

    [BG]1501.4 Manner of removal.

    Waste materials shall be removed in a manner which prevents injury or damage to persons, adjoining properties, and public rights-of-way.

    [BG]1501.5 Fire safety during construction.

    Fire safety during construction shall comply with the applicable requirements of the International Building Code and the applicable provisions of Chapter 33 of the International Fire Code.

    [BS]1501.6 Protection of pedestrians.

    Pedestrians shall be protected during construction and demolition activities as required by Sections 1501.6.1 through 1501.6.7 and Table 1501.6. Signs shall be provided to direct pedestrian traffic.

    [BS] TABLE 1501.6

    PROTECTION OF PEDESTRIANS

    HEIGHT OF CONSTRUCTIONDISTANCE OF CONSTRUCTION TO LOT LINETYPE OF PROTECTION REQUIRED
    8 feet or lessLess than 5 feetConstruction railings
    5 feet or moreNone
    More than 8 feetLess than 5 feetBarrier and covered walkway
    5 feet or more, but not more than one-fourth the height of constructionBarrier and covered walkway
    5 feet or more, but between one-fourth and one-half the height of constructionBarrier
    5 feet or more, but exceeding one-half the height of constructionNone

    For SI: 1 foot = 304.8 mm.

    [BS]1501.6.1 Walkways.

    A walkway shall be provided for pedestrian travel in front of every construction and demolition site unless the applicable governing authority authorizes the sidewalk to be fenced or closed. Walkways shall be of sufficient width to accommodate the pedestrian traffic, but in no case shall they be less than 4 feet (1219 mm) in width. Walkways shall be provided with a durable walking surface. Walkways shall be accessible in accordance with Chapter 11 of the International Building Code and shall be designed to support all imposed loads and in no case shall the design live load be less than 150 pounds per square foot (psf) (7.2 kN/m2).

    [BS]1501.6.2 Directional barricades.

    Pedestrian traffic shall be protected by a directional barricade where the walkway extends into the street. The directional barricade shall be of sufficient size and construction to direct vehicular traffic away from the pedestrian path.

    [BS]1501.6.3 Construction railings.

    Construction railings shall be at least 42 inches (1067 mm) in height and shall be sufficient to direct pedestrians around construction areas.

    [BS]1501.6.4 Barriers.

    Barriers shall be a minimum of 8 feet (2438 mm) in height and shall be placed on the side of the walkway nearest the construction. Barriers shall extend the entire length of the construction site. Openings in such barriers shall be protected by doors which are normally kept closed.

    [BS]1501.6.4.1 Barrier design.

    Barriers shall be designed to resist loads required in Chapter 16 of the International Building Code unless constructed as follows:

    1. 1.Barriers shall be provided with 2 × 4 top and bottom plates.

    2. 2.The barrier material shall be a minimum of 3/4 inch (19.1 mm) boards or 1/4 inch (6.4 mm) wood structural use panels.

    3. 3.Wood structural use panels shall be bonded with an adhesive identical to that for exterior wood structural use panels.

    4. 4.Wood structural use panels 1/4 inch (6.4 mm) or 1/16 inch (1.6 mm) in thickness shall have studs spaced not more than 2 feet (610 mm) on center.

    5. 5.Wood structural use panels 3/8 inch (9.5 mm) or 1/2 inch (12.7 mm) in thickness shall have studs spaced not more than 4 feet (1219 mm) on center, provided a 2-inch by 4-inch (51 mm by 102 mm) stiffener is placed horizontally at the mid-height where the stud spacing exceeds 2 feet (610 mm) on center.

    6. 6.Wood structural use panels 5/8 inch (15.9 mm) or thicker shall not span over 8 feet (2438 mm).

    [BS]1501.6.5 Covered walkways.

    Covered walkways shall have a minimum clear height of 8 feet (2438 mm) as measured from the floor surface to the canopy overhead. Adequate lighting shall be provided at all times. Covered walkways shall be designed to support all imposed loads. In no case shall the design live load be less than 150 psf (7.2 kN/m2) for the entire structure.

    Exception: Roofs and supporting structures of covered walkways for new, light-frame construction not exceeding two stories above grade plane are permitted to be designed for a live load of 75 psf (3.6 kN/m2) or the loads imposed on them, whichever is greater. In lieu of such designs, the roof and supporting structure of a covered walkway are permitted to be constructed as follows:

    1. 1.Footings shall be continuous 2 × 6 members.

    2. 2.Posts not less than 4 × 6 shall be provided on both sides of the roof and spaced not more than 12 feet (3658 mm) on center.

    3. 3.Stringers not less than 4 × 12 shall be placed on edge upon the posts.

    4. 4.Joists resting on the stringers shall be at least 2 × 8 and shall be spaced not more than 2 feet (610 mm) on center.

    5. 5.The deck shall be planks at least 2 inches (51 mm) thick or wood structural panels with an exterior exposure durability classification at least 23/32 inch (18.3 mm) thick nailed to the joists.

    6. 6.Each post shall be knee-braced to joists and stringers by 2 × 4 minimum members 4 feet (1219 mm) long.

    7. 7.A 2 × 4 minimum curb shall be set on edge along the outside edge of the deck.

    [BS]1501.6.6 Repair, maintenance and removal.

    Pedestrian protection required by Section 1501.6 shall be maintained in place and kept in good order for the entire length of time pedestrians may be endangered. The owner or the owner’s agent, upon the completion of the construction activity, shall immediately remove walkways, debris and other obstructions and leave such public property in as good a condition as it was before such work was commenced.

    [BS]1501.6.7 Adjacent to excavations.

    Every excavation on a site located 5 feet (1524 mm) or less from the street lot line shall be enclosed with a barrier not less than 6 feet (1829 mm) high. Where located more than 5 feet (1524 mm) from the street lot line, a barrier shall be erected when required by the code official. Barriers shall be of adequate strength to resist wind pressure as specified in Chapter 16 of the International Building Code.

    1501.7 Facilities required.

    Sanitary facilities shall be provided during construction or demolition activities in accordance with the International Plumbing Code.