NORMATIVE APPENDIX C—
PRESCRIPTIVE EQUIPMENT EFFICIENCY TABLES


  • (This is a normative appendix and is part of this standard.)

    Informative Note: The first 15 tables are in I-P units, followed by15 tables in SI units.

    TABLE C-1 (Supersedes Table 6.8.1A in ANSI/ASHRAE/IES Standard 90.1)
    Electrical-Operated Unitary Air Conditioners and Condensing Units (I-P)

    Equipment TypeSize CategoryHeating Section TypeSub-Category or
    Rating Conditions
    Minimum
    Efficiency
    Test Procedurea
    Air conditioners,
    air-cooled
    <65,000 Btu/hAllSplit systems14.0 SEER
    12.0 EER
    ARI 210/240
    Single packaged14.0 SEER
    11.6 EER
    Through-the-wall,
    air-cooled
    <30,000 Btu/hAllSplit systems12.0 SEER
    Single packaged12.0 SEER
    Small-duct
    high velocity,
    air-cooled
    <65,000 Btu/hAllSplit systems10 SEER
    Air conditioners,
    air-cooled
    ≥65,000 Btu/h and
    <135,000 Btu/h
    Electric resistance (or none)Split systems and single package11.5 EER
    12.0 IEER
    ARI 340/360
    All otherSplit systems and single package11.3 EER
    11.8 IEER
    ≥135,000 Btu/h and
    <240,000 Btu/h
    Electric resistance (or none) Split systems and single package11.5 EER
    12.0 IEER
    All otherSplit systems and single package11.3 EER
    11.8 IEER
    ≥240,000 Btu/h and
    <760,000 Btu/h
    Electric resistance (or none)Split systems and single package10.0 EER
    10.5 IEER
    All otherSplit systems and single package9.8 EER
    10.3 IEER
    ≥760,000 Btu/hElectric resistance (or none)Split systems and single package9.7 EER
    10.2 IEER
    All otherSplit systems and single package9.5 EER
    10.0 IEER
    Air conditioners,
    water and evapora
    tively cooled
    <65,000 Btu/hAllSplit systems and single package14.0 EER
    14.3 IEER
    ARI 210/240
    ≥65,000 Btu/h and
    <135,000 Btu/h
    Electric resistance (or none)Split systems and single package14.0 EER
    14.3 IEER
    ARI 340/360
    All otherSplit systems and single package13.8 EER
    14.1 IEER
    ≥135,000 Btu/h and
    <240,000 Btu/h
    Electric resistance (or none)Split systems and single package14.0 EER
    14.3 IEER
    All otherSplit systems and single package13.8 EER
    14.1 IEER
    ≥240,000 Btu/hElectric resistance (or none)Split systems and single package14.0 EER
    14.0 IEER
    All otherSplit systems and single package13.8 EER
    13.8 IEER
    Condensing units,
    air-cooled
    ≥135,000 Btu/hNot applicable
    match with
    indoor coil
    ARI 365
    Condensing, water or
    evaporatively cooled
    ≥135,000 Btu/hNot applicable
    match with
    indoor coil
    a. Section 11 contains a complete specification of the referenced test procedures, including year version of the test procedure.

    TABLE C-2 (Supersedes Table 6.8.1B in ANSI/ASHRAE/IES Standard 90.1)
    Electrically-Operated Unitary and Applied Heat Pumps Minimum Efficiency Requirements (I-P)

    Equipment TypeSize Category Heating Section TypeSub-Category or
    Rating Conditions
    Minimum
    Efficiency
    Test
    Procedure
    a
    Air conditioners,
    air-cooled
    (cooling mode)
    <65,000 Btu/hAllSplit systems14.0 SEER
    12.0 EER
    ARI 210/240
    Single packaged14.0 SEER
    11.6 EER
    Through-the-wall,
    air-cooled
    (cooling mode)
    <30,000 Btu/hAllSplit systems12.0 SEER
    Single packaged12.0 SEER
    Small-duct
    high velocity,
    air-cooled
    (cooling mode)
    <65,000 Btu/hAllSplit systems10.0 SEER
    Air conditioners,
    air-cooled
    (cooling mode)
    ≥ 65,000 Btu/h and
    <135,000 Btu/h
    Electric resistance (or none)Split systems and single package11.3 EER
    11.8 IEER
    ARI 340/360
    All otherSplit systems and single package11.1EER
    11.6 IEER
    ≥ 135,000 Btu/h and
    <240,000 Btu/h
    Electric resistance (or none)Split systems and single package11.3 EER
    11.8 IEER
    All otherSplit systems and single package11.1EER
    11.6 IEER
    ≥ 240,000 Btu/hElectric resistance (or none)Split systems and single package9.8 EER
    9.8 IEER
    All otherSplit systems and single package9.6 EER
    9.6 IEER
    Water-source
    (cooling mode)
    <17,000 Btu/hAll86°F entering water14.0 EERISO-13256-1
    ≥ 17,000 Btu/h and
    <65,000 Btu/h
    All86°F entering water14.0 EER
    >65,000 Btu/h and
    <135,000 Btu/h
    All86°F entering water14.0 EER
    Groundwater-source
    (cooling mode)
    <135,000 Btu/hAll59°F entering water16.2 EER
    77°F entering water13.4 EER
    Air conditioners,
    air-cooled
    (heating mode)
    <65,000 Btu/hAllSplit systems8.5 HSPFARI210/240
    Single packaged8.0 HSPF
    Through-the-wall,
    air-cooled
    (heating mode)
    <30,000 Btu/hAllSplit systems7.4 HSPF
    Single packaged7.4 HSPF
    Small-duct
    high velocity,
    air-cooled
    (heating mode)
    <65,000 Btu/hAllSplit systems6.8 HSPF
    Air-cooled
    (heating mode)
    ≥ 65,000 Btu/h and
    <135,000 Btu/h
    (cooling capacity)
    47°F DB/43°F WB Outdoor air3.3 COPARI 340/360
    17°F DB/15°F WB Outdoor air2.2 COP
    ≥ 135,000 Btu/h
    (cooling capacity)
    47°F DB/43°F WB Outdoor air3.2 COP
    17°F DB/15°F WB Outdoor air2.0 COP
    Water-source
    (heating mode)
    <135,000 Btu/h
    (cooling capacity)
    68°F entering water4.2 COPISO-13256-1
    Groundwater-source
    (heating mode)
    <135,000 Btu/h
    (cooling capacity)
    50°F entering water3.6 COP
    32°F entering fluid3.1 COP
    a. Section 11 contains a complete specification of the referenced test procedures, including year version of the test procedure.

    TABLE C-3 (Supersedes Table 6.8.1C in ANSI/ASHRAE/IES Standard 90.1)
    Water Chilling Packages—Minimum Efficiency Requirementsa (I-P)

    Equipment TypeSize CategoryUnitsMinimum Efficiencyc (I-P)Test
    Procedure
    b
    Path APath Bd
    Full LoadIPLVFull LoadIPLV
    Air-cooled chillers with
    condenser,
    electrically operated
    <150 tonsEER10.00012.500NANAARI 550/590
    ≥150 tonsEER10.000 12.750 NANA
    Air-cooled without
    condenser,
    electrical operated
    All capacitiesEERCondenserless units shall be rated with
    matched condensers
    ARI 550/590
    Water-cooled,
    electrically operated,
    positive displacement
    (reciprocating)
    All capacitieskw/tonReciprocating units required to comply with water
    cooled positive displacement requirements
    ARI 550/590
    Water-cooled
    electrically operated,
    positive displacement
    <75 tonskw/ton0.7800.6300.8000.600ARI 550/590
    ≥75 tons and
    <150 tons
    kw/ton0.7750.6150.7900.586
    ≥150 tons and
    <300 tons
    kw/ton0.6800.580 0.7180.540
    ≥300 tonskw/ton0.6200.5400.6390.490
    Water-cooled electrically
    operated, centrifugala
    <150 tonskw/ton0.6340.5960.6390.450ARI 550/590
    ≥150 tons and
    <300 tons
    kw/ton0.6340.5960.6390.450
    ≥300 tons and
    <600 tons
    kw/ton0.5760.5490.6000.400
    ≥600 tonskw/ton0.5700.5390.5900.400
    Air-cooled absorption
    single effectg
    All capacitiesCOP0.600NRfNAeNAeARI 560
    Water-cooled absorption
    single effectg
    All capacitiesCOP0.700NRfNAeNAe
    Absorption double effect
    indirect-fired
    All capacitiesCOP1.0001.050NAeNAe
    Absorption double effect
    direct fired
    All capacitiesCOP1.0001.000NAeNAe
    a. The chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is
    b Section 11 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure
    c. Compliance with this standard can be obtained by meeting the minimum requirements of Path A or Path B. However both the full load and IPLV must be met to fulfill the requirements of Path A and Path B
    d. Path B is intended for applications with significant operating time at part load. All Path B machines shall be equipped with demand limiting capable controls
    e. NA means that this requirement is not applicable and can not be used for compliance
    f. NR means that for this category there are no minimum requirements
    g. Only allowed to be used in heat recovery applications
    h. Packages that are not designed for operation at ARI Standard 550/590 test conditions (and, thus, cannot be tested to meet the requirements of Table C-3) of 44°F leaving chilledwater temperature and 85°F entering condenser-water temperature with 3 gpm/ton condenser-water flow shall have maximum full-load kW/ton and NPLV ratings adjusted using the following equation:
    Adjusted maximum full load kW/ton rating = (full load kW/ton from Table C-3) / Kadj
    Adjusted maximum NPLV rating = (IPLV from Table C-3) / Kadj