Browse
  • APPENDIXB (IFGS)
    SIZING OF VENTING SYSTEMS SERVING APPLIANCES EQUIPPED
    WITH DRAFT HOODS, CATEGORY I APPLIANCES AND
    APPLIANCES LISTED FOR USE WITH TYPE B VENTS

    (This appendix is informative and is not part of the code.)

    EXAMPLES USING SINGLE
    APPLIANCE VENTING TABLES

    Example 1: Single draft-hood-equipped appliance.

    An installer has a 120,000 British thermal unit (Btu) per hour input appliance with a 5-inch-diameter draft hood outlet that needs to be vented into a 10-foot-high Type B vent system. What size vent should be used assuming (a) a 5-foot lateral single-wall metal vent connector is used with two 90-degree elbows, or (b) a 5-foot lateral single-wall metal vent connector is used with three 90-degree elbows in the vent system?

    Solution:

    Table 504.2(2) should be used to solve this problem, because single-wall metal vent connectors are being used with a Type B vent.

    1. (a)Read down the first column in Table 504.2(2) until the row associated with a 10-foot height and 5-foot lateral is found. Read across this row until a vent capacity greater than 120,000 Btu per hour is located in the shaded columns labeled “NAT Max” for draft-hood-equipped appliances. In this case, a 5-inch-diameter vent has a capacity of 122,000 Btu per hour and can be used for this application.

    2. (b)If three 90-degree elbows are used in the vent system, then the maximum vent capacity listed in the tables must be reduced by 10 percent (see Section 504.2.3 for single appliance vents). This implies that the 5-inch-diameter vent has an adjusted capacity of only 110,000 Btu per hour. In this case, the vent system must be increased to 6 inches in diameter (see calculations below).

      122,000 (.90) = 110,000 for 5-inch vent

      From Table 504.2(2), Select 6-inch vent

      186,000 (.90) = 167,000; This is greater than the required 120,000. Therefore, use a 6-inch vent and connector where three elbows are used.

      FIGURE B-1 TYPE B DOUBLE-WALL VENT SYSTEM SERVING A SINGLE APPLIANCE WITH A TYPE B DOUBLE-WALL VENT

      For SI: 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W.

      Table 504.2(1) is used when sizing Type B double-wall gas vent connected directly to the appliance.

      Note: The appliance can be either Category I draft hood equipped or fan-assisted type.

      FIGURE B-1

      TYPE B DOUBLE-WALL VENT SYSTEM SERVING A SINGLE APPLIANCE WITH A TYPE B DOUBLE-WALL VENT

    FIGURE B-2 TYPE B DOUBLE-WALL VENT SYSTEM SERVING A SINGLE APPLIANCE WITH A SINGLE-WALL METAL VENT CONNECTOR

    For SI: 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W.

    Table 504.2(2) is used when sizing a single-wall metal vent connector attached to a Type B double-wall gas vent.

    Note: The appliance can be either Category I draft hood equipped or fan-assisted type.

    FIGURE B-2

    TYPE B DOUBLE-WALL VENT SYSTEM SERVING A SINGLE APPLIANCE WITH A SINGLE-WALL METAL VENT CONNECTOR

    FIGURE B-3 VENT SYSTEM SERVING A SINGLE APPLIANCE WITH A MASONRY CHIMNEY OF TYPE B DOUBLE-WALL VENT CONNECTOR

    Table 504.2(3) is used when sizing a Type B double-wall gas vent connector attached to a tile-lined masonry chimney.

    Note: “A” is the equivalent cross-sectional area of the tile liner.

    Note: The appliance can be either Category I draft hood equipped or fan-assisted type.

    FIGURE B-3

    VENT SYSTEM SERVING A SINGLE APPLIANCE WITH A MASONRY CHIMNEY OF TYPE B DOUBLE-WALL VENT CONNECTOR

    FIGURE B-4 VENT SYSTEM SERVING A SINGLE APPLIANCE USING A MASONRY CHIMNEY AND A SINGLE-WALL METAL VENT CONNECTOR

    Table 504.2(4) is used when sizing a single-wall vent connector attached to a tile-lined masonry chimney.

    Note: “A” is the equivalent cross-sectional area of the tile liner.

    Note: The appliance can be either Category I draft hood equipped or fan-assisted type.

    FIGURE B-4

    VENT SYSTEM SERVING A SINGLE APPLIANCE USING A MASONRY CHIMNEY AND A SINGLE-WALL METAL VENT CONNECTOR

    FIGURE B-5 ASBESTOS CEMENT TYPE B OR SINGLE-WALL METAL VENT SYSTEM SERVING A SINGLE DRAFT-HOOD-EQUIPPED APPLIANCE

    Asbestos cement Type B or single-wall metal vent serving a single draft-hood-equipped appliance [see Table 504.2(5)].

    FIGURE B-5

    ASBESTOS CEMENT TYPE B OR SINGLE-WALL METAL VENT SYSTEM SERVING A SINGLE DRAFT-HOOD-EQUIPPED APPLIANCE

    FIGURE B-6 VENT SYSTEM SERVING TWO OR MORE APPLIANCES WITH TYPE B DOUBLE-WALL VENT AND TYPE B DOUBLE-WALL VENT CONNECTOR

    Table 504.3(1) is used when sizing Type B double-wall vent connectors attached to a Type B double-wall common vent.

    Note: Each appliance can be either Category I draft hood equipped or fan-assisted type.

    FIGURE B-6

    VENT SYSTEM SERVING TWO OR MORE APPLIANCES WITH TYPE B DOUBLE-WALL VENT AND TYPE B DOUBLE-WALL VENT CONNECTOR

    FIGURE B-7 VENT SYSTEM SERVING TWO OR MORE APPLIANCES WITH TYPE B DOUBLE-WALL VENT AND SINGLE-WALL METAL VENT CONNECTORS

    Table 504.3(2) is used when sizing single-wall vent connectors attached to a Type B double-wall common vent.

    Note: Each appliance can be either Category I draft hood equipped or fan-assisted type.

    FIGURE B-7

    VENT SYSTEM SERVING TWO OR MORE APPLIANCES WITH TYPE B DOUBLE-WALL VENT AND SINGLE-WALL METAL VENT CONNECTORS

    FIGURE B-8 MASONRY CHIMNEY SERVING TWO OR MORE APPLIANCES WITH TYPE B DOUBLE-WALL VENT CONNECTOR

    Table 504.3(3) is used when sizing Type B double-wall vent connectors attached to a tile-lined masonry chimney.

    Note: “A” is the equivalent cross-sectional area of the tile liner.

    Note: Each appliance can be either Category I draft hood equipped or fan-assisted type.

    FIGURE B-8

    MASONRY CHIMNEY SERVING TWO OR MORE APPLIANCES WITH TYPE B DOUBLE-WALL VENT CONNECTOR

    FIGURE B-9 MASONRY CHIMNEY SERVING TWO OR MORE APPLIANCES WITH SINGLE-WALL METAL VENT CONNECTORS

    Table 504.3(4) is used when sizing single-wall metal vent connectors attached to a tile-lined masonry chimney.

    Note: “A” is the equivalent cross-sectional area of the tile liner.

    Note: Each appliance can be either Category I draft hood equipped or fan-assisted type.

    FIGURE B-9

    MASONRY CHIMNEY SERVING TWO OR MORE APPLIANCES WITH SINGLE-WALL METAL VENT CONNECTORS

    FIGURE B-10 ASBESTOS CEMENT TYPE B OR SINGLE-WALL METAL VENT SYSTEM SERVING TWO OR MORE DRAFT-HOOD-EQUIPPED APPLIANCES

    Asbestos cement Type B or single-wall metal pipe vent serving two or more draft-hood-equipped appliances [see Table 504.3(5)].

    FIGURE B-10

    ASBESTOS CEMENT TYPE B OR SINGLE-WALL METAL VENT SYSTEM SERVING TWO OR MORE DRAFT-HOOD-EQUIPPED APPLIANCES

    FIGURE B-11 USE OF MANIFOLD COMMON VENT CONNECTOR

    Example: Manifolded Common Vent Connector LM shall be not greater than 18 times the common vent connector manifold inside diameter; i.e., a 4-inch (102 mm) inside diameter common vent connector manifold shall not exceed 72 inches (1829 mm) in length (see Section 504.3.4).

    Note: This is an illustration of a typical manifolded vent connector. Different appliance, vent connector, or common vent types are possible. Consult Section 502.3.

    FIGURE B-11

    USE OF MANIFOLD COMMON VENT CONNECTOR

    FIGURE B-12 USE OF OFFSET COMMON VENT

    Example: Offset Common Vent

    Note: This is an illustration of a typical offset vent. Different appliance, vent connector, or vent types are possible. Consult Sections 504.2 and 504.3.

    FIGURE B-12

    USE OF OFFSET COMMON VENT

    FIGURE B-13 MULTISTORY GAS VENT DESIGN PROCEDURE FOR EACH SEGMENT OF SYSTEM

    Vent connector size depends on:Common vent size depends on:
    • Input• Rise
    • Available total height “H”• Combined inputs
    • Available total height “H”Table 504.3(1) common vent
    Table 504.3(1) connectors

    FIGURE B-13

    MULTISTORY GAS VENT DESIGN PROCEDURE FOR EACH SEGMENT OF SYSTEM

    FIGURE B-14 MULTISTORY VENT SYSTEMS

    Principles of design of multistory vents using vent connector and common vent design tables (see Sections 504.3.11 through 504.3.17).

    FIGURE B-14

    MULTISTORY VENT SYSTEMS

    FIGURE B-15(EXAMPLE 1) SINGLE DRAFT-HOOD-EQUIPPED APPLIANCE

    For SI: 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W.

    FIGURE B-15 (EXAMPLE 1)

    SINGLE DRAFT-HOOD-EQUIPPED APPLIANCE

    Example 2: Single fan-assisted appliance.

    An installer has an 80,000 Btu per hour input fan-assisted appliance that must be installed using 10 feet of lateral connector attached to a 30-foot-high Type B vent. Two 90-degree elbows are needed for the installation. Can a single-wall metal vent connector be used for this application?

    Solution:

    Table 504.2(2) refers to the use of single-wall metal vent connectors with Type B vent. In the first column find the row associated with a 30-foot height and a 10-foot lateral. Read across this row, looking at the FAN Min and FAN Max columns, to find that a 3-inch-diameter single-wall metal vent connector is not recommended. Moving to the next larger size single wall connector (4 inches), note that a 4-inch-diameter single-wall metal connector has a recommended minimum vent capacity of 91,000 Btu per hour and a recommended maximum vent capacity of 144,000 Btu per hour. The 80,000 Btu per hour fan-assisted appliance is outside this range, so the conclusion is that a single-wall metal vent connector cannot be used to vent this appliance using 10 feet of lateral for the connector.

    However, if the 80,000 Btu per hour input appliance could be moved to within 5 feet of the vertical vent, then a 4-inch single-wall metal connector could be used to vent the appliance. Table 504.2(2) shows the acceptable range of vent capacities for a 4-inch vent with 5 feet of lateral to be between 72,000 Btu per hour and 157,000 Btu per hour.

    If the appliance cannot be moved closer to the vertical vent, then Type B vent could be used as the connector material. In this case, Table 504.2(1) shows that for a 30-foot-high vent with 10 feet of lateral, the acceptable range of vent capacities for a 4-inch-diameter vent attached to a fan-assisted appliance is between 37,000 Btu per hour and 150,000 Btu per hour.

    FIGURE B-16 (EXAMPLE 2) SINGLE FAN-ASSISTED APPLIANCE

    For SI: 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W.

    FIGURE B-16 (EXAMPLE 2)

    SINGLE FAN-ASSISTED APPLIANCE

    Example 3: Interpolating between table values.

    An installer has an 80,000 Btu per hour input appliance with a 4-inch-diameter draft hood outlet that needs to be vented into a 12-foot-high Type B vent. The vent connector has a 5-foot lateral length and is also Type B. Can this appliance be vented using a 4-inch-diameter vent?

    Solution:

    Table 504.2(1) is used in the case of an all Type B vent system. However, since there is no entry in Table 504.2(1) for a height of 12 feet, interpolation must be used. Read down the 4-inch diameter NAT Max column to the row associated with 10-foot height and 5-foot lateral to find the capacity value of 77,000 Btu per hour. Read further down to the 15-foot height, 5-foot lateral row to find the capacity value of 87,000 Btu per hour. The difference between the 15-foot height capacity value and the 10-foot height capacity value is 10,000 Btu per hour. The capacity for a vent system with a 12-foot height is equal to the capacity for a 10-foot height plus 2/5 of the difference between the 10-foot and 15-foot height values, or 77,000 + 2/5 (10,000) = 81,000 Btu per hour. Therefore, a 4-inch-diameter vent can be used in the installation.