  • (This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI requirements for a standard and may contain material that has not been subject to public review or a consensus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI.)

    INFORMATIVE APPENDIX E
    BUILDING ENVELOPE TABLES

    The first eight tables are in I-P units, followed by eight tables in SI units. U-factors, C-factors, F-factors, and SHGC in these tables meet the requirements of Section 7.4.2.1, although the R-values in most cases provide more insulation than is required in Section 7.4.2.1. These R-values represent common assemblies in building construction. Assemblies with lower R-values are allowed to be used the meet the criteria of Section 7.4.2.1 when they meet the appropriate U-factor, Cfactor, or F-factor criteria.

    TABLE E-1 (Supersedes Table 5.5-1 in ANSI/ASHRAE/IES Standard 90.1)

    Building Envelope Requirements for Climate Zone 1 (A,B)* (I-P)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.048R-20 c.i.U-0.039R-25 c.i.U-0.218R-3.8 c.i.
    Metal buildingaU-0.041R-10 + R-19 FCU-0.041R-10 + R-19 FCU-0.115R-10
    Attic and otherU-0.027R-38U-0.027R-38U-0.081R-13
    Walls, above grade
    MassU-0.580NRU-0.151bR-5.7 c.i.bU-0.580NR
    Metal buildingU-0.094R-0 + R-9.8 c.i.U-0.094R-0 + R-9.8 c.i.U-0.352NR
    Steel framedU-0.124R-13U-0.124R-13U-0.352NR
    Wood framed and otherU-0.089R-13U-0.089R-13U-0.292NR
    Wall, below grade
    Below-grade wallC-1.140NRC-1.140NRC-1.140NR
    Floors
    MassU-0.322NRU-0.322NRU-0.322NR
    Steel joistU-0.350NRU-0.350NRU-0.350NR
    Wood framed and otherU-0.282NRU-0.282NRU-0.282NR
    Slab-on-grade floors
    UnheatedF-0.730NRF-0.730NRF-0.730NR
    HeatedF-1.020R-7.5 for 12 in.F-1.020R-7.5 for 12 in.F-1.020R-7.5 for 12 in.
    Opaque doors
    SwingingU-0.700U-0.500U-0.700
    NonswingingU-1.450U-0.500U-1.450
    FenestrationAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-0.45cE,W, &S-0.25 N-0.351.10U-0.45cE,W, &S-0.25 N-0.351.10U-0.84NRNR
    Metal framing, fixedU-0.51cU-0.51cU-1.08
    Metal framing, operableU-0.59cU-0.59cU-1.08
    Metal framing, entrance doorU-0.99cU-0.99cU-0.99c
    Skylight, 0% to 3% of roof0.350.35
    All typesU-0.75NRU-0.75NRU-1.80NRNR
    1. * The following definitions apply: c.i. = continuous insulation (see ANSI/ASHRAE/IES Standard 90.1-2013, Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).

    3. b.Exception to ANSI/ASHRAE/IES Standard 90.1-2013, Section 5.5.3.2, applies for mass walls above grade.

    4. c.For locations in Climate Zone 1 with a cooling design temperature of 95°F and greater, the maximum U-factors for vertical fenestration shall be 10% lower than those in ANSI/ASHRAE/IES Standard 90.1-2013, Section 5.5.4.3.

    TABLE E-2 (Supersedes Table 5.5-2 in ANSI/ASHRAE/IES Standard 90.1)

    Building Envelope Requirements for Climate Zone 2 (A,B)* (I-P)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.039R-25 c.i.U-0.039R-25 c.i.U-0.173R-5 c.i.
    Metal buildingaU-0.041R-10 + R-19 FCU-0.041R-10 + R-19 FCU-0.096R-16
    Attic and otherU-0.027R-38U-0.027R-38U-0.053R-19
    Walls, above grade
    MassU-0.151bR-5.7 c.i.bU-0.123R-7.6 c.i.U-0.580NR
    Metal buildingU-0.094R-0 + R-9.8 c.i.U-0.094R-0 + R-9.8. c.i.U-0.162R-13
    Steel framedU-0.084R-13 + R-3.8 c.i.U-0.064R-13 + R-7.5 c.i.U-0.124R-13
    Wood framed and otherU-0.089R-13U-0.089R-13U-0.089R-13
    Wall, below grade
    Below-grade wallC-1.140NRC-1.140NRC-1.140NR
    Floors
    MassU-0.107R-6.3 c.i.U-0.087R-8.3 c.i.U-0.322NR
    Steel joistU-0.038R-30U-0.038R-30U-0.069R-13
    Wood framed and otherU-0.033R-30U-0.033R-30U-0.066R-13
    Slab-on-grade floors
    UnheatedF-0.730NRF-0.730NRF-0.730NR
    HeatedF-0.900R-10 for 24 in.F-0.860R-15 for 24 in.F-1.020R-7.5 for 12 in.
    Opaque doors
    SwingingU-0.700U-0.500U-0.700
    NonswingingU-0.500U-0.500U-1.450
    FenestrationAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min. VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-0.36E,W, &S-0.25 N-0.351.10U-0.36E,W, &S-0.25 N-0.351.10U-0.84NRNR
    Metal framing, fixedU-0.51U-0.51U-1.08
    Metal framing, operableU-0.59U-0.59U-1.08
    Metal framing, entrance doorU-0.75U-0.69U-0.75
    Skylight, 0% to 3% of roof0.350.35
    All typesU-0.65NRU-0.65NRU-1.80NRNR
    1. *The following definitions apply: c.i. = continuous insulation (see ANSI/ASHRAE/IES Standard 90.1-2013, Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).

    3. b.Exception to ANSI/ASHRAE/IES Standard 90.1-2013, Section 5.5.3.2, applies for mass walls above grade.

    TABLE E-3 (Supersedes Table 5.5-3 in ANSI/ASHRAE/IES Standard 90.1)

    Building Envelope Requirements for Climate Zone 3 (A,B,C)* (I-P)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.039R-25 c.i.U-0.039R-25 c.i.U-0.119R-7.6 c.i.
    Metal buildingaU-0.041R-10 + R-19 FCU-0.041R-10 + R-19 FCU-0.096R-16
    Attic and otherU-0.027R-38U-0.027R-38U-0.053R-19
    Walls, above grade
    MassU-0.123R-7.6 c.i.U-0.104R-9.5 c.i.U-0.580NR
    Metal buildingU-0.094R-0 + R-9.8 c.i.U-0.072R-0 + R-13 c.i.U-0.162R-13
    Steel framedU-0.077R-13 + R-5 c.i.U-0.064R-13 + R-7.5 c.i.U-0.124R-13
    Wood framed and otherU-0.089R-13U-0.064R-13 + R-3.8 c.i. or R-20U-0.089R-13
    Wall, below grade
    Below-grade wallC-1.140NRC-1.140NRC-1.140NR
    Floors
    MassU-0.074R-10 c.i.U-0.074R-10 c.i.U-0.137R-4.2 c.i.
    Steel joistU-0.038R-30U-0.038R-30U-0.052R-19
    Wood framed and otherU-0.033R-30U-0.033R-30U-0.051R-19
    Slab-on-grade floors
    UnheatedF-0.730NRF-0.540R-10 for 24 in.F-0.730NR
    HeatedF-0.860R-15 for 24 in.F-0.860R-15 for 24 in.F-1.020R-7.5 for 12 in.
    Opaque doors
    SwingingU-0.700U-0.500U-0.700
    NonswingingU-0.500U-0.500U-1.450
    FenestrationAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-0.32E,W, &S-0.25 N-0.351.10U-0.32E,W, &S-0.25 N-0.351.10U-0.78NRNR
    Metal framing, fixedU-0.45U-0.45U-1.08
    Metal framing, operableU-0.54U-0.54U-1.08
    Metal framing, entrance doorU-0.69U-0.61U-0.69
    Skylight, 0% to 3% of roof0.350.35
    All typesU-0.55NRU-0.55NRU-1.70NRNR
    1. *The following definitions apply: c.i. = continuous insulation (see ANSI/ASHRAE/IES Standard 90.1-2013, Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).

    TABLE E-4 Building Envelope Requirements for Climate Zone 4 (A,B,C)* (I-P)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.029R-35 c.i.U-0.029R-35 c.i.U-0.084R-12 c.i.
    Metal buildingaU-0.033R-13 + R-25 c.i.U-0.033R-13 + R-25 c.i.U-0.074R-0 + R-13 c.i.
    Attic and otherU-0.019R-60U-0.019R-60U-0.031R-38
    Walls, above grade
    MassU-0.094R-11.4c.i.U-0.081R-13.0U-0.580NR
    Metal buildingU-0.054R-11 + R-13 c.i.U-0.045R-16 + R-15.8 c.i.U-0.146R-0 + R-6.5 c.i.
    Steel framedU-0.058R-13.0 + R-12.5 c.i.U-0.058R-13.0 + R-12.5 c.i.U-0.112R-13.0 + R-3.8 c.i.
    Wood framed and otherU-0.058R-13.0 + R-7.5 c.i.U-0.058R-13.0 + R-7.5 c.i.U-0.080R-13.0 + R-3.8 c.i.
    Wall, below grade
    Below-grade wallC-0.107R-10.0 c.i.C-0.083R-12.5 c.i.C-1.140NR
    Floors
    MassU-0.051R-16.7 c.i.U-0.046R-18.7 c.i.U-0.096R-8.3 c.i.
    Steel joistU-0.034R-38.0U-0.034R-38.0U-0.047R-30.0
    Wood framed and otherU-0.030R-38.0U-0.030R-38.0U-0.046R-30.0
    Slab-on-grade floors
    UnheatedF-0.468R-20.0 for 48 in.F-0.468R-20.0 for 48 in.F-0.730NR
    HeatedF-0.759R-20.0 for 48 in.F-0.619R-15.0 full slabF-0.810R-20.0 for 48 in.
    Opaque doors
    SwingingU-0.450U-0.450U-0.630
    NonswingingU-0.450U-0.450U-1.305
    FenestrationAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-0.32S-0.40 E&W-0.36 N-0.501.10U-0.32S-0.40 E&W-0.36 N-0.501.10U-0.46NRNR
    Metal framing, fixedU-0.38U-0.38U-0.66
    Metal framing, operableU-0.45U-0.45U-0.73
    Metal framing, entrance doorU-0.69U-0.61U-0.69
    Skylight, 0% to 3% of roof0.400.40
    All typesU-0.50NRU-0.50NRU-1.15NRNR
    1. *The following definitions apply: c.i. = continuous insulation (see ANSI/ASHRAE/IES Standard 90.1-2013, Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).

    TABLE E-5 (Supersedes Table 5.5-5 in ANSI/ASHRAE/IES Standard 90.1)

    Building Envelope Requirements for Climate Zone 5 (A,B,C)* (I-P)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.029R-35 c.i.U-0.029R-35 c.i.U-0.057R-17 c.i.
    Metal buildingaU-0.033R-13 + R-25 c.i.U-0.033R-13 + R-25 c.i.U-0.074R-0 + R-13 c.i.
    Attic and otherU-0.019R-60U-0.019R-60U-0.031R-38
    Walls, above grade
    MassU-0.081R-13.0U-0.072R-15.2 c.i.U-0.136R-7.5c.i.
    Metal buildingU-0.045R-16 + R-15.8 c.i.U-0.045R-16 + R-15.8 c.i.U-0.085R-11 + R-6.5 c.i.
    Steel framedU-0.050R-13.0 + R-12.5 c.i.U-0.050R-13.0 + R-12.5 c.i.U-0.076R-13.0 + R-7.5 c.i.
    Wood framed and otherU-0.046R-13.0 + R-12.5 c.i.U-0.046R-13.0 + R-12.5 c.i.U-0.080R-13.0 + R-3.8 c.i.
    Wall, below grade
    Below-grade wallC-0.107R-10.0 c.i.C-0.083R-12.5 c.i.C-1.140NR
    Floors
    MassU-0.051R-16.7 c.i.U-0.046R-18.7 c.i.U-0.096R-8.3 c.i.
    Steel joistU-0.034R-38.0U-0.034R-38.0U-0.047R-30.0
    Wood framed and otherU-0.030R-38.0U-0.030R-38.0U-0.046R-30.0
    Slab-on-grade floors
    UnheatedF-0.468R-20.0 for 48 in.F-0.459R-20.0 for 48 in.F-0.730NR
    HeatedF-0.619R-15.0 full slabF-0.619R-15.0 full slabF-0.810R-20.0 for 48 in.
    Opaque doors
    SwingingU-0.450U-0.450U-0.630
    NonswingingU-0.450U-0.450U-1.305
    FenestrationAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-0.29S-0.40 E&W-0.36 N-0.501.10U-0.29S-0.40 E&W-0.36 N-0.501.10U-0.41NRNR
    Metal framing, fixedU-0.38U-0.38U-0.56
    Metal framing, operableU-0.45U-0.45U-0.63
    Metal framing, entrance doorU-0.69U-0.61U-0.69
    Skylight, 0% to 3% of roof0.400.40
    All typesU-0.50NRU-0.50NRU-0.98NRNR
    1. *The following definitions apply: c.i. = continuous insulation (see ANSI/ASHRAE/IES Standard 90.1-2013, Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).

    TABLE E-6 (Supersedes Table 5.5-6 in ANSI/ASHRAE/IES Standard 90.1)

    Building Envelope Requirements for Climate Zone 6 (A,B) * (I-P)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.029R-35 c.i.U-0.029R-35 c.i.U-0.057R-17 c.i.
    Metal buildingaU-0.028R-11 + R-32 c.i.U-0.026R-19 + R-32 c.i.U-0.054R-11 + R-13 c.i.
    Attic and otherU-0.019R-60U-0.019R-60U-0.031R-38
    Walls, above grade
    MassU-0.072R-15.2 c.i.U-0.064R-19.6 c.i.U-0.136R-7.5c.i.
    Metal buildingU-0.045R-16 + R-15.8 c.i.U-0.045R-16 + R-15.8 c.i.U-0.085R-11 + R-6.5 c.i.
    Steel framedU-0.044R-13.0 + R-15.6 c.i.U-0.044R-13.0 + R-15.6 c.i.U-0.076R-13.0 + R-7.5 c.i.
    Wood framed and otherU-0.046R-13.0 + R-12.5 c.i.U-0.046R-13.0 + R-12.5 c.i.U-0.080R-13.0 + R-3.8 c.i.
    Wall, below grade
    Below-grade wallC-0.083R-12.5 c.i.C-0.057R-17.5 c.i.C-0.107R-10.0 c.i.
    Floors
    MassU-0.046R-18.7 c.i.U-0.046R-18.7 c.i.U-0.078R-10.4 c.i.
    Steel joistU-0.029R-49.0U-0.029R-49.0U-0.047R-30.0
    Wood framed and otherU-0.024R-38.0+ R-7.5 c.i.U-0.024R-38.0 + R-7.5 c.i.U-0.046R-30.0
    Slab-on-grade floors
    UnheatedF-0.459R-20.0 for 48 in.F-0.391R-15.0 full slabF-0.730NR
    HeatedF-0.619R-15.0 full slabF-0.604R-15.0 full slabF-0.774R-20.0 for 48 in.
    Opaque doors
    SwingingU-0.450U-0.450U-0.630
    NonswingingU-0.450U-0.450U-0.450
    FenestrationAssembly Max. UAssembly Max. SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-0.29S-0.40 E&W-0.36 N-0.501.10U-0.29S-0.40 E&W-0.36 N-0.501.10U-0.41NRNR
    Metal framing, fixedU-0.38U-0.38U-0.46
    Metal framing, operableU-0.45U-0.45U-0.53
    Metal framing, entrance doorU-0.69U-0.61U-0.69
    Skylight, 0% to 3% of roof0.400.40
    All typesU-0.50NRU-0.50NRU-0.85NRNR
    1. *The following definitions apply: c.i. = continuous insulation (ANSI/ASHRAE/IES Standard 90.1-2013, see Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).

    TABLE E-7 (Supersedes Table 5.5-7 in ANSI/ASHRAE/IES Standard 90.1)

    Building Envelope Requirements for Climate Zone 7* (I-P)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.025R-40 c.i.U-0.025R-40 c.i.U-0.035R-28 c.i.
    Metal buildingaU-0.026R-19 + R-32 c.i.U-0.026R-19 + R-32 c.i.U-0.033R-13 + R-25 c.i.
    Attic and otherU-0.015R-71U-0.015R-71U-0.024R-49
    Walls, above grade
    MassU-0.064R-19.6 c.i.U-0.064R-19.6 c.i.U-0.111R-9.5 c.i.
    Metal buildingU-0.040R-19 + R-19 c.i.U-0.040R-19 + R-19 c.i.U-0.065R-13 + R-9.8 c.i.
    Steel framedU-0.044R-13.0 + R-15.6 c.i.U-0.038R-13.0 + R-18.8 c.i.U-0.058R-13.0 + R-12.5 c.i.
    Wood framed and otherU-0.046R-13.0 + R-12.5 c.i.U-0.046R-13.0 + R-12.5 c.i.U-0.058R-13.0 + R-7.5 c.i.
    Wall, below grade
    Below-grade wallC-0.057R-17.5 c.i.C-0.057R-17.5 c.i.C-0.107R-10.0 c.i.
    Floors
    MassU-0.038R-25.1 c.i.U-0.038R-25.1 c.i.U-0.067R-12.5 c.i.
    Steel joistU-0.029R-49.0U-0.029R-49.0U-0.047R-30.0
    Wood framed and otherU-0.024R-38.0+ R-7.5 c.i.U-0.024R-38.0 + R-7.5 c.i.U-0.046R-30.0
    Slab-on-grade floors
    UnheatedF-0.459R-20.0 for 48 in.F-0.391R-15.0 full slabF-0.730NR
    HeatedF-0.604R-15.0 full slabF-0.604R-15.0 full slabF-0.774R-20.0 for 48 in.
    Opaque doors
    SwingingU-0.450U-0.450U-0.630
    NonswingingU-0.450U-0.450U-0.450
    FenestrationAssembly Max. UAssembly Max. SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-0.29S-0.45 E&W-0.41 N-0.551.10U-0.29S-0.45 E&W-0.41 N-0.551.10U-0.29NRNR
    Metal framing, fixedU-0.34U-0.34U-0.34
    Metal framing, operableU-0.36U-0.36U-0.40
    Metal framing, entrance doorU-0.69U-0.61U-0.69
    Skylight, 0% to 3% of roof
    All typesU-0.50NRNRU-0.50NRNRU-0.85NRNR
    1. *The following definitions apply: c.i. = continuous insulation (see ANSI/ASHRAE/IES Standard 90.1-2013, Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).

    TABLE E-8 (Supersedes Table 5.5-8 in ANSI/ASHRAE/IES Standard 90.1)

    Building Envelope Requirements for Climate Zone 8* (I-P)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.025R-40 c.i.U-0.025R-40 c.i.U-0.035R-28 c.i.
    Metal buildingaU-0.023R-16 + R-38 c.i.U-0.023R-16 + R-38 c.i.U-0.033R-13 + R-25 c.i.
    Attic and otherU-0.015R-71U-0.015R-71U-0.024R-49
    Walls, above grade
    MassU-0.043R-22.0 c.i.U-0.043R-22.0 c.i.U-0.094R-11.4c.i.
    Metal buildingU-0.035R-19 + R-22.1 c.i.U-0.035R-19 + R-22.1 c.i.U-0.054R-11 + R-13 c.i.
    Steel framedU-0.033R-13.0 + R-25 c.i.U-0.033R-13.0 + R-25 c.i.U-0.058R-13.0 + R-12.5 c.i.
    Wood framed and otherU-0.029R-13.0 + R-25 c.i.U-0.029R-13.0 + R-25 c.i.U-0.046R-13.0 + R-12.5 c.i.
    Wall, below grade
    Below-grade wallC-0.057R-17.5 c.i.C-0.057R-17.5 c.i.C-0.107R-10.0 c.i.
    Floors
    MassU-0.034R-27.2 c.i.U-0.034R-27.2 c.i.U-0.058R-14.6 c.i.
    Steel joistU-0.029R-49.0U-0.029R-49.0U-0.047R-30.0
    Wood framed and otherU-0.024R-38.0+ R-7.5 c.i.U-0.024R-38.0 + R-7.5 c.i.U-0.030R-38.0
    Slab-on-grade floors
    UnheatedF-0.391R-15.0 full slabF-0.382R-15.0 full slabF-0.486R-20.0 for 48 in.
    HeatedF-0.604R-15.0 full slabF-0.336R-25.0 full slabF-0.774R-20.0 for 48 in.
    Opaque doors
    SwingingU-0.450U-0.450U-0.450
    NonswingingU-0.450U-0.450U-0.450
    FenestrationAssembly Max. UAssembly Max. SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-0.29S-0.45 E&W-0.41 N-0.551.10U-0.29S-0.45 E&W-0.41 N-0.551.10U-0.29NRNR
    Metal framing, fixedU-0.34U-0.34U-0.34
    Metal framing,operableU-0.36U-0.36U-0.40
    Metal framing, entrance doorU-0.69U-0.61U-0.69
    Skylight, 0% to 3% of roof
    All typesU-0.50NRNRU-0.50NRNRU-0.85NRNR
    1. *The following definitions apply: c.i. = continuous insulation (see ANSI/ASHRAE/IES Standard 90.1-2013, Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).

    TABLE E-1 (Supersedes Table 5.5-1 in ANSI/ASHRAE/IES Standard 90.1)

    Building Envelope Requirements for Climate Zone 1 (A,B)* (SI)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.273R-3.5 c.i.U-0.220R-4.4 c.i.U-1.240R-0.7 c.i.
    Metal buildingaU-0.233R-1.8 + R-3.3 FCU-0.233R-1.8 + R-3.3 FCU-0.653R-1.8
    Attic and otherU-0.153R-6.7U-0.153R-6.7U-0.459R-2.3
    Walls, above grade
    MassU-3.293NRU-0.857bR-1.0 c.i.bU-3.293NR
    Metal buildingU-0.533R-0 + R-1.7 c.i.U-0.533R-0 + R-1.7 c.i.U-1.998NR
    Steel framedU-0.705R-2.3U-0.705R-2.3U-1.998NR
    Wood framed and otherU-0.504R-2.3U-0.504R-2.3U-1.660NR
    Wall, below grade
    Below-grade wallC-6.473NRC-6.473NRC-6.473NR
    Floors
    MassU-1.825NRU-1.825NRU-1.825NR
    Steel joistU-1.986NRU-1.986NRU-1.986NR
    Wood framed and otherU-1.599NRU-1.599NRU-1.599NR
    Slab-on-grade floors
    UnheatedF-1.264NRF-1.264NRF-1.264NR
    HeatedF-1.766R-1.3 for 300 mmF-1.766R-1.3 for 300 mmF-1.766R-1.3 for 300 mm
    Opaque doors
    SwingingU-3.975U-2.839U-3.975
    NonswingingU-8.233U-2.839U-8.233
    FenestrationAssembly Max. UAssembly Max. SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-2.56cE,W, &S-0.25 N-0.351.10U-2.56cE,W, &S-0.25 N-0.351.10U-4.75NRNR
    Metal framing, fixedU-2.91cU-2.91cU-6.13
    Metal framing,operableU-3.32cU-3.32cU-6.13
    Metal framing, entrance doorU-5.62cU-5.62cU-5.62c
    Skylight, 0% to 3% of roof
    All typesU-4.260.35NRU-4.260.35NRU-10.22NRNR
    1. *The following definitions apply: c.i. = continuous insulation (see ANSI/ASHRAE/IES Standard 90.1-2013, Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).

    3. b.Exception to ANSI/ASHRAE/IES Standard 90.1-2013, Section 5.5.3.2, applies for mass walls above grade.

    4. c.For locations in Climate Zone 1 with a cooling design temperature of 35°C and greater, the maximum U-factors for vertical fenestration shall be 10% lower than those in ANSI/ASHRAE/IES Standard 90.1-2013, Section 5.5.4.3.

    TABLE E-2 (Supersedes Table 5.5-2 in ANSI/ASHRAE/IES Standard 90.1)

    Building Envelope Requirements for Climate Zone 2 (A,B)* (SI)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.220R-4.4 c.i.U-0.220R-4.4 c.i.U-0.982R-0.9 c.i.
    Metal buildingaU-0.233R-1.8 + R-3.3 FCU-0.233R-1.8 + R-3.3 FCU-0.545R-2.8
    Attic and otherU-0.153R-6.7U-0.153R-6.7U-0.300R-3.3
    Walls, above grade
    MassU-0.857bR-1.0 c.i.bU-0.701R-1.3 c.i.U-3.293NR
    Metal buildingU-0.533R-0 + R-1.7 c.i.U-0.533R-0 + R-1.7 c.i.U-0.920R-2.3
    Steel framedU-0.479R-2.3 + R-0.7 c.i.U-0.365R-2.3 + R-1.3 c.i.U-0.705R-2.3
    Wood framed and otherU-0.504R-2.3U-0.504R-2.3U-0.504R-2.3
    Wall, below grade
    Below-grade wallC-6.473NRC-6.473NRC-6.473NR
    Floors
    MassU-0.606R-1.9U-0.496R-1.5U-1.825NR
    Steel joistU-0.214R-5.3U-0.214R-5.3U-0.390R-2.3
    Wood framed and otherU-0.188R-5.3U-0.188R-5.3U-0.376R-2.3
    Slab-on-grade floors
    UnheatedF-1.264NRF-1.264NRF-1.264NR
    HeatedF-1.558R-1.8 for 600 mmF-1.489R-2.6 for 600 mmF-1.766R-1.3 for 300 mm
    Opaque doors
    SwingingU-3.975U-2.839U-3.975
    NonswingingU-2.839U-2.839U-8.233
    FenestrationAssembly Max. UAssembly Max. SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-2.04E,W, &S-0.25 N-0.351.10U-2.04E,W, &S-0.25 N-0.351.10U-4.75NRNR
    Metal framing, fixedU-2.91U-2.91U-6.13
    Metal framing,operableU-3.32U-3.32U-6.13
    Metal framing, entrance doorU-4.24U-3.94U-4.24
    Skylight, 0% to 3% of roof
    All typesU-3.690.35NR3.69035NRU-10.22NRNR
    1. * The following definitions apply: c.i. = continuous insulation (see ANSI/ASHRAE/IES Standard 90.1-2013, Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).

    3. b.Exception to ANSI/ASHRAE/IES Standard 90.1-2013, Section 5.5.3.2, applies for mass walls above grade.

    TABLE E-3 (Supersedes Table 5.5-3 in ANSI/ASHRAE/IES Standard 90.1)

    Building Envelope Requirements for Climate Zone 3 (A,B,C)* (SI)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.220R-4.4 c.i.U-0.220R-4.4 c.i.U-0.677R-1.3 c.i.
    Metal buildingaU-0.233R-1.8 + R-3.3 FCU-0.233R-1.8 + R-3.3 FCU-0.545R-2.8
    Attic and otherU-0.153R-6.7U-0.153R-6.7U-0.300R-3.3
    Walls, above grade
    MassU-0.701R-1.3 c.i.U-0.592R-1.7 c.i.U-3.293NR
    Metal buildingU-0.533R-0 + R-1.7 c.i.U-0.410R-0 + R-2.3 c.i.U-0.920R-2.3
    Steel framedU-0.435R-2.3 + R-0.9 c.i.U-0.365R-2.3 + R-1.3 c.i.U-0.705R-2.3
    Wood framed and otherU-0.504R-2.3U-0.365R-2.3 + R-0.7 c.i. or R-3.5U-0.504R-2.3
    Wall, below grade
    Below-grade wallC-6.473NRC-6.473NRC-6.473NR
    Floors
    MassU-0.420R-1.8 c.i.U-0.420R-1.8 c.i.U-0.780R-0.7 c.i.
    Steel joistU-0.214R-5.3U-0.214R-5.3U-0.296R-3.3
    Wood framed and otherU-0.188R-5.3U-0.188R-5.3U-0.288R-3.3
    Slab-on-grade floors
    UnheatedF-1.264NRF-0.935R-1.8 for 600 mmF-1.264NR
    HeatedF-1.489R-2.6 for 600 mmF-1.489R-2.6 for 600 mmF-1.766R-1.3 for 300 mm
    Opaque doors
    SwingingU-3.975U-2.839U-3.975
    NonswingingU-2.839U-2.839U-8.233
    FenestrationAssembly Max. UAssembly Max. SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-1.79E,W, &S-0.25 N-0.351.10U-1.79E,W, &S-0.25 N-0.351.10U-4.45NRNR
    Metal framing, fixedU-2.56U-2.56U-6.13
    Metal framing,operableU-3.07U-3.07U-6.13
    Metal framing, entrance doorU-3.94U-3.48U-3.94
    Skylight, 0% to 3% of roof
    All typesU-3.120.35NRU-3.120.35NRU-9.65NRNR
    1. *The following definitions apply: c.i. = continuous insulation (see ANSI/ASHRAE/IES Standard 90.1-2013, Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).

    TABLE E-4 (Supersedes Table 5.5-4 in ANSI/ASHRAE/IES Standard 90.1) Building Envelope Requirements for Climate Zone 4 (A,B,C)* (SI)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.164R-6.2 c.i.U-0.164R-6.2 c.i.U-0.475R-2.1 c.i.
    Metal buildingaU-0.189R-2.3 + R-4.4 c.i.U-0.189R-2.3 + R-4.4 c.i.U-0.419R-0 + R-2.3 c.i.
    Attic and otherU-0.107R-10.6U-0.107R-10.6U-0.174R-6.7
    Walls, above grade
    MassU-0.532R-2.01U-0.460R-2.29U-3.293NR
    Metal buildingU-0.307R-1.9 + R-2.3 c.i.U-0.256R-2.8 + R-2.8 c.i.U-0.828R-0 + R-1.1 c.i.
    Steel framedU-0.327R-2.3 + R-2.2 c.i.U-0.327R-2.3 + R-2.2 c.i.U-0.634R-2.3+ R-0.7 c.i.
    Wood framed and otherU-0.327R-2.3 + R-1.3 c.i.U-0.327R-2.3 + R-1.3 c.i.U-0.455R-2.3+ R-0.7 c.i.
    Wall, below grade
    Below-grade wallC-0.608R-1.8 c.i.C-0.4703R-2.2 c.i.C-6.473NR
    Floors
    MassU-0.291R-2.9 c.i.U-0.2607R-3.3 c.i.U-0.547R-1.5 c.i.
    Steel joistU-0.194R-6.7U-0.194R-6.7U-0.266R-5.3
    Wood framed and otherU-0.169R-6.7U-0.169R-6.7U-0.261R-5.3
    Slab-on-grade floors
    UnheatedF-2.658R-3.5 for 1200 mmF-2.658R-3.5 for 1200 mmF-1.264NR
    HeatedF-4.309R-3.5 for 1200 mmF-3.5171R-2.6 full slabF-4.601R-3.5 for 1200 mm
    Opaque doors
    SwingingU-2.556U-2.556U-3.578
    NonswingingU-2.556U-2.556U-7.412
    FenestrationAssembly Max. UAssembly Max. SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-1.79S-0.40 E&W-0.36 N-0.501.10U-1.79S-0.40 E&W-0.36 N-0.501.10U-2.61NRNR
    Metal framing, fixedU-2.15U-2.15U-3.73
    Metal framing,operableU-2.56U-2.56U-4.14
    Metal framing, entrance doorU-3.94U-3.48U-3.94
    Skylight, 0% to 3% of roof
    All typesU-2.840.40NRU-2.840.40NRU-6.53NRNR
    1. *The following definitions apply: c.i. = continuous insulation (see ANSI/ASHRAE/IES Standard 90.1-2013, Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).

    TABLE E-5 (Supersedes Table 5.5-5 in ANSI/ASHRAE/IES Standard 90.1)

    Building Envelope Requirements for Climate Zone 5 (SI)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.164R-6.2 c.i.U-0.164R-6.2 c.i.U-0.322R-3.0 c.i.
    Metal buildingaU-0.189R-2.3 + R-4.4 c.i.U-0.189R-2.3 + R-4.4 c.i.U-0.419R-0 + R-2.3 c.i.
    Attic and otherU-0.107R-10.6U-0.107R-10.6U-0.174R-6.7
    Walls, above grade
    MassU-0.460R-2.29U-0.409R-2.68U-0.772R-1.32
    Metal buildingU-0.256R-2.8 + R-2.8 c.i.U-0.256R-2.8 + R-2.8 c.i.U-0.481R-1.9 + R-1.1 c.i.
    Steel framedU-0.281R-2.3 + R-2.2 c.i.U-0.281R-2.3 + R-2.2 c.i.U-0.429R-2.3+ R-1.3 c.i.
    Wood framed and otherU-0.261R-2.3 + R-2.2 c.i.U-0.261R-2.3 + R-2.2 c.i.U-0.455R-2.3+ R-0.7 c.i.
    Wall, below grade
    Below-grade wallC-0.608R-1.8 c.i.C-0.4703R-2.2 c.i.C-6.473NR
    Floors
    MassU-0.291R-2.9 c.i.U-0.2607R-3.3 c.i.U-0.547R-1.5 c.i.
    Steel joistU-0.194R-6.7U-0.194R-6.7U-0.266R-5.3
    Wood framed and otherU-0.169R-6.7U-0.169R-6.7U-0.261R-5.3
    Slab-on-grade floors
    UnheatedF-2.658R-3.5 for 1200 mmF-2.607R-3.5 for 1200 mmF-1.264NR
    HeatedF-3.517R-2.6 full slabF-3.5171R-2.6 full slabF-4.601R-3.5 for 1200 mm
    Opaque doors
    SwingingU-2.556U-2.556U-3.578
    NonswingingU-2.556U-2.556U-7.412
    FenestrationAssembly Max. UAssembly Max. SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-1.64S-0.40 E&W-0.36 N-0.501.10U-1.64S-0.40 E&W-0.36 N-0.501.10U-2.30NRNR
    Metal framing, fixedU-2.15U-2.15U-3.17
    Metal framing,operableU-2.56U-2.56U-3.58
    Metal framing, entrance doorU-3.94U-3.48U-3.94
    Skylight, 0% to 3% of roof
    All typesU-2.840.40NRU-2.840.40NRU-5.56NRNR
    1. *The following definitions apply: c.i. = continuous insulation (see ANSI/ASHRAE/IES Standard 90.1-2013, Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).

    TABLE E-6 (Supersedes Table 5.5-6 in ANSI/ASHRAE/IES Standard 90.1)

    Building Envelope Requirements for Climate Zone 6 (A,B)* (SI)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.164R-6.2 c.i.U-0.164R-6.2 c.i.U-0.322R-3.0 c.i.
    Metal buildingaU-0.158R-1.9 + R-5.6 c.i.U-0.148R-3.3 + R-5.6 c.i.U-0.307R-1.9 + R-2.3 c.i.
    Attic and otherU-0.107R-10.6U-0.107R-10.6U-0.174R-6.7
    Walls, above grade
    MassU-0.409R-2.68U-0.363R-3.45U-0.772R-1.32
    Metal buildingU-0.256R-2.8 + R-2.8 c.i.U-0.256R-2.8 + R-2.8 c.i.U-0.481R-1.9 + R-1.1 c.i.
    Steel framedU-0.250R-2.3 + R-2.7 c.i.U-0.250R-2.3 + R-2.7 c.i.U-0.429R-2.3+ R-1.3 c.i.
    Wood framed and otherU-0.261R-2.3 + R-2.2 c.i.U-0.261R-2.3 + R-2.2 c.i.U-0.455R-2.3+ R-0.7 c.i.
    Wall, below grade
    Below-grade wallC-0.470R-2.2 c.i.C-0.3221R-3.1 c.i.C-0.6083R-1.8 c.i.
    Floors
    MassU-0.261R-3.3 c.i.U-0.2607R-3.3 c.i.U-0.445R-1.8 c.i.
    Steel joistU-0.164R-8.6U-0.164R-8.6U-0.266R-5.3
    Wood framed and otherU-0.138R-6.7+ R-1.3 c.i.U-0.138R-6.7+ R-1.3 c.i.U-0.261R-5.3
    Slab-on-grade floors
    UnheatedF-2.607R-3.5 for 1200 mmF-2.219R-2.6 full slabF-1.264NR
    HeatedF-3.517R-2.6 full slabF-3.4302R-2.6 full slabF-4.396R-3.5 for 1200 mm
    Opaque doors
    SwingingU-2.556U-2.556U-3.578
    NonswingingU-2.556U-2.556U-2.556
    FenestrationAssembly Max. UAssembly Max. SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-1.64S-0.40 E&W-0.36 N-0.501.10U-1.64S-0.40 E&W-0.36 N-0.501.10U-2.30NRNR
    Metal framing, fixedU-2.15U-2.15U-2.61
    Metal framing,operableU-2.56U-2.56U-3.02
    Metal framing, entrance doorU-3.94U-3.48U-3.94
    Skylight, 0% to 3% of roof
    All typesU-2.840.40NRU-2.840.40NRU-4.83NRNR
    1. *The following definitions apply: c.i. = continuous insulation (ANSI/ASHRAE/IES Standard 90.1-2013, see Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).

    TABLE E-7 (Supersedes Table 5.5-7 in ANSI/ASHRAE/IES Standard 90.1)

    Building Envelope Requirements for Climate Zone 7* (SI)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.143R-7.0 c.i.U-0.143R-7.0 c.i.U-0.199R-4.9 c.i.
    Metal buildingaU-0.148R-3.3 + R-5.6 c.i.U-0.148R-3.3 + R-5.6 c.i.U-0.189R-2.3 + R-4.4 c.i.
    Attic and otherU-0.087R-12.5U-0.087R-12.5U-0.138R-8.6
    Walls, above grade
    MassU-0.363R-3.45U-0.363R-3.45U-0.629R-1.67
    Metal buildingU-0.225R-3.3 + R-3.3 c.i.U-0.225R-3.3 + R-3.3 c.i.U-0.368R-2.3 + R-1.71 c.i.
    Steel framedU-0.250R-2.3 + R-2.7 c.i.U-0.215R-2.3 + R-3.3 c.i.U-0.327R-2.3+ R-2.2 c.i.
    Wood framed and otherU-0.261R-2.3 + R-2.2 c.i.U-0.261R-2.3 + R-2.2 c.i.U-0.327R-2.3+ R-1.3 c.i.
    Wall, below grade
    Below-grade wallC-0.322R-3.1 c.i.C-0.3221R-3.1 c.i.C-0.6083R-1.8 c.i.
    Floors
    MassU-0.215R-4.4 c.i.U-0.2147R-4.4 c.i.U-0.378R-2.2 c.i.
    Steel joistU-0.164R-8.6U-0.164R-8.6U-0.266R-5.3
    Wood framed and otherU-0.138R-6.7+ R-1.3 c.i.U-0.138R-6.7+ R-1.3 c.i.U-0.261R-5.3
    Slab-on-grade floors
    UnheatedF-2.607R-3.5 for 1200 mmF-2.219R-2.6 full slabF-1.264NR
    HeatedF-3.430R-2.6 full slabF-3.4302R-2.6 full slabF-4.396R-3.5 for 1200 mm
    Opaque doors
    SwingingU-2.556U-2.556U-3.578
    NonswingingU-2.556U-2.556U-2.556
    FenestrationAssembly Max. UAssembly Max. SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-1.64S-0.45 E&W-0.41 N-0.551.10U-1.64S-0.45 E&W-0.41 N-0.551.10U-1.64NRNR
    Metal framing, fixedU-1.94U-1.94U-1.94
    Metal framing,operableU-2.04U-2.04U-2.25
    Metal framing, entrance doorU-3.94U-3.48U-3.94
    Skylight, 0% to 3% of roof
    All typesU-2.84NRNRU-2.84NRNRU-4.83NRNR
    1. *The following definitions apply: c.i. = continuous insulation (see ANSI/ASHRAE/IES Standard 90.1-2013, Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).

    TABLE E-8 (Supersedes Table 5.5-8 in ANSI/ASHRAE/IES Standard 90.1)

    Building Envelope Requirements for Climate Zone 8* (SI)

    NonresidentialResidentialSemiheated
    Opaque ElementsAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-ValueAssembly MaximumInsulation Min. R-Value
    Roofs
    Insulation entirely above deckU-0.143R-7.0 c.i.U-0.143R-7.0 c.i.U-0.199R-4.9 c.i.
    Metal buildingaU-0.133R-2.8 + R-6.7 c.i.U-0.133R-2.8 + R-6.7 c.i.U-0.189R-2.3 + R-4.4 c.i.
    Attic and otherU-0.087R-12.5U-0.087R-12.5U-0.138R-8.6
    Walls, above grade
    MassU-0.245R-3.87 c.i.U-0.245R-3.87 c.i.U-0.532R-2.01
    Metal buildingU-0.199R-3.3 + R-3.9 c.i.U-0.199R-3.3 + R-3.9 c.i.U-0.307R-1.9 + R-2.3 c.i.
    Steel framedU-0.189R-2.3 + R-4.4 c.i.U-0.189R-2.3 + R-4.4 c.i.U-0.327R-2.3+ R-2.2 c.i.
    Wood framed and otherU-0.164R-2.3 + R-4.4 c.i.U-0.164R-2.3 + R-4.4 c.i.U-0.261R-2.3+ R-2.2 c.i.
    Wall, below grade
    Below-grade wallC-0.322R-3.1 c.i.C-0.3221R-3.1 c.i.C-0.6083R-1.8 c.i.
    Floors
    MassU-0.194R-4.8 c.i.U-0.1943R-4.8 c.i.U-0.327R-2.6 c.i.
    Steel joistU-0.164R-8.6U-0.164R-8.6U-0.266R-5.3
    Wood framed and otherU-0.138R-6.7+ R-1.3 c.i.U-0.138R-6.7+ R-1.3 c.i.U-0.169R-6.7
    Slab-on-grade floors
    UnheatedF-2.219R-2.6 full slabF-2.167R-2.6 full slabF-2.7605R-3.5 for 1200 mm
    HeatedF-3.430R-2.6 full slabF-1.9068R-4.4 full slabF-4.396R-3.5 for 1200 mm
    Opaque doors
    SwingingU-2.556U-2.556U-2.556
    NonswingingU-2.556U-2.556U-2.556
    FenestrationAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGCAssembly Max. UAssembly Max.SHGCAssembly Min.VT/SHGC
    Vertical fenestration,0% to 40% of wall(for all frame types)(for all frame types)(for all frame types)
    Nonmetal framing, allU-1.64S-0.45 E&W-0.41 N-0.551.10U-1.64S-0.45 E&W-0.41 N-0.551.10U-1.64NRNR
    Metal framing, fixedU-1.94U-1.94U-1.94
    Metal framing,operableU-2.04U-2.04U-2.25
    Metal framing, entrance doorU-3.94U-3.48U-3.94
    Skylight, 0% to 3% of roof
    All typesU-2.84NRNRU-2.84NRNRU-4.83NRNR
    1. *The following definitions apply: c.i. = continuous insulation (see ANSI/ASHRAE/IES Standard 90.1-2013, Section 3.2), FC = filled cavity (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.5), Ls = liner system (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2.4), NR = no (insulation) requirement.

    2. a.When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see ANSI/ASHRAE/IES Standard 90.1-2013, Section A2.3.2).